14

INS

T

ALLA

TION

Ceiling mounting by using  
a ceiling mounting plate 

(optional)

The unit can be equipped with an optional ceiling 
mounting plate. The ceiling mounting plate must be 
fastened on rafter frames or other frame structure with 
M8 thread bars. The bars must be fastened so that they 
withstand the weight of the unit.

The ceiling mounting plate must be fastened horizontally 
to make sure that the unit is level. The ceiling mounting 
plate must be fastened so that there is a 10  mm gap 
between its rear edge and the finished wall. This way 
the ventilation unit will be installed as close to the wall as 
possible. The top edge of the white covering strip of the 
ceiling mounting plate can be installed against the finished 
ceiling. Alternatively, a concealed mounting method can 
be used, in which case the finished ceiling can be 30 mm 
or less from the top edge of the white covering strip.

The ceiling mounting plate is fastened to the M8 thread 
bars with the mounting supplies delivered with the 
mounting plate.  NOTE! The end of the thread bars must 
be 5mm or less below the fastening nut (more detailed 
instructions are provided with the ceiling mounting plate).

Installing the ventilation unit to the ceiling 
mounting plate

Remove the unit door. Lift the unit and take the wires 
through the opening in the ceiling mounting plate. Lift 
the ventilation unit against the ceiling mounting plate so 
that it locks in place. The unit has become locked on the 
ceiling mounting plate when the two operating levers on 
the mounting plate have been restored to the same level 
with the white covering strip of the ceiling mounting plate 
(more detailed instructions are provided with the ceiling 
mounting plate).

Ceiling mounting plate (optional)

The top edge of the white covering strip of the ceiling mounting plate can be installed against the finished ceiling. Alternatively, 
a concealed mounting method can be used, in which case the finished ceiling can be  30 mm or less from the top edge of the 
white covering strip.

The minimum distance from  
the finished rear wall is 10 mm

The recommended distance from  
the finished side wall is 10 mm

 598 

 10 

 10 

 598 

Finished wall

Finished wall

Concealed installation 
of the ceiling mounting plate 
on the ceiling, max. 30 mm

 483 

 453 

 53 

 53 

Finished ceiling

Siphon Silent Klick

Installation 
space of 
the siphon 
73 mm

Installation 
space of 
the elbow 
47 mm

Concealed installation 
of the ceiling mounting plate 
on the ceiling, max. 30 mm

 483 

 453 

 38 

 38 

Finished ceiling

Elbow

 10 

Finished wall

Summary of Contents for A3740

Page 1: ...Manual MANUAL Ventilation unit Document D4686 Valid from 31 08 2020 Updated 20 01 2021 Model Vallox 101 MC R Vallox 101 MC L Type A3740...

Page 2: ...o not ensure safe operation of the unit Such persons can use the unit under supervision or by following the instructions of someone who is responsible for their safety 12 13 14 Vallox Simple Control p...

Page 3: ...t recovery cell is bypassed when the outdoor temperature is above 14 C The heat recovery will be turned on when the outdoor temperature falls below 12 C In the AUTO position the unit will operate as f...

Page 4: ...air is faulty Check the sensor and the wires replace as required 6 The supply air fan has stopped Check the wiring of the fan replace the fan as required 7 The extract air fan has stopped Check the wi...

Page 5: ...on the ambient dust concentration It is recommended that the filters be replaced every spring and autumn or at the very least once a year HEAT RECOVERY CELL Check that the heat recovery cell D is cle...

Page 6: ...grilles undo their mounting screws K 3 screws grille and remove the grilles from the fans Put the control grilles back in place after cleaning To remove the fan disconnect the quick connector H of the...

Page 7: ...heating season begins e g during autumn maintenance check that the condensing water outlets in the bottom pool are not clogged To check this pour some water into the pool Clean as required Water must...

Page 8: ...Enclosure protection class IP 34 Post heating Electrical resistor 1500 W Pre heating Additional heating Fans Supply air Extract air 0 119 kW 0 9 A EC 0 119 kW 0 9 A EC Specific energy consumption SEC...

Page 9: ...71 74 78 83 85 88 88 54 57 63 66 70 75 78 79 80 LWA dB A 43 53 57 61 65 68 71 72 74 35 40 45 49 53 55 58 59 60 Sound pressure level coming through the envelope of the unit in the room in which it is i...

Page 10: ...t link between connectors 3 and 5 from the female side of the control panel connector Post heating control PWM level adjustment 4 5 6 Protective earth to a separate block 7 8 9 1 Supply air fan 2 3 Ex...

Page 11: ...rminal connector GND S GND S MC VENTILATION UNIT Four terminal connector MV VENTILATION UNIT GND AN I RM I RM O E I LED E O PROGRAMMING CONNECTORS OF THE MOTHERBOARD CONTACT DATA GUARD FUNCTION NORMAL...

Page 12: ...485 Common RH optional 946147 Nomak 2x2x0 5 0 5 0 10V LED G G0 Y1 Y2 DI1 A1 Y3 A2 Y4 U1 A B C S DI2 G0 Vallox Procontrol 949034 S LED S B term CONFIG Control signal S Cooker hood or boost switch 11 2...

Page 13: ...0 30 11 84 84 35 30 35 7 14 kpl 550 30 25 25 30 Wall mounting plate 283 166 6 604 Bottom edge of the wall mounting plate The top surface of the side panel of the unit can be installed against the nish...

Page 14: ...ng plate Installing the ventilation unit to the ceiling mounting plate Remove the unit door Lift the unit and take the wires through the opening in the ceiling mounting plate Lift the ventilation unit...

Page 15: ...k siphon Installation height 53 mm installation space 73 mm outer diameter of the duct 12 mm Location of the condensing water outlets R and L models If the Vallox Silent Klick siphon does not fit into...

Page 16: ...225 6 HR cell 933260 7 Lower support for the HR cell 4102504 8 Upper support for HR cell 3467200 9 Filter frame extraction 978226 10 Coarse filter for extract air 978227 NO Part Product number 11 HR c...

Reviews: