8
2.7
The appliance must not be fitted directly against a combustible
wall.
If the appliance is to be fitted against a wall with combustible cladding,
such materials must be removed from the area covered by the metal outer
surround of the appliance (see figure 1). We suggest that the actual surround is
used as a template to mark the area for combustible cladding removal.
•
The appliance can be fitted to a purpose made proprietary class “O” 150°C
surround.
•
The cut-out area in the surround should be between the size limits shown in
figure 1.
2.8
The minimum allowable distance from the outside edge of the
metal front surround of the appliance to a corner wall having
combustible materials is 178mm at either side (see figure 2).
2.9
The minimum height from the top surface of the hearth to the
underside of any shelf made from wood or other combustible
materials is as follows:-
•
For a shelf up to 150mm deep
•
Minimum height = 750mm.
•
For a shelf deeper than 150mm
•
Minimum height = 750mm + 12.5mm for every 25mm
depth over 150mm.
2.10
Note that soft wall coverings (e.g. embossed vinyl, etc.) are
easily affected by heat. They may scorch or become discoloured
when close to a heating appliance. Please bear this in mind when
installing.
2.11
The appliance must not be installed in any room which contains a bath or
shower or where steam is regularly present.
2.12
An extractor fan may only be used in the same room as this appliance, or
in any area from which ventilation for the appliance is taken, if it does not affect
the safe performance of the appliance. Note the spillage test requirements
detailed further on in this manual. If the extractor fan is likely to affect the
appliance, the appliance must not be installed unless the fan is permanently
disconnected.
2.13
A fan-powered flue system tends to depressurise the room containing the
appliance. In the United Kingdom no additional ventilation should normally be
required. In the Republic of Ireland permanent ventilation must comply with
the rules in force. In exceptional circumstances however, the spillage check (See
further on in this guide) may indicate a need for further ventilation in order to
ensure that there is adequate air replacement. If necessary seek expert advice.
2.14
Make sure that the damp course or any electrical wiring, piping etc in the
wall is not affected when cutting the flue box or spigot installation hole.
2.15
Any gas supply pipe installed in the wall, floor or cavity of a cavity wall
must be continuous and enclosed in a factory fitted gas tight sleeve (Ref: Gas
safety (Installation & Use) Regulations 1994 as amended & Certificate of
exemption no.1 1996).
Fig. 2