background image

VALLOX DIGIT2 SE/VKL/MLV

© VALLOX • We reserve the right to make changes without prior notification.

DESCRIPTION OF OPERATION/ELECTRIC RADIATOR

12

Control of operation

Power supply to the unit can be controlled with a contactor in the
distribution panel if needed, e.g. with a timer programme.  After
starting, the unit first operates at minimum power. After that power is
adjusted based either on the measurement data from air quality sensors
and/or on manual control at the control panel.

Fan speed adjustment

Manual control

Fan speed of the ventilation unit is controlled in 8 steps at control panel

H

.

Week-clock control

Fan speed of the ventilation unit is controlled in 8 steps using the week
clock in control panel 

H

. The week clock can be used to programme

the desired fan power option and the setpoint for supply air temperature
for each day of the week and each hour in the day.

Carbon dioxide and humidity control

The fan capacity of the ventilation unit is controlled in multiple steps
depending on loads, and based on the measurement results of the air
quality sensors (CO

2

 and %RH sensors) located in the ventilation zone.

 The aim is to keep carbon dioxide and/or humidity content below the
threshold set at control panel 

H

. It is also possible to select an automatic

search for the humidity content setpoint at control panel 

H

. One or

more modes of control may be used simultaneously – the mode
demanding boosting is the dominant one. Fan speed varies depending
on load between the base and maximum fan speeds. The base and
maximum fan speeds can be set at the desired level at control panel

H

.

Control through voltage or current signal

The fan power of the ventilation unit is controlled in 8 steps with a
voltage signal of 0...10 VDC, or with a current signal of 0...20 mA.
However, fan power cannot be raised above the set maximum fan
speed.  Voltage or current signal control is used to control base fan
speed. This means that fan speed can be raised when necessary, but
not lowered, by the manual, CO

2

 and %RH controls.

Supply air temperature

Supply air temperature can be controlled with either constant temperature
control or cascade control.

Supply air constant temperature control

The control unit directs the operation of post-heating unit 

LP2

 on the

basis of the measurement data given by temperature sensor 

TE2

, aiming

at keeping supply air temperature at the temperature value set on
control panel 

H

 (+10…+30 ºC).

Supply air cascade control

The control unit directs the operation of post-heating unit 

LP2

 on the

basis of the measurement data given by extract air sensor 

TE4

, aiming

at keeping extract air temperature at the temperature value set on
control panel 

H

 (+10…+30 ºC).

Heat recovery bypass

Heat recovery is enabled whenever post-heating has been switched
on. Automatic heat recovery bypass is active whenever post-heating
has been switched off and outdoor temperature exceeds the setpoint
(to be set between 0 and +25 

°

C). In this case, the control unit directs

the operation of damper motor 

FG

 on the basis of measurement results

given by outdoor temperature sensor 

TE3

 and extract air temperature

sensor 

TE4

. The aim is to get as cool supply air to the ventilation zone

as possible. Heat recovery is, however, on whenever outdoor temperature
is below the limit set, or whenever outdoor air is warmer than extract
air.

Heat recovery antifreeze

The control centre of the unit controls the operation of preheating unit

LP1

 on the basis of the measurement data of temperature sensors 

TE1

and 

TE3,

 preventing freezing alerts and the stopping of supply air fan

TF

. If the capacity of preheating unit 

LP1

 is not sufficient or it is not on,

the control centre keeps stopping supply air fan 

TF

 on the basis of the

measurement data on temperature sensor 

TE1

 and 

TE3

, thus preventing

the heat recovery cell from freezing. As soon as the risk passes, the
fan restarts automatically. The threshold temperature (-6...+15 

°

C) and

the difference area (1 ...10 

°

C) for antifreeze can be set at control

panel 

H

. When fan 

TF

 stops, power supply from radiator 

LP1

 is stopped

and post-heating radiator 

LP2

 continues to heat.

For preheating to work, its threshold temperature has to be set at least
one degree higher than the threshold temperature controlling fan
stopping. Temperatures are adjusted at control panel 

H

.

Overheat protection for the heating element

Overheat protection thermostats 

TS1

 and 

TS2

 monitor the surface

temperature of heating unit 

LP2

 and overheat protection thermostats

TS3

 and 

TS4

 that of 

LP1

. If surface temperature exceeds the threshold,

overheat protection is triggered and power supply to the heating unit
is stopped. Overheat protection for 

TS1

 and 

TS3

 is reset automatically,

whereas overheat protection for 

TS2

 and 

TS4

 is reset manually.

Alarms

Pressure difference switches 

PDE1

 and 

PDE2

 monitor the pressure

difference on the supply and extract air sides. If the pressure difference
rises too high because of dirty filters or clogged ducts, an alarm will
be issued. This is indicated by a symbol ( ) in the main display of the
control panel. If the unit is not equipped with pressure difference
switches, the symbol ( ) appearing in the main display of the control
panel reminds of the need of servicing the unit. The reminder interval
can be set at 1...15 months. The factory setting is 4 months. This
function is always active.
The fault signal relay in the unit gives potential-free alarm indications
on the following fault conditions:

Alarm of high carbon dioxide content (> 5000 ppm) switches the

relay at 1-second intervals.

In other fault situations, such as sensor faults, the contacts of the

relay close.

Booster or fireplace switch function

The booster or fireplace switch function of the ventilation unit is controlled
either at control panel 

H

 and/or separate switch 

S

, which can be

connected to the connection box of the unit. The mode of operation
of the switch is selected at control panel 

H

. The booster switch function

raises fan speed to the set maximum fan speed for 45 minutes. The
fireplace switch stops the extract air fan for 15 minutes and produces
overpressure in the ventilation zone. LON remote monitoring control
can be implemented with a VALLOX LON converter. (See a separate
brochure.)

Voltage values
for each fan speed:

0

0.20...1.25 VDC

1

1.75...2.25 VDC

2 2.75...3.25 VDC

3 3.75...4.25 VDC

4 4.75...5.25 VDC

5 5.75...6.25 VDC

6 6.75...7.25 

 

VDC

7.75...8.25    VDC

8 8.75...10.00 

VDC

Current signal values
for each fan speed:

0 0.5...2.5  mA

1

3.5...4.5 mA

2

5.5...6.5 mA

3 7.5...8.5  mA

4 9.5...10.5 mA

5 11.5...12.5 

mA

6 13.5...14.5 

mA

7 15.5...16.5 

mA

8 17.5...20.0 

mA

Voltage and current signal values (selection in the motherboard)

Summary of Contents for DIGIT2 SE VKL

Page 1: ...GIT2 SE MLV R DIGIT2 SE MLV L Models DIGIT SED ELECTRONIC CONTROLLER WITH LCD DISPLAY Electrical connection 230 V 50 Hz Class of protection IP34 Fans Extract air 210 kW 0 91 A AC 120 dm3 s 120 Pa Supp...

Page 2: ...or water Heat recovery cell Outdoor air filter F7 Outdoor and extract air prefilter G3 Summer winter damper Maintenance switch Connection box cover plate Self actuated one way dampers only in VKL and...

Page 3: ...30 42 67 97 130 167 205 242 315 Control voltage V Air flows DIGIT2 SE VKL liquid radiator unit winter setting NOTE When the system is being adjusted post heating must be selected winter setting Air fl...

Page 4: ...the unit has been installed 10 m2 sound absorption Sound values 63 125 250 500 1000 2000 4000 8000 LW dB LWA dB A Hz LpA dB A 3 48 l s 73 63 46 47 52 37 32 23 73 54 4 60 l s 76 68 51 51 53 42 37 31 77...

Page 5: ...dicator is not lit 1 2 3 4 5 6 7 8 Fan speed 3 Supply air temperature 21 C Post heating is on Time Filter guard alert Maintenance reminder alert Fireplace booster switch on The fireplace booster switc...

