Troubleshooting Guide 

Multi-Voltage On/Off Electric Actuators  

5610/5616 Series

 

IOM 

5610 

5616 

TSG On/Off

 

Electrical Wiring Diagram for 5610/5616 series On-Off Actuators

 

Before connecting 
power, confirm 
correct voltage is 
being applied 

CLOSED 

OPEN 

Customer 
Supplied 
Relay or 
Switch 

Power  Connection 

LS1 

OPEN 

Signal 

LS2 
CLOSED 
Signal 

Position Confirmation       

Limit Switches   

 

N / - 

L / + 

LS1  

N / - 

LS2   

N / - 

COM 

L / + 

Earth 

Ground 

Power       

VAC or VDC 

Wiring Position Confirmation Limit Switches:  

Two  auxiliary  dry  contact  limit  switches  are  provided  to  confirm  the    
actuator  (valve)  open  and  closed  position.  Use  of  these  switches  is       
optional and not required for the actuator to function properly. Switch 
rating  3A@125/250VAC,  30VDC  resistive  load.  Do  not  connect  a 
ground to this connector. 

PIN 1: Common 

PIN 2: Output Signal to confirm Closed Position 

PIN 3: Output Signal to confirm Open Position 

Wire Identification for Optional Prewired DIN Cables 

PIN 1 - Brown  

PIN 3 - Black  

PIN 2 - Blue 

GROUND  - Green/Yellow 

Wiring Main Power Connection:  

Power  is  connected  to  the  actuator  via  the  large  gray  DIN  plug        
connector. Wires are connected to screw terminals located inside the 
connector. User/installer to supply a SPDT mechanical relay or a 3-way 
2-position switch to control the actuator open and closed position. 

Power supplied to PIN 1 and PIN 2: CLOSED POSITION 

Power supplied to PIN 1 and PIN 3: OPEN POSITION 

Ground: Connect the flat pin on DIN connector to earth ground  

 

NOTES:  

1.  The Neutral (AC voltages) or Negative (DC voltages) must be connected 

to PIN 1. The actuator is polarity sensitive. 

2.  Power  should  be  maintained,  either  in  the  open  or  closed  position  to 

activate the internal heater. This heater will help prevent condensation 
build up inside the actuator.  

3.  Actuator should have it’s own fused and isolated circuit. Do not connect 

actuators in parallel or on the same circuit with other equipment.     

4.  Supply  voltage  to  24  volt  actuators  should  not  exceed  25.2  volts          

(24 volts +5%). 

DIN Plug Connectors 

1. Seal 

2. Screw terminal block (Pins 1, 2, 3 & G) 

3. Connector housing 

4. Retainer screw 

5. Cable retainer gland 

Power 
Connector 

Position  
confirmation 
switches 