Venting

KEY

VENT TERMINAL LOCATIONS - MINIMUM DISTANCES

MINIMUM 

CLEARANCE

 

Inches

Cm

A

Clearance above grade, verandah, porch, deck or balcony

1

0

B

Clearance to window or door that may be opened

1

0

C

Clearance to permanently closed window (recommended to prevent 

condensation on window) 

1

0

D

Vertical clearance to ventilated soffit located above the terminal within a 

horizontal distance of 2 feet (60 cm) from the center-line of the terminal 

18

E

Clearance to unventilated soffit

1

0

F

Clearance to outside corner

1

0

G

Clearance to inside corner

1

0

H

Horizontal clearance to center-line of meter/regulator assembly located within 15 

feet (4.6 m) below the terminal

90

I

Clearance to service regulator vent outlet 

90

J

Clearance to non-mechanical air supply inlet to the building or the combustion air 

inlet to any other appliance

1

0

K

Clearance to a mechanical air supply inlet

180

L

Clearance above paved sidewalk or a paved driveway located on public property

Note

A vent must not terminate directly above a sidewalk or paved driveway, 

which is located between two single-family dwellings and serves both dwellings

8

10

M

Clearance under a verandah, porch, deck or balcony

Only permitted if veranda, porch, deck or balcony is fully open on a minimum of 2 

sides beneath the floor

1

0

Note:

  Local codes and regulations may require different clearances.

Horizontal

Vent 

Termination

The vent terminal must be located on an outside wall or through the roof.

This direct vent appliance is designed to operate when an undisturbed airflow hits the 

outside vent terminal from any direction. 

The minimum clearances from this terminal that must be maintained when located on an 

outside wall are shown in the figure below. Any reduction in these clearances could result 

in a disruption of the airflow or a safety hazard. Local codes or regulations may require 

greater clearances.

The vent terminal must not be recessed into a wall or siding.

The vent terminal should be positioned where it will not be covered by snowdrifts.

Sidewall vent terminations within 7’ of grade require a terminal guard when using a 551DVK.

Summary of Contents for Madrona MF28EN

Page 1: ...liance is a domestic room heating appliance It must not be used for any other purposes such as drying clothes etc This appliance is suitable for installation in a bedroom or bed sitting room Massachus...

Page 2: ...he installation or maintenance of your heater and assumes no responsibility for any consequential damage s Thank You For purchasing a Valor Madrona Your new radiant gas heater is a technical appliance...

Page 3: ...e Preparation 16 Supply Gas 21 Ceramic Logs 22 Window Refitting 23 Initial Remote Control Set up 23 Operation Check Aeration Settings Adjustment 24 Front Top Installation 24 Remote Control Handset Wal...

Page 4: ...tion manual NO OTHER vent system or components MAY BE USED This gas fireplace and vent assembly MUST be vented directly to the outside and MUST NEVER be attached to a chimney serving a separate solid...

Page 5: ...e the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors a In the event that the side wall hor...

Page 6: ...s and 2 A complete parts list for the venting system design or venting system d MANUFACTURER REQUIREMENTS GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED When the manufacturer of a Product Approved side wal...

Page 7: ...00 feet Input Maximum Btu h 28 000 28 000 Input Minimum Btu h 12 000 14 500 Manifold Pressure in w c 3 75 10 2 Minimum Supply Pressure in w c 5 0 11 0 Maximum Supply Pressure in w c 11 0 14 0 Main Bur...

Page 8: ...Exhaust collar 4 17 7 8 28 1 2 23 7 1 2 27 1 2 14 30 1 2 25 1 8 Center line Hearth Requirements This unit is approved for mounting directly on combustible wood flooring If installed directly on carpet...

Page 9: ...stove Min 5 between combustible wall and rear of stove 17 7 8 28 1 2 Clearances 40 1 2 minimum 43 1 2 minimum 26 maximum Alcove clearances Maximum 26 from wall for projection of combustible mantel or...

Page 10: ...frame a minimum of 10 x 10 opening to ensure that the insulation is kept clear of the vent pipe Also seal all joints between the wall plates the wall and the vent pipe Follow the installation instruct...

Page 11: ...Through wall without vertical rise Typical Venting Components See list of approved venting pipes and accessories on pages 34 35 Through wall with vertical rise Through roof Maximum pipe length 24 stra...

Page 12: ...45 90 can be used Each 90 elbow installed on the horizontal plane is equivalent to a 3 horizontal pipe therefore 3 must be subtracted from allowable horizontal run 45 elbow is equivalent to 18 horizon...

Page 13: ...n is based on laboratory tests The ideal restrictor position may vary slightly especially when the vent pipe length is near the limits of the acceptable configurations for each type of restrictors The...

Page 14: ...located on public property Note A vent must not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings 84 210 M Clearance...

Page 15: ...2 to 10 12 2 5 Over 10 12 to 11 12 3 25 Over 11 12 to 12 12 4 Over 12 12 to 14 12 5 Venting Packs Contents Appliance Castings The Madrona Stove is supplied in three 3 cartons In one carton is the engi...

