REASON

• Air cools down in the attic ducts.
• The heat recovery cell is frozen, which is why extract air cannot heat outdoor air.
• The preheating radiator does not work.
• The extract air filter or the cell is clogged.
• The initial adjustment of ventilation has not been done.

DO THIS

• Measure the temperature of supply air in the unit and compare it with the air coming

from the valve.

• Check the insulation of the attic ducts.
• Check the operation of the defrost thermostat and preheating resistor (see Section

2.6 Defrosting on page 5). You can turn the defrost thermostat clockwise. In this case
there will probably be no freezing, but extract air can be too warm when going out.
The defrost thermostat can also be turned anticlockwise. In this case, the risk of
freezing of the heat recovery cell will increase. According to the factory setting, the
defrost thermostat works at +5

°

C.

• Check that the filters and the heat recovery cell are clean.
• Check the initial adjustment.

1. Outdoor air coming to the dwelling is cold

REASON

The heat recovery cell defrost function works and prevents the cell from freezing.

DO THIS

If you want the fan to stop at temperatures lower than the preset value, you can decrease
the threshold value of the thermostat by 1 to 2

°

C.

NOTE!
If you decrease the threshold value too much, the cell may freeze.

See Section 1.

2. Supply air fan keeps stopping

4. TROUBLESHOOTING

Summary of Contents for TSK Multi 50 L

Page 1: ...MAINTENANCE MODELS VALLOX TSK MULTI 50 R VALLOX TSK MULTI 50 L VALLOX TSK MULTI 80 R VALLOX TSK MULTI 80 L SUPPLY AND EXTRACT AIR VENTILATION WITH HEAT RECOVERY TYPE TSK MULTI 50 3601 TSK MULTI 80 360...

Page 2: ...ter L or R after the name of the unit indicates whether the unit is left or right handed VALLOX TSK Multi 50 R VALLOX TSK Multi 50 L VALLOX TSK Multi 80 R VALLOX TSK Multi 80 L EVERYDAY QUICK GUIDE NO...

Page 3: ...tumn Dust mites thrive in indoor air if humidity exceeds 50 and if humidity stays at over 60 for a long time in winter water condenses in the cold structures of the house and mould starts to form The...

Page 4: ...dwelling it is not necessary to raise the speed of VALLOX Multi TSK 50 80 during cooking 2 3 Post heating For most of the year heat recovered from the air being extracted is enough to warm the cold a...

Page 5: ...xtract air may freeze in the heat recovery cell Freezing can be prevented by stopping the supply air fan or the unit can be equipped with a preheating resistor which is switched on as needed 2 6 1 Sto...

Page 6: ...ast every two years The fine filter D is not washable Clean it at the same time as the G3 class filters by vacuuming it with a brush nozzle When cleaning be careful not to break filter material To ens...

Page 7: ...trical quick connectors 1 of the fan assembly have to be unfastened The fan assembly can then be tilted sidewards 2 and pulled out through the maintenance door 3 3 4 Condensing water During the heatin...

Page 8: ...sistor see Section 2 6 Defrosting on page 5 You can turn the defrost thermostat clockwise In this case there will probably be no freezing but extract air can be too warm when going out The defrost the...

Page 9: ......

Reviews: