INSTALLER’S GUIDE
Page 23
Figure 26. Smoke match tube position
11.2
Check For Spillage
A spillage check must be made
before leaving the installed
appliance with the customer. Make
this check with the appliance fully
installed with the ceramic fuel
effects and front surround in
position.
1.
Close all doors and windows in the
room containing the appliance.
2.
Light the appliance and turn the
control knob to “HIGH”.
3.
Leave the appliance on for five minutes.
4.
Place the smoke match tube into the convection box at the right hand side and
immediately below the black top cross member. Angle it at approximately 45° to the
horizontal.
Insert the tube so that the neck of its flared end touches the inside surface of the edge of
the cross member - See figure 26.
Keeping the neck of flared end in contact with the edge of the cross member, slide the
tube to the left until you feel it enter the notch in the edge of the cross member. Make
sure that the tube is pointed upwards at 45º to the horizontal. The installation is
satisfactory if the smoke is drawn into the appliance. If the smoke is not drawn into the
appliance leave the appliance alight at the maximum setting for a further ten minutes and
then repeat the test. If the smoke is still not drawn into the appliance inspect the sealing
to the fireplace surround. If the sealing is satisfactory but the appliance is installed with
the flue restrictor (see section 7.1) remove the restrictor, reseal the appliance and retest. If
smoke is still not drawn into the appliance
disconnect the appliance and seek expert
advice.
5.
If the above test is satisfactory open all internal connecting doors, hatches, etc. in the
room. Keep all doors and windows that open to the outside of the building closed.
Recheck for spillage as above. If an extractor fan is installed in the same room as the
appliance or a connecting room, check that spillage does not occur with the fan operating
and all doors and other openings between the fan and the appliance open.
If the smoke is drawn into the appliance, continue with the installation. If the test is not
satisfactory
disconnect the appliance and advise the customer of the cause of failure
.