13
© Vallox Oy - All rights reserved
TECHNIC
AL SPECIFIC
ATIONS
Volume flow rate
Power (W)
SUPPLY/EXTRACT AIR VOLUMES
VALLOX 245 MV
50
100
150
200
250
300
350
50 %
40 %
30 %
60
80 100
120
160
140
dm³/s
(l/s)
m³/h
180 200 220
260 280
240
216 288 360 432 504
576 648 720 792 864 936 1008
300
1080
60 %
100 %
0
FAN INPUT POWER
60
80
100
120
160
140
180
200
220
260 280
240
216
288
360
432
504
576
648
720
792
864
936 1008
300
1080
50
100
150
200
250
300
350
50 %
30 %
40 %
400
100 %
60 %
m³/h
(l/s)
dm³/s
Volume flow rate
(dm
3
/s)
Pressure loss in ducts. Total pressure (Pa)
Input power (total) (W)
Air flow (max) (dm3/s)
SFP =
SFP rate (Specific Fan Power)
recommended value <1.8 (kW m
3
/s)
extract air
supply air
Sound power level in the supply air duct (one duct)
by octave band L
w
, dB
Sound power level in the extract air duct (one duct)
by octave band L
w
, dB
Adjustment position
Adjustment position
Adjustment position (%)
30
40
50
60
100
30
40
50
60
100
Air flow dm³/s
132
160
190
213
250
143
170
204
230
278
Air flow m³/h
475
576
684
767
900
515
612
734
828
1001
Medium
frequency
of the
octave
band Hz
63
66
69
72
74
77
54
57
60
63
66
125
62
63
67
69
72
54
54
57
60
62
250
56
62
64
67
70
51
58
61
64
66
500
51
56
59
63
69
38
42
46
48
52
1000
51
55
58
61
64
37
41
45
48
51
2000
49
54
58
61
64
32
36
41
43
47
4000
36
42
48
52
57
25
28
30
34
38
8000
28
36
44
49
54
24
24
25
26
28
L
W
,dB
L
WA
, dB(A)
68
71
74
76
79
58
62
64
67
70
56
60
64
67
71
46
50
53
57
59
Sound pressure level coming through the envelope of the unit in the room in which it is installed (10m² sound absorption)
Adjustment position / Air flows (supply/extract)
Adjustment position (%)
30
40
50
60
100
Air flow dm³/s
132/148
159/179
192/214
214/243
251/282
Air flow m³/h
475/533
572/644
691/770
770/875
904/1015
L
pA
, dB (A)
37
39
42
45
48
SOUND VALUES
TECHNICAL SPECIFICATIONS
Product title
Vallox 245 MV R
Vallox 245 MV L
Product number
3513100
3513200
Air volumes
Supply air
Extract air
245 dm
3
/s, 100 Pa
267 dm
3
/s, 100 Pa
Fans
Supply air
Extract air
0,170 kW 1,25 A EC
0,170 kW 1,25 A EC
Post-heating
Electrical resistor, 900 W
Electrical connection
230 V, 50 Hz, 14,5 A power plug
Pre-heating
–
Enclosure protection class
IP34
Additional heating
Electrical resistor, 1500 W
Heat recovery bypass
Automatic
Filters
Supply air
Extract air
ISO Coarse > 75 % + ISO ePM₁
ISO Coarse > 75 %
Specific energy consumption (SEC)
in a cold climate
in a temperate climate
A+
A
Operating efficiencies
Annual efficiency
Supply air efficiency
Specific Fan Power (SFP)
75 % A+
87,6 %
0,59 kW (150 dm
3
/s) A++
Dimensions
(w x h x d)
1038 x 1241 x 773 mm
Weight
200 kg
TECHNIC
AL SPECIFIC
ATIONS
Summary of Contents for Vallox 245 MV VKL