background image

20

TECHNIC

AL SPECIFIC

ATIONS

Always follow first and foremost the connection diagram 

provided by the HVAC designer or heat pump manufacturer. 

Also read the duct radiator manual. 
The accompanying figure shows an example of the 

arrangement for connecting the heating/cooling radiator unit 

to the heat collection circuit.
Connect the radiator output pipe to the heat collection 

circuit return pipe. Direct the fluid returning from the radiator 

unit to the heat collection circuit return pipe. If you know 

that there is a large loss of internal pressure inside the heat 

pump, the heat pump should be bypassed. If this is done, 

the fluid circuit will come into operation when the heat pump 

comes to a halt. When this happens the pressure loss in the 

one-way bypass valve Y2 must be lower than the pressure 

loss in the heat pump.

Heating:

 The pump starts when the outdoor air temperature 

drops below the winter limit value set at the factory (-5 °C).

Cooling 

The supply air setpoint value for the active mode 

(for example, At home) controls the pump start-up. The pump 

starts when the supply air setting is below the temperature 

of the supply air that is blown into the apartment.
The duct radiator can be installed in both the supply air 

duct and the outdoor air duct. If the radiator is installed in 

the outdoor air duct, it can be used for both preheating and 

cooling, or for preheating or cooling alone. If the radiator 

is installed in the supply air duct, it can be used only for 

preheating or cooling.
The duct radiator can be set to function either automatically 

or manually. 

•  Automatic

 - In summer, the supply air temperature will 

be maintained at the level specified in the temperature 

setting. In winter, the duct radiator will turn on, when the 

outdoor temperature falls below the winter setting.

•  Manual

 - In summer, the duct radiator will turn on, 

when the outdoor temperature rises above the summer 

setting. In winter, the duct radiator will turn on, when the 

outdoor temperature falls below the winter setting.

To prevent the risk of condensation in the supply air 

duct, you can set the adjustment of the supply air limit to 

automatic or manual. 

•  Automatic

 - The supply air limit is adjusted automatically 

based on the dew point of the extract air. When the 

supply air temperature falls too low, the duct radiator will 

turn off.  

•  Manual

 - The supply air limit can be set manually. When 

the supply air temperature falls down to the set value, 

the duct radiator will turn off.

If an external sensor is in use, it is selected from the settings 

of the external sensor whether it is used to control the 

outdoor air duct radiator or the supply air duct radiator.

NOTE:

 If the duct 

radiator is used in 

the supply air duct, it 

can only be used for 

cooling. 

NOTE:

 When used to 

control the outdoor air 

duct radiator, the exter-

nal NTC sensor is ins-

talled in the outdoor air 

duct before the radiator. 

When used to control 

the supply air duct ra-

diator, the external NTC 

sensor is installed after 

the radiator.

NOTE:

When selecting the 

relay (C), take account 

of the maximum 

allowed combined 

power supply (6W) of 

the circuit board in the 

external MV electrical 

box, if the relay power 

supply comes from the 

circuit board’s +24V 

connector.

NOTE:

Due to the risk of humi-

dity damage, in a duct 

that has not been insu-

lated for condensation 

the supply air tempera-

ture must not fall below 

+16 … 20 °C.

DUCT RADIATOR OPERATION

Summary of Contents for Vallox 245 MV VKL

Page 1: ...Manual Model Vallox 245 MV Vallox 245 MV VKL Type A3732 A3732 Document D5337 Valid from 04 03 2020 Updated 05 02 2020 Ventilation unit MANUAL...

Page 2: ...ing and closing the doors 9 Changing the filters 9 Cleaning the heat recovery cell 10 Condensing water 10 Cleaning the fans 11 Removing and cleaning the supply and extract air fans 11 Removing the res...

Page 3: ...odifications or changes made to the software INTENDED USE All Vallox ventilation units have been designed to provide appropriate and continuous ventilation so as to present no threat to health and to...

Page 4: ...Indicates a hazard that will result in death or serious injury if not avoided WARNING Indicates a hazard that can result in death or serious injury if not avoided IMPORTANT Indicates a hazard that can...

Page 5: ...smartphone or tablet Also the unit software is updated automatically through the cloud service To connect to the cloud service the ventilation unit must be connected to the Internet via LAN and regis...

Page 6: ...9 R model in the figure MAIN PARTS Vallox 245 MV Vallox 245 MV VKL Internal humidity sensor behind the electric box Internal carbon dioxide sensor behind the electric box Control panel Carbon dioxide...

Page 7: ...ow for easier ventilation adjustment WARNING Water must at all times be kept out of the electrical system NOTE When installing the unit reserve a space of at least 800 mm in front of the unit for serv...

Page 8: ...els Dimensions and duct outlets Dimensions Duct outlets R model Inner diameter of the female collar 250mm 1 Extract air from the apartment to the unit 2 Supply air from the unit to the apartment 3 Out...

Page 9: ...ilters insects heavy pollen and other relatively large foreign objects out of the outdoor air Fine filter for supply air filters microscopic pollen and dust particles out of the supply air Coarse filt...

Page 10: ...rs reassemble the ventilation unit in the reverse order 10 Close the doors Ensure that the safety switch catch of the door is touching the safety switch 11 Plug the ventilation unit back into the main...

Page 11: ...eding it through the rubber feed Removing and cleaning the supply and extract air fans To clean the supply air fan 1 Disconnect the ventilation unit from the mains electricity supply 2 Open the doors...

Page 12: ...connector of the resistor a Press down the locking device b Pull off the connector 5 Undo the two wing nuts connecting the resistor to the ventilation unit 6 Lift the resistor out of the ventilation...

Page 13: ...2 46 48 52 1000 51 55 58 61 64 37 41 45 48 51 2000 49 54 58 61 64 32 36 41 43 47 4000 36 42 48 52 57 25 28 30 34 38 8000 28 36 44 49 54 24 24 25 26 28 LW dB LWA dB A 68 71 74 76 79 58 62 64 67 70 56 6...

Page 14: ...9 61 66 500 59 66 46 52 1000 57 62 45 51 2000 57 62 41 47 4000 46 52 30 38 8000 40 47 25 28 LW dB LWA dB A 74 79 64 70 63 69 53 59 Sound pressure level coming through the envelope of the unit in the r...

Page 15: ...erived from these measurements A Thermal input kW B Difference in water temperature C C Water flow dm s D Air flow dm s Vallox 245 MV liquid radiator ta1 15 C tf1 55 C Vallox 245 MV liquid radiator ta...

Page 16: ...tor D I1 Digital input 1 D I2 Digital input 2 11V1 11 1 V operating voltage AN I Analog input 0 10VDC RM I 24V relay input RM O 24V relay output T Supply air fan P Extract air fan M Damper motor TK Sa...

Page 17: ...re Modbus B signal NTC External temperature sensor connector D I1 Digital input 1 D I2 Digital input 2 11V1 11 1 V operating voltage AN I Analog input 0 10VDC RM I 24V relay input RM O 24V relay outpu...

Page 18: ...ut EXTERNAL ELECTRICAL CONNECTION 3x1 5S 2x2x0 5 0 5 2x0 5 2x0 5 7028350 2014 08 29 JS 2x2x0 5 0 5 2x0 5 2x2x0 5 0 5 2x2x0 5 0 5 2x2x0 5 0 5 2x0 5 2x0 5 CAT Analog input two different functions Potent...

Page 19: ...2 11V1 11 1 V operating voltage AN I Analog input 0 10VDC RM I 24V relay input RM O 24V relay output P Circulation pump V Solenoid valve EXTERNAL ELECTRICAL CONNECTION FOR CONTROLLING THE MLV DUCT RA...

Page 20: ...the supply air temperature will be maintained at the level specified in the temperature setting In winter the duct radiator will turn on when the outdoor temperature falls below the winter setting Ma...

Page 21: ...ve Not included in the delivery The valve that is chosen must be compatible with the heat collection circuit fluid for example ELV05006 Stig Wahlstr m K Condensing water tube Not included in the deliv...

Page 22: ...er motor 930618 32 Liquid radiator actuator 946320 7 Post heating resistor 942220 20 Fine filter for supply air 978159 33 Liquid radiator control relay 948517 8 Additional heating resistor 942220 21 C...

Page 23: ...CONFORMITY CERTIFICATES...

Page 24: ...D5337 04 02 2020FIN 05 02 2020ENG PDF www vallox com Vallox Oy Myllykyl ntie 9 11 32200 LOIMAA FINLAND Customer service 358 10 7732 200 Aftersales 358 10 7732 270...

Reviews: