4

USING THE UNIT

FIREPLACE SWITCH

A switch with timer functions can be connected to the unit. The switch stops the 
extract air fan when the fireplace is being used. NOTE! Starting up the extract 
air fan can reduce the draw of the fireplace! In winter, this can disturb the winter 
mode of the ventilation unit. The situation will return to normal soon after the 
fireplace mode is turned off.

ADJUSTING THE SUPPLY AND EXTRACT AIR 
RATIO 

This function might be needed when the air flows are adjusted at the valves 
during installation. The user does not need to adjust this function once 
the valves have been adjusted, and indeed should not adjust it at all. A 
potentiometer can be used to reduce the supply or extract air flow as required. 

When the potentiometer is set roughly in the centre position, neither the supply 
nor the extract air flow has been reduced. When the potentiometer is turned 
anti-clockwise, the supply air flow is reduced, and when the potentiometer is 
turned clockwise, the extract air flow is reduced.

The potentiometer for adjusting  

the supply and extract air flows

TROUBLESHOOTING

Flashing LED

Problem

Correction

1

NTC sensor of the supply air from the cell is faulty

Check the sensor and the wires, replace as required

2

NTC sensor of the extract air is faulty 

Check the sensor and the wires, replace as required

3

NTC sensor of the extract air is faulty 

Check the sensor and the wires, replace as required

4

NTC sensor of the exhaust air is faulty 

Check the sensor and the wires, replace as required

5

NTC sensor of the outdoor air is faulty 

Check the sensor and the wires, replace as required

6

The supply air fan has stopped

Check the wiring of the fan, replace the fan as required

7

The extract air fan has stopped

Check the wiring of the fan, replace the fan as required

8

EEPROM is faulty 

Replace the circuit board

Concealed installation of  

the fireplace switch (optional)

TROUBLESHOOTING TABLE

If the ventilation unit is affected by any of the errors listed in the table, the unit will report the error through the error relay, 
signal light, and circuit board LEDS. The number of flashes indicates the nature of the error.

The error relay can be connected to remote monitoring.  

NOTE! When remote monitoring is used, the signal light of the control panel cannot be turned on.

MAINTENANCE REMINDER

If a signal light is connected to the connectors of the unit’s error relay, the unit will send a reminder of service need every 
six months,. If connected, the signal light will flash every second. Sounds made by the relay can then be heard from 
inside the unit. The maintenance reminder will be set off automatically when the door of the ventilation unit is opened or 
the power is turned off. The maintenance reminder can also be set off manually.

The Vallox Simple Control panel, and the Vallox 
X-Line PTXP MC and PTXPA MC control hoods, 
VAK 0-10 VDC:

•  The low speed is turned on, then higher-lower-higher

 

-  Low speed under 4 V

 

-  High speed over 6 V

 

-  The selected speed will always be turned  
   on for 1-5 seconds

Vallox Delico PTD EC and Vallox Capto PTC EC 
control hoods:

•  The damper is closed, then open-closed-open

•  Press at a 1-5 second interval.

The service reminder will only be set off if it has been activated. Refer to the maintenance instructions for the necessary 
maintenance measures.

Summary of Contents for A3740

Page 1: ...Manual MANUAL Ventilation unit Document D4686 Valid from 31 08 2020 Updated 20 01 2021 Model Vallox 101 MC R Vallox 101 MC L Type A3740...

Page 2: ...o not ensure safe operation of the unit Such persons can use the unit under supervision or by following the instructions of someone who is responsible for their safety 12 13 14 Vallox Simple Control p...

Page 3: ...t recovery cell is bypassed when the outdoor temperature is above 14 C The heat recovery will be turned on when the outdoor temperature falls below 12 C In the AUTO position the unit will operate as f...

Page 4: ...air is faulty Check the sensor and the wires replace as required 6 The supply air fan has stopped Check the wiring of the fan replace the fan as required 7 The extract air fan has stopped Check the wi...

Page 5: ...on the ambient dust concentration It is recommended that the filters be replaced every spring and autumn or at the very least once a year HEAT RECOVERY CELL Check that the heat recovery cell D is cle...

Page 6: ...grilles undo their mounting screws K 3 screws grille and remove the grilles from the fans Put the control grilles back in place after cleaning To remove the fan disconnect the quick connector H of the...

Page 7: ...heating season begins e g during autumn maintenance check that the condensing water outlets in the bottom pool are not clogged To check this pour some water into the pool Clean as required Water must...

Page 8: ...Enclosure protection class IP 34 Post heating Electrical resistor 1500 W Pre heating Additional heating Fans Supply air Extract air 0 119 kW 0 9 A EC 0 119 kW 0 9 A EC Specific energy consumption SEC...

Page 9: ...71 74 78 83 85 88 88 54 57 63 66 70 75 78 79 80 LWA dB A 43 53 57 61 65 68 71 72 74 35 40 45 49 53 55 58 59 60 Sound pressure level coming through the envelope of the unit in the room in which it is i...

Page 10: ...t link between connectors 3 and 5 from the female side of the control panel connector Post heating control PWM level adjustment 4 5 6 Protective earth to a separate block 7 8 9 1 Supply air fan 2 3 Ex...

Page 11: ...rminal connector GND S GND S MC VENTILATION UNIT Four terminal connector MV VENTILATION UNIT GND AN I RM I RM O E I LED E O PROGRAMMING CONNECTORS OF THE MOTHERBOARD CONTACT DATA GUARD FUNCTION NORMAL...

Page 12: ...485 Common RH optional 946147 Nomak 2x2x0 5 0 5 0 10V LED G G0 Y1 Y2 DI1 A1 Y3 A2 Y4 U1 A B C S DI2 G0 Vallox Procontrol 949034 S LED S B term CONFIG Control signal S Cooker hood or boost switch 11 2...

Page 13: ...0 30 11 84 84 35 30 35 7 14 kpl 550 30 25 25 30 Wall mounting plate 283 166 6 604 Bottom edge of the wall mounting plate The top surface of the side panel of the unit can be installed against the nish...

Page 14: ...ng plate Installing the ventilation unit to the ceiling mounting plate Remove the unit door Lift the unit and take the wires through the opening in the ceiling mounting plate Lift the ventilation unit...

Page 15: ...k siphon Installation height 53 mm installation space 73 mm outer diameter of the duct 12 mm Location of the condensing water outlets R and L models If the Vallox Silent Klick siphon does not fit into...

Page 16: ...225 6 HR cell 933260 7 Lower support for the HR cell 4102504 8 Upper support for HR cell 3467200 9 Filter frame extraction 978226 10 Coarse filter for extract air 978227 NO Part Product number 11 HR c...

Reviews: