3

Apply warning plate supplied with fireplace
to inside of existing masonry fireplace

Prepare existing masonry fireplace

A few points must be considered before inserting the 

gas fireplace into an existing fireplace cavity. Verify 

the structural integrity of the existing fireplace before 

installing the gas insert and liners. Components that are 

bolted or screwed on such as dampers or baffles may 

be removed to accommodate the installation of the gas 

fireplace. Check with local authorities if in doubt.

Clean Fireplace and Chimney

Have the chimney swept and the fireplace cavity 

including ash dumps and clean-outs cleaned before 

installing the gas fireplace and vent liners. Any creosote 

or soot residue remaining in the fireplace cavity chimney 

or clean-out may cause odors or stains once the gas 

fireplace is installed. Consult with chimney sweep for 

information on how best to clean.

Existing Dampers

Dampers in masonry fireplaces must be fixed open and 

may remain in place.

Gas Line Routing

Plan the routing of the gas line before proceeding. 

See 

Dimensions

 section of the heater installation 

manual for detailed location of gas inlet. Also, take into 

consideration whether or not a fan or shut-off valve will 

interfere when planning routing of the gas line.

Existing Glass Doors and Wire Screens

Existing glass doors must be permanently removed

prior to installing the gas fireplace.

Combustible Mantels

Combustible mantel clearances must conform to those 

required for the original solid-fuel fireplace into which 

the gas fireplace is being installed.

Attach Warning Conversion Plate to Existing 

Fireplace (label supplied loose with 739 heater)

Attach the “This fireplace has been converted...” label 

to 

the existing fireplace

 using screws or other mechanical 

means and store any removed parts in back of the 

existing fireplace for future use.

Exterior view

Note: Limited 
overlap of 1-1/2”
between collar and
mounting flange

Exhaust

Approx 3-1/2”

Approx 7-1/2”

Top view

Install terminal

Considerations

•  Intake and exhaust liners must correspond between 

heater and sidewall termination.

•  Ensure liners do not sag and are not crimped when 

installing.

•  Do not bend liners less than 3” radius.

1.  Carefully drill or chisel a hole at the appropriate 

height into the outside wall of the fireplace using the 

diagram shown below as a guide.

Alternately, a standard cast iron chimney clean-out 

frame may be used to frame the hole and the cover 

or door stored in the fireplace cavity for future.

2.  Rough-in approved 3-inch aluminum flex liners 

through the existing fireplace damper and leave 

enough protruding through the hole in the exterior 

masonry to connect terminal.

3.  Connect the liners to the sidewall terminal using 

minimum 3 sheet metal screws per liner. Note which 

liner is the exhaust.

4.  Fasten the sidewall terminal to the masonry chimney 

using screws and anchors (not supplied). Note the 

asymmetrical overlap of the hole for the liners 

when mounting the terminal. Seal the flanges of the 

terminal to the masonry using silicone sealant.

5.  Carefully pull any excess liner down within the 

existing fireplace cavity ensuring the liners do not sag 

and are not crimped or torn.

Summary of Contents for 720SWK-M

Page 1: ...nts Sidewall terminal Vent slider plate with NO restrictor 4001133 Sidewall terminal Front Vent slider plate with NO restrictor 4001133 Rear 12 12 8 1 2 3 intake 3 exhaust 2022 Miles Industries Ltd Kit content This kit must be installed or serviced by a qualified installer service agency or gas supplier These instructions are to be used in conjunction with the main installation instructions for th...

Page 2: ... restrictor see instructions below The 739MN MP and 739VN VP do not have restrictor plates behind the rear log as other 739 models do 1 Remove the existing vent slider plate having built in restrictor 2 Replace with a vent slider plate having no restrictor supplied in this kit If more than 10 0 vertical vent run vent plate with restrictor can remain in place Vent plate with restrictor Vent plate w...

Page 3: ...original solid fuel fireplace into which the gas fireplace is being installed Attach Warning Conversion Plate to Existing Fireplace label supplied loose with 739 heater Attach the This fireplace has been converted label to the existing fireplace using screws or other mechanical means and store any removed parts in back of the existing fireplace for future use Exterior view Note Limited overlap of ...

Page 4: ...rovided with the fireplace 1 2 Description Part Numbers 1 Sidewall termination 4004410 2 Vent slider assembly 4001133 Designed and Manufactured by for Miles Industries Ltd 190 2255 Dollarton Highway North Vancouver B C CANADA V7H 3B1 Tel 604 984 3496 Fax 604 984 0246 www valorfireplaces com Because our policy is one of constant development and improvement details may vary slightly from those given...

Page 5: ...al est de plus de 10 pieds Contenu du kit Sortie d évacuation murale Plaque d évent sans restricteur 4001133 Sortie murale colinéaire Contenu du kit Plaque d évent sans restricteur 4001133 Cette trousse doit être installée et entretenue par un installateur qualifié une agence de service certifiée ou un fournisseur de gaz Ces instructions doivent être utilisées conjointement avec les instructions d...

Page 6: ...ous Les foyers 739MN MP et 739VN VP n ont pas de plaques de restricteur derrière la paroi arrière comme d autres modèles 739 1 Enlevez la plaque d évent avec restricteur intégré 2 Remplacez la avec la plaque d évent sans restricteur fournie Si le parcours vertical d évacuation est de plus de 10 pieds la plaque d évent avec restricteur peut demeurer en place Plaque d évent avec restricteur intégré ...

Page 7: ...lement considérez l interférence possible que l installation d un ventilateur ou d un robinet de sûreté peuvent avoir avec la parcours de la conduite de gaz Portes de verre et pare étincelles existants Les portes de verre doivent être enlevées complètement avant d installer le foyer à gaz Manteaux de cheminée combustibles Les dégagements pour les manteaux de cheminée combustibles doivent être conf...

Page 8: ... sortie 5 Tirez soigneusement tout excès de conduits vers l intérieur de la cheminée en vous assurant que les conduits ne sont pas affaissés coincés ou déchirés 6 Raccordez les conduits aux buses du foyer à l aide de 3 vis par conduits ou colliers de serrage à engrenage Assurez vous que le conduit d évacuation est raccordé à la buse d évacuation 7 Continuez l installation du foyer tel qu indiqué d...

Reviews: