MAINTENANCE

The R model is shown in the figures. 

In the L model, the parts are mirrored.

BEFORE BEGINNING 
MAINTENANCE WORK

When you open the door of Vallox 101 MC, the safety 
switch (S) cuts the power. Despite this, disconnect the 
power supply plug anyway. Always disconnect the power 
plug before starting maintenance on the Vallox 101 MC.

FILTERS

When the maintenance reminder becomes activated, 
check the cleanliness of the filters and replace them if 
required. The Vallox ventilation unit has three air filters: 

•  Coarse filter for supply air (A) filters insects, heavy 

pollen and other relatively large foreign objects out of 
the outdoor air. 

•  Fine filter for supply air (B) filters microscopic pollen 

and dust particles out of the supply air. 

•  Coarse filter for extract air (C) filters the extract air 

and keeps the heat recovery cell clean. 

Using original Vallox filters ensures the best operation 
of the ventilation unit and the best filtering results. The 
filter replacement interval depends on the ambient dust 
concentration. It is recommended that the filters be 
replaced every spring and autumn, or at the very least 
once a year.

HEAT RECOVERY CELL

Check that the heat recovery cell (D) is clean roughly 
once a year when the filters are being replaced. Clean by 
washing as required.

•  Remove the sealing strip (E) above the heat recovery 

cell in the direction of the arrow. Also remove the 
extract air filter (C).

•  Lift the heat recovery cell and pull it out of the unit.

IMPORTANT! Handle the cell carefully! For example, do 
not lift the cell by the layers. The cell layers are very thin 
and easily damaged.

If the heat recovery cell is dirty, clean it by immersing it in 
water containing a small amount of a mild detergent. Rinse 
the heat recovery cell clean with a water spray. When all 
the water has drained from between the layers, the heat 
recovery cell can be installed.

•  Ensure that the lower support (F) is in place between 

the knobs at the bottom of the unit before the heat 
recovery cell is installed. 

•  Push the heat recovery cell in place. Also push the 

sealing strip (E) in place so that the strip is supported 
by the corner bracket (G) at the rear. Lastly, install the 
extract air filter (C) in place.

S

A

B

C

E

G

C

D

F

Summary of Contents for A3740

Page 1: ...Manual MANUAL Ventilation unit Document D4686 Valid from 31 08 2020 Updated 20 01 2021 Model Vallox 101 MC R Vallox 101 MC L Type A3740...

Page 2: ...o not ensure safe operation of the unit Such persons can use the unit under supervision or by following the instructions of someone who is responsible for their safety 12 13 14 Vallox Simple Control p...

Page 3: ...t recovery cell is bypassed when the outdoor temperature is above 14 C The heat recovery will be turned on when the outdoor temperature falls below 12 C In the AUTO position the unit will operate as f...

Page 4: ...air is faulty Check the sensor and the wires replace as required 6 The supply air fan has stopped Check the wiring of the fan replace the fan as required 7 The extract air fan has stopped Check the wi...

Page 5: ...on the ambient dust concentration It is recommended that the filters be replaced every spring and autumn or at the very least once a year HEAT RECOVERY CELL Check that the heat recovery cell D is cle...

Page 6: ...grilles undo their mounting screws K 3 screws grille and remove the grilles from the fans Put the control grilles back in place after cleaning To remove the fan disconnect the quick connector H of the...

Page 7: ...heating season begins e g during autumn maintenance check that the condensing water outlets in the bottom pool are not clogged To check this pour some water into the pool Clean as required Water must...

Page 8: ...Enclosure protection class IP 34 Post heating Electrical resistor 1500 W Pre heating Additional heating Fans Supply air Extract air 0 119 kW 0 9 A EC 0 119 kW 0 9 A EC Specific energy consumption SEC...

Page 9: ...71 74 78 83 85 88 88 54 57 63 66 70 75 78 79 80 LWA dB A 43 53 57 61 65 68 71 72 74 35 40 45 49 53 55 58 59 60 Sound pressure level coming through the envelope of the unit in the room in which it is i...

Page 10: ...t link between connectors 3 and 5 from the female side of the control panel connector Post heating control PWM level adjustment 4 5 6 Protective earth to a separate block 7 8 9 1 Supply air fan 2 3 Ex...

Page 11: ...rminal connector GND S GND S MC VENTILATION UNIT Four terminal connector MV VENTILATION UNIT GND AN I RM I RM O E I LED E O PROGRAMMING CONNECTORS OF THE MOTHERBOARD CONTACT DATA GUARD FUNCTION NORMAL...

Page 12: ...485 Common RH optional 946147 Nomak 2x2x0 5 0 5 0 10V LED G G0 Y1 Y2 DI1 A1 Y3 A2 Y4 U1 A B C S DI2 G0 Vallox Procontrol 949034 S LED S B term CONFIG Control signal S Cooker hood or boost switch 11 2...

Page 13: ...0 30 11 84 84 35 30 35 7 14 kpl 550 30 25 25 30 Wall mounting plate 283 166 6 604 Bottom edge of the wall mounting plate The top surface of the side panel of the unit can be installed against the nish...

Page 14: ...ng plate Installing the ventilation unit to the ceiling mounting plate Remove the unit door Lift the unit and take the wires through the opening in the ceiling mounting plate Lift the ventilation unit...

Page 15: ...k siphon Installation height 53 mm installation space 73 mm outer diameter of the duct 12 mm Location of the condensing water outlets R and L models If the Vallox Silent Klick siphon does not fit into...

Page 16: ...225 6 HR cell 933260 7 Lower support for the HR cell 4102504 8 Upper support for HR cell 3467200 9 Filter frame extraction 978226 10 Coarse filter for extract air 978227 NO Part Product number 11 HR c...