Page 6: ...nnect them to the terminal block of the connection box by connec ting the first humidity sensor to RH1 in place of the 6K8resistor in the termi nal block remove the resistor in this ca se and the seco...

Page 7: ...u red ro rose va white ha grey vio violet PM DAMPER MOTOR CONNECTION 3R R model 3L L model 3 pu s CONNECTION BOX inside the unit 4 5 m CONNECTION BOX on top of the unit m ke s pu m vio ha r va ro vi H...

Page 8: ...SENSOR IS CONNECTED TO REPLACE THE R6k8 RESISTOR HUMIDITY SENSOR RH1 OPTION BLACK M WHITE 2 B ORANGE 2 A WHITE 1 ORANGE 1 FAULT SIGNAL MAX 1 A 24 VDC POTENTIAL FREE CONTACTS FIREPLACE SWITCH pressure...

Page 9: ...loss in the valve 0 3 0 4 Liquid flow dm3 s 0 2 0 02 0 03 0 04 0 05 0 06 0 08 0 1 0 01 1 2 3 4 5 6 7 0 25 0 5 0 75 1 00 1 25 1 45 1 55 1 7 17 5 open Adjustment position Kv value Pressure loss p kPa C...

Page 10: ...s 70 dm3 s 90 dm3 s 8 10 Radiator pressure loss kPa 10 5 15 20 25 0 0 06 liquid flow dm3 s 30 0 08 0 04 0 02 0 35 Performance of VALLOX DIGIT2 SE MLV heating cooling radiator MLV RADIATOR HEATING POWE...

Page 11: ...ric radiator model Parts list VALLOX DIGIT2 SE electric radiator model TE1 Temperature sensor heat Exhaust air temperature Standard recovery cell antifreeze Adjustment range 6 15 C preheating control...

Page 12: ...is however on whenever outdoor temperature is below the limit set or whenever outdoor air is warmer than extract air Heat recovery antifreeze The control centre of the unit controls the operation of...

Page 13: ...DEL VALLOX DIGIT2 SE VKL water radiator model Parts list VALLOX DIGIT2 SE VKL water radiator model TE1 Temperature sensor heat Exhaust air temperature Standard recovery cell antifreeze Adjustment rang...

Page 14: ...TE3 preventing freezing alerts and the stopping of supply air fan TF If the capacity of preheating unit LP1 is not sufficient or it is not on the control centre keeps stopping supply air fan TF on th...

Page 15: ...RAM MLV MODEL VALLOX DIGIT2 SE MLV heating cooling radiator model VALLOX DIGIT2 SE MLV heating cooling radiator model TE1 Temperature sensor heat recovery Exhaust air temperature Standard cell antifre...

Page 16: ...ble Heat recovery is however on whenever outdoor temperature is below the limit set or whenever outdoor air is warmer than extract air Heat recovery antifreeze Controlling preheating in a liquid circu...

Page 17: ...IT2 SE can be equipped with an optional easy to use ceiling mounting plate patent pending The ceiling mounting plate is fixed to the ceiling with M8 thread bars Fix the bars so that they stand the wei...

Page 18: ...nward slope The condensing water pipe must never be connected directly to the sewer If condensing water is led to a water seal or floor drain where also warm washing or shower water is led VALLOX Sile...

Page 19: ...LECTOR P MV Heating water adjustment Y E P Circulation pump Size e g 0 07 dm3 s 60 kPa not included in the delivery Because of the risk of condensing the pump should be suitable for pumping liquid col...

Page 20: ...VALLOX DIGIT2 SE VKL MLV VALLOX Wereservetherighttomakechangeswithoutpriornotification Vallox Oy Myllykyl ntie 9 11 FI 32200 Loimaa Tel 358 10 7732 200 www vallox com 1 09 391E 5 2 2009 PDF...

Reviews: