© VALLOX • We reserve the right to make changes without prior notification

VALLOX TSK Multi 50/80

INSTRUCTIONS FOR USE

5

2.4. Heat recovery bypass

In winter use, the heat recovery cell of VALLOX TSK Multi 50/80 recovers heat from the
air leaving the dwelling and uses it to heat the air coming from the outside.
In summer use when it is warm outside, it is unnecessary to heat outdoor air. The heat
recovery cell is then bypassed with damper (A) in VALLOX TSK Multi 50/80. The damper
is controlled using a separate 0-1 switch (not included in the unit delivery). The switch is
mounted in the flat at the same time with the electric installation for the unit. In the summer
position air flow through the cell is prevented, and heat recovery bypass is activated.

2.5. Air filtering

VALLOX TSK Multi 50/80 features coarse filtering of both extract and supply air before
the fans. The supply air side includes a G3 class coarse filter (B) and the extract air side
a G3 class coarse filter (C). The unit can also be equipped with an F7 fine filter (D), which
captures fine dust and pollen as well dust not seen to the eye. The filters need to be in
place in the unit whenever ventilation is in operation.

2.6. Antifreeze

Water condensing from extract air may freeze in the heat recovery cell. Freezing can be
prevented by stopping the supply air fan, or the unit can be equipped with a preheating
resistor, which is switched on as needed.

2.6.1. Stopping the supply air fan

Antifreeze thermostat T1 stops the supply air fan whenever the temperature of extract air
is below +5 

°

C after the cell. The fan restarts when temperature has risen by circa three

degrees to +8 

°

C. The limit of the thermostat (E) can be adjusted. If the unit includes a

preheating radiator (G), the supply air fan cannot be stopped.

2.6.2. Outdoor air preheating

The unit has possibly been equipped with a preheating radiator (F) at the factory. If that
is the case, antifreeze thermostat T1 switches the preheating radiator on whenever the
temperature of extract air goes below +5 

°

C after the cell. The preheating radiator switches

off when temperature has risen by circa three degrees to +8 

°

C. The preheating radiator

heats outdoor air before the heat recovery cell and prevents it from freezing. In very cold
temperatures the preheating radiator is not enough to heat maximum air flow to a sufficient
degree (in a temperature of -30 

°

C, maximum air flow is 30 dm

3

/s). The limit of the

thermostat can be adjusted.

The damper is controlled electronically with
a separate 0-1 switch mounted in the dwelling.

Damper in winter position
(heat recovery active)

Damper in summer position
(heat recovery bypass)

A

A

C

F

D

B

E

Summary of Contents for TSK Multi 50 L

Page 1: ...MAINTENANCE MODELS VALLOX TSK MULTI 50 R VALLOX TSK MULTI 50 L VALLOX TSK MULTI 80 R VALLOX TSK MULTI 80 L SUPPLY AND EXTRACT AIR VENTILATION WITH HEAT RECOVERY TYPE TSK MULTI 50 3601 TSK MULTI 80 360...

Page 2: ...ter L or R after the name of the unit indicates whether the unit is left or right handed VALLOX TSK Multi 50 R VALLOX TSK Multi 50 L VALLOX TSK Multi 80 R VALLOX TSK Multi 80 L EVERYDAY QUICK GUIDE NO...

Page 3: ...tumn Dust mites thrive in indoor air if humidity exceeds 50 and if humidity stays at over 60 for a long time in winter water condenses in the cold structures of the house and mould starts to form The...

Page 4: ...dwelling it is not necessary to raise the speed of VALLOX Multi TSK 50 80 during cooking 2 3 Post heating For most of the year heat recovered from the air being extracted is enough to warm the cold a...

Page 5: ...xtract air may freeze in the heat recovery cell Freezing can be prevented by stopping the supply air fan or the unit can be equipped with a preheating resistor which is switched on as needed 2 6 1 Sto...

Page 6: ...ast every two years The fine filter D is not washable Clean it at the same time as the G3 class filters by vacuuming it with a brush nozzle When cleaning be careful not to break filter material To ens...

Page 7: ...trical quick connectors 1 of the fan assembly have to be unfastened The fan assembly can then be tilted sidewards 2 and pulled out through the maintenance door 3 3 4 Condensing water During the heatin...

Page 8: ...sistor see Section 2 6 Defrosting on page 5 You can turn the defrost thermostat clockwise In this case there will probably be no freezing but extract air can be too warm when going out The defrost the...

Page 9: ......

Reviews: