9.7 Digital inputs
BIN0:
For recipe selection (in remote recipe
selection mode).
BIN1:
Selectable. Recipe select.
• If "BIN1" is used for recipe selection, all four recipes can be activated through in-
put signals.
• If "BIN1" is used for sampling information, sample timing can be automated (no
need to press the SAMPLE key). Only two recipes (recipe 1 and recipe 2) can be
activated through input signals.
9.8 Address
HART(R) address of the device. Acceptable
values are from 0 to 15. Default value is 0
(zero), i.e. normal installation with a single sen-
sor, analog output signal (4–20 mA) is active.
Values 1–15 define a fixed 4 mA current output and all communication with the device is
performed over the digital HART protocol.
Caution:
Do not set values 1–15 if the 4–20 mA analog output signal is needed!
Profibus PA address, 0–126.