Page 16: ...ch 1 Appliance s foot print Casting Base Release the spring bolts at top and bottom of the window by pushing and turning 1 4 turn Lift the window and set it aside in a safe place to avoid damage Remov...

Page 17: ...n see detail below Center the engine using the holes at front of the base as guidelines Casting Side Panels On the casting side panels release the top and bottom screws Drop a hinge pin on the back co...

Page 18: ...ket Tighten the top and bottom screws Adjust the engine as required and fix it to the casting base at bottom of its side brackets with the nuts and bolts provided 1 Receiver hooked to burner pipes Lig...

Page 19: ...port LPG and then the burner Using 3 screws fix the fan to the firebox bracket Fix the fan control box bracket provided to the control box with 2 screws Fix the bracket with the control box attached t...

Page 20: ...appliance 22 screws of the intake plate and 2 rear screws of the collar Exhaust collar 8 screws NOTE The gaskets are glued to the engine or the intake plate it is not necessary to separate them from...

Page 21: ...ve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1 2 psig 3 5kPa The appliance must be isolated from the gas supply p...

Page 22: ...hind front log retainers LPG ONLY Drop Rear Log into place centered side to side against back support Front Log locating pins Front Log support LPG ONLY Place LH Cross Log onto locating pins 5 4 3 1 2...

Page 23: ...in the remote control receiver and handset The receiver is located left of the control valve under the burner module With a sharp object press and hold the receiver s reset button until you hear two...

Page 24: ...The burner is equipped with an adjustable shutter to control primary aeration See the figures below The shutter is factory set to an aeration gap which will give optimum performance for the vast majo...

Page 25: ...light switch plate IMPORTANT The location of the remote control handset is important to assure proper temperature regulation To obtain a constant temperature we recommend that the handset should be b...

Page 26: ...t outwards see page 16 Set aside in a safe place to avoid damage To refit the window place it on its frame and hold it in place while pushing and turning its fastening studs 90 degrees Then apply ligh...

Page 27: ...erent ways IMPORTANT BEFORE YOU BEGIN please note that on this system the settings of time temperature and automatic ON OFF can only be programmed when the function display is flashing Be patient when...

Page 28: ...or to go to pilot Standby position For fine adjustments tap the and buttons Quick Flame Adjustment If or are pressed for 0 5 sec the flame will increase to maximum or decrease to the pilot Standby pos...

Page 29: ...turn off when you go to bed at night P2 stop time If you wish to set only one time period at which your fireplace will turn on and off program P2 start time and P2 stop time for the same time as P1 s...

Page 30: ...o turn off your fireplace and cannot do it with the remote control handset misplaced lost dead batteries etc you can turn off the appliance with the manual switch located on the right hand side of the...

Page 31: ...step 3 AUTOMATIC IGNITION Fig 1 Locate the pilot Fig 3 inside of firebox at left hand side ON OFF switch 1 in ON position MAN knob 2 in ON position set Flame Adjustment knob 3 to lowest setting On the...

Page 32: ...32 Wiring Diagram...

Page 33: ...dard Black MFCS02 Madrona Stove Kit Majolica Brown 551DVK Direct Vent Kit for horizontal terminations with vertical rise See also venting accessories listed on pages 34 35 555CFK Circulating Fan Kit w...

Page 34: ...6DVA VCE Co linear 3PDVCV HS C33U 99 559CLT HS C33F 1313 Snorkel 14 Rise 46DVA SNK14 4DT ST14 Snorkel 36 Rise 46DVA SNK36 4DT ST36 Vent Adapters Couplers Universal Adapter 3 Flex Coupler 2150 Co linea...

Page 35: ...T 48 B SV4LB48 Flashings Roof Flashing 0 12 6 12 46DVA F6 4DT AF6 SV4FA Roof Flashing 7 12 12 12 46DVA F12 4DT AF12 SV4B Flat Roof Flashing 46DVA FF SV4F Various Venting System Parts Wall Thimble 46DV...

Page 36: ...ther household equipment or appliances iii Damage due to chemicals dampness condensation or sulphur in the fuel supply lines which exceeds industry standards This warranty does not cover glass log bre...

Page 37: ...Majolica 1 Base 4000926AH 4000926MJ 6 Fret 4000935AH 4000935MJ 2 Top Panel 4000928AH 4000928MJ 7 LH Side Panel 4000931AH 4000931MJ 3 Leg 4 4000929AH 4000929MJ 8 Infill Plate 4000927AH 4000927MJ 4 RH...

Page 38: ...923 44 Pipe Valve to Main Burner 4000600 17 Firebox Assembly 4000920 45 Tube Nut 220K558 18a Rear Log Support 4000621 46 Valve Mount 4000141 18b Rear Log Support LPG 4001456 47a Pilot Assembly NG 4000...

Page 39: ...6 7 8 9 10 2a 2b 1 50 75 11 12 13 14 15 16 18a 19a 19b 20 21 22 23 24b 27 28 29 30 31 32 33 34 35a 35b 36 37 38 39 40 41 17 25 31 47a 47b 49 50 48 42 46 43 44 45 53 51 52 54a 54b 55 56 30e 30a 30d 57...

Reviews: