PIPE CONNECTIONS

Connection of VKL post-heating radiator to underfloor heating circuit

To minimise the risk of freezing involved in the connection the system has several antifreeze functions.
1. The unit stops if supply air temperature goes below the set temperature and automatically starts as soon as temperature rises.
2. When the unit stops, the self-actuated dampers (E) close.
3.  The electric valve (T) opens when the unit becomes dead.
4.  The unit issues an alarm of freezing risk at the controller.

Use of VKL post-heating radiator

•  The temperature of heating water shall be adjusted according to the temperature of outdoor air.
•  No water must be led into the radiator of the unit until the system has been adjusted for operation and the heating network

has heating on or it has been otherwise ensured that the radiator will not freeze.

•  Water circulation in the heating network connected to the unit and the circulation pump must not be stopped during the

heating season.

•  The base volume of water flow into the radiator of the unit can be adjusted with valves (R), which can also act as stop valves

(not included in the delivery)..

RADIATOR HEATING

R

R

HEAT PUMP

T

UNDERFLOOR HEATING

GROUND COLLECTOR

P

MV

Heating

water

adjustment

Y

E

P

Circulation pump. Size e.g. 0.07 dm

3

/s,

60 kPa, not included in the delivery
Because of the risk of condensing the pump
should be suitable for pumping liquid colder
than the ambient temperature.

MV

Solenoid valve, not included in the delivery.
The valve has to be suitable for the liquid in
the ground collector (e.g. Grundfors UPS-25-
60 180 model K).

T

Valve, included in the unit delivery

Y

One-way valve, not included in the delivery
(as low pressure loss as possible)

E

Self-actuated dampers, included in the
delivery

Connection of MLV preheating/cooling radiator

The radiator is connected to the pipe coming from the ground collector. When the requirements for starting the
heating or cooling function are met, the control function of the unit opens the solenoid valve (MV) and starts the
pump (P).
Observe the frost resistance of the liquid used in the ground collector. Connection pipes of the MLV radiator have
to be insulated against condensation.

Note! Because of the risk of humidity damage, supply air temperature in a duct with no condensation insulation should
not go below +16...20 

°

C.

Other connections

Heat can be conducted to the post-heating radiator of DIGIT2 SE VKL in other ways than described above. It is
possible to build a separate circuit for the radiator if higher power is desired, or the risk of freezing can be
eliminated by using non-freezing heat transfer solution. For more information, see the instructions for VALLOX VKL
connections.

Summary of Contents for DIGIT2 SE VKL

Page 1: ...GIT2 SE MLV R DIGIT2 SE MLV L Models DIGIT SED ELECTRONIC CONTROLLER WITH LCD DISPLAY Electrical connection 230 V 50 Hz Class of protection IP34 Fans Extract air 210 kW 0 91 A AC 120 dm3 s 120 Pa Supp...

Page 2: ...or water Heat recovery cell Outdoor air filter F7 Outdoor and extract air prefilter G3 Summer winter damper Maintenance switch Connection box cover plate Self actuated one way dampers only in VKL and...

Page 3: ...30 42 67 97 130 167 205 242 315 Control voltage V Air flows DIGIT2 SE VKL liquid radiator unit winter setting NOTE When the system is being adjusted post heating must be selected winter setting Air fl...

Page 4: ...the unit has been installed 10 m2 sound absorption Sound values 63 125 250 500 1000 2000 4000 8000 LW dB LWA dB A Hz LpA dB A 3 48 l s 73 63 46 47 52 37 32 23 73 54 4 60 l s 76 68 51 51 53 42 37 31 77...

Page 5: ...dicator is not lit 1 2 3 4 5 6 7 8 Fan speed 3 Supply air temperature 21 C Post heating is on Time Filter guard alert Maintenance reminder alert Fireplace booster switch on The fireplace booster switc...

Page 6: ...nnect them to the terminal block of the connection box by connec ting the first humidity sensor to RH1 in place of the 6K8resistor in the termi nal block remove the resistor in this ca se and the seco...

Page 7: ...u red ro rose va white ha grey vio violet PM DAMPER MOTOR CONNECTION 3R R model 3L L model 3 pu s CONNECTION BOX inside the unit 4 5 m CONNECTION BOX on top of the unit m ke s pu m vio ha r va ro vi H...

Page 8: ...SENSOR IS CONNECTED TO REPLACE THE R6k8 RESISTOR HUMIDITY SENSOR RH1 OPTION BLACK M WHITE 2 B ORANGE 2 A WHITE 1 ORANGE 1 FAULT SIGNAL MAX 1 A 24 VDC POTENTIAL FREE CONTACTS FIREPLACE SWITCH pressure...

Page 9: ...loss in the valve 0 3 0 4 Liquid flow dm3 s 0 2 0 02 0 03 0 04 0 05 0 06 0 08 0 1 0 01 1 2 3 4 5 6 7 0 25 0 5 0 75 1 00 1 25 1 45 1 55 1 7 17 5 open Adjustment position Kv value Pressure loss p kPa C...

Page 10: ...s 70 dm3 s 90 dm3 s 8 10 Radiator pressure loss kPa 10 5 15 20 25 0 0 06 liquid flow dm3 s 30 0 08 0 04 0 02 0 35 Performance of VALLOX DIGIT2 SE MLV heating cooling radiator MLV RADIATOR HEATING POWE...

Page 11: ...ric radiator model Parts list VALLOX DIGIT2 SE electric radiator model TE1 Temperature sensor heat Exhaust air temperature Standard recovery cell antifreeze Adjustment range 6 15 C preheating control...

Page 12: ...is however on whenever outdoor temperature is below the limit set or whenever outdoor air is warmer than extract air Heat recovery antifreeze The control centre of the unit controls the operation of...

Page 13: ...DEL VALLOX DIGIT2 SE VKL water radiator model Parts list VALLOX DIGIT2 SE VKL water radiator model TE1 Temperature sensor heat Exhaust air temperature Standard recovery cell antifreeze Adjustment rang...

Page 14: ...TE3 preventing freezing alerts and the stopping of supply air fan TF If the capacity of preheating unit LP1 is not sufficient or it is not on the control centre keeps stopping supply air fan TF on th...

Page 15: ...RAM MLV MODEL VALLOX DIGIT2 SE MLV heating cooling radiator model VALLOX DIGIT2 SE MLV heating cooling radiator model TE1 Temperature sensor heat recovery Exhaust air temperature Standard cell antifre...

Page 16: ...ble Heat recovery is however on whenever outdoor temperature is below the limit set or whenever outdoor air is warmer than extract air Heat recovery antifreeze Controlling preheating in a liquid circu...

Page 17: ...IT2 SE can be equipped with an optional easy to use ceiling mounting plate patent pending The ceiling mounting plate is fixed to the ceiling with M8 thread bars Fix the bars so that they stand the wei...

Page 18: ...nward slope The condensing water pipe must never be connected directly to the sewer If condensing water is led to a water seal or floor drain where also warm washing or shower water is led VALLOX Sile...

Page 19: ...LECTOR P MV Heating water adjustment Y E P Circulation pump Size e g 0 07 dm3 s 60 kPa not included in the delivery Because of the risk of condensing the pump should be suitable for pumping liquid col...

Page 20: ...VALLOX DIGIT2 SE VKL MLV VALLOX Wereservetherighttomakechangeswithoutpriornotification Vallox Oy Myllykyl ntie 9 11 FI 32200 Loimaa Tel 358 10 7732 200 www vallox com 1 09 391E 5 2 2009 PDF...

Reviews: