Code
Name
Technical data
(factory settings in parentheses)
Standard/
Option
Code
Name
Technical data
(factory settings in parentheses)
Standard/
Option
CO
2
Carbon dioxide sensor
Adjustment range 500…2000 ppm (900) Option
Carbon dioxide control
Adjustment interval 1…15 min. (10)
G3
Filter
Supply air, extract air
Standard
F7
Filter
Supply air
Standard
FG
Damper motor
HR bypass automation 24 V, 0.5 W, 2 Nm Standard
H
Control panel
User interface
Standard
LP1
Preheating unit
Electric radiator 1.2 kW
Standard
LP2
Post-heating unit
Water radiator
Standard
LTO1
Heat recovery cell
Cross-flow, efficiency = 60%
Standard
PDE1
Pressure difference switch
Adjustment range 0...500 Pa (320)
Option
Pressure guard on
the supply air side
PDE2
Pressure difference switch
Adjustment range 0...500 Pa (320)
Option
Pressure guard on
the extract air side
PF1
Extract air fan AC
qv = 120 dm
3
/s (120 Pa)
Standard
%RH
Humidity sensor
Automatic/Adjustment range 1...99% (99) Option
Humidity control
Adjustment range 1...15 min. (10)
VALLOX DIGIT2 SE/VKL/MLV
© VALLOX • We reserve the right to make changes without prior notification.
13
CONTROL DIAGRAM/VKL MODEL
VALLOX DIGIT2 SE VKL (water radiator model)
Parts list VALLOX DIGIT2 SE VKL (water radiator model)
TE1
Temperature sensor, heat
Exhaust air temperature
Standard
recovery cell antifreeze,
Adjustment range -6…+15
°
C (HR)
preheating control
Adjustment range -6…+15
°
C
(preheating)
TE2
Temperature sensor
Supply air temperature
Standard
TE3
Temperature sensor
Outdoor air temperature
Standard
TE4
Temperature sensor
Extract air temperature
Standard
TF
Supply air fan AC
qv = 100 dm
3
/s (100 Pa)
Standard
V1
Water radiator actuator/valve
Standard
TS3
Overheat protection for
Aut 30
°
C
Included in
the heating element
LP1
TS4
Overheat protection for
Manually reset, +55
°
C
Included in
the heating element
LP1
S
Fireplace/booster switch function In the controller
Standard
Selectable as either a fireplace
Separate switch
Option
or booster switch function
SP
Damper 2 pcs
Air flow operated
Standard
LON
LON converter
Remote monitoring control
Option
DISTRIBUTION
PANEL
PLUG
LON
CONVERTER
REMOTE MONITORING CONTROL CENTRE OF THE PROPERTY
ALARM
OPERATION MODE
CONTROL
MEASUREMENT
ADJUSTMENT
VENTILATION ZONE
INTERNAL ELECTRICAL AND CONTROL CONNECTIONS
POST-HEATING
RADIATOR
PREHEATING
RADIATOR
FIREPLACE/
BOOSTER SWITCH
CARBON DIOXIDE
SENSOR (5 AT MOST)
CONTROL PANEL
(3 AT MOST)
HUMIDITY SENSOR
(2 AT MOST)
SILENCER
SILENCER