background image

9

Vallox

90

K

MC

© VALLOX • We reserve the right to make changes without prior notice.
What the units include can vary depending on the sales area.

MC CONTROLLER

Indicator

Indicator (A) shown in Figure 1 is lit when the MC ventilation unit controlled by the hood is 

on. If the indicator blinks at one-second intervals, the ventilation unit reminds of the need for 

maintenance. The reminder is given at half-year intervals. The maintenance reminder is reset 

when the cover of the ventilation unit is opened. The instructions for the ventilation unit also 

include explanations for other cases where the indicator blinks in fault situations.
The indicator is not in use if a cooker hood is used to control roof fans or other ventilation unit 

or the indicator is not connected to the ventilation unit.

Adjustment of fan speeds

A low signal voltage comes to the controller, which means that the adjustment can be made 
when the controller is connected and the ventilation unit is in operation. 
•  The adjustment is conducted in the four holes below the controller knob (Figure 2) one 

speed at a time, at the potentiometer corresponding to each speed. 

•     The voltage adjusted can be measured at the measuring points found below the knob 

(markings S and –) or on the terminal block below a black housing (markings S and –, 

see Figure 6) with a multimeter direct-current voltage measurement. The adjustment range 

is ~2...11.2 V.

•     Control voltage (air flow) rises when the potentiometer is turned clockwise. The preset 

voltages are as follows: 2.5 V, 5 V, 7.5 V and 10 V.

 

Note! Do not set control voltage so low that the fan does not start (circa 1.5 V).

Sample adjustment of air flows:

Basic ventilation is adjusted at speed 2.
•  Set the controller at speed 2 and measure air flows at the valves. 
•  If the total air flow is too low, set the control voltage higher at potentiometer 2.
•  If the total air flow is too high, set the control voltage lower at potentiometer 2. 
 

Do not throttle the air flow unnecessarily with valves.

•  The balance between supply and extract air flows in the Vallox MC ventilation unit can 

be adjusted with the potentiometer inside the unit. Do not change this balance during 

measurements carried out at other speeds. 

•  Adjust the absence air flows correspondingly at speed 1 (potentiometer 1).
•  Adjust the boosting air flows correspondingly at speed 3 (potentiometer 3).
•  You can usually leave speed 4 for full power.

Finally, measure voltage at all speeds at the measurement pins and enter them in the 

measurement record.  In for instance a terraced house, you can use voltage measurement to 

copy the measurement in the first dwelling to other similar dwellings.

Set the speed knob in position 1 and 

detach the knob with for instance 

screwdriver. 

There are adjustment and measurement 

holes between the knob. 

Measure voltage at contacts – and S, 

adjust for instance speed 1  

at potentiometer 1.

Put the knob back in place, turn the knob to 

the following speed position and detach the 

knob again.

Measure voltage at contacts – and S, adjust 

speed 2 at potentiometer 2,  

and so on.

You can also carry out the measurement at 

the terminal block, in locations shown in the 

electrical diagram.

Summary of Contents for 90K MC Series

Page 1: ...90K MC R VALLOX 90K MC L Operating maintenance and technical instructions 10 1 2 8 4 5 3 11 12 6 7 9 Electrical connection 230V 50Hz 5 7A Degree of protection provided by enclosures IP34 Fans Extract...

Page 2: ...n it is advisable to contact Vallox Maintenance Adjustment of the relationship between supply and extract air This feature may be useful when adjusting air flows at the valves during mounting After th...

Page 3: ...s of filters A coarse filter A filters off insects heavy pollen and other dust An F7 class fine filter B filters off fine dust invisible to the eye Extract air is filtered with a coarse filter C By us...

Page 4: ...maintenance e g in autumn before the beginning of the heating season make sure that the condensing water outlet L in the bottom tank is not clogged You can check it by pouring a little water in the t...

Page 5: ...nd values Sound power level from the ventilation unit to supply air ducts by octave band LW dB Sound power level from the ventilation unit to extract air ducts by octave band LW dB ADJUSTMENT POSITION...

Page 6: ...fety switch SNO Phase voltage to supply air fan SFN Zero voltage to supply air fan EFL Phase voltage to extract air fan EFN Zero voltage to extract air fan FSO Input to fireplace switch FSI Fireplace...

Page 7: ...g a pipe to the water seal the water condensing from extract air can be led to a floor drain not directly to the drain The pipe must not rise after the water seal The unit has to be mounted horizontal...

Page 8: ...clude can vary depending on the sales area MOUNTING INSTRUCTIONS During mounting the unit rises 10 mm higher than the final height The lead in of electric wires can be done from both sides of the unit...

Page 9: ...e The preset voltages are as follows 2 5 V 5 V 7 5 V and 10 V Note Do not set control voltage so low that the fan does not start circa 1 5 V Sample adjustment of air flows Basic ventilation is adjuste...

Page 10: ...be a separate extract valve in the kitchen Basic extraction is not possible through the cooker hood when a VALLOX 90K MC unit is used The cooker hood is used for boosted smoke abatement An alternativ...

Page 11: ...r edge of the covering door on the door of the ventilation unit VALLOX 90K MC Mounting of covering door brackets Lower edge of covering door 620 Fixing moulding A Glue the magnet tape C Screws 3 5 15...

Page 12: ...12 Vallox 90K MC VALLOX We reserve the right to make changes without prior notice What the units include can vary depending on the sales area 1 09 351E 17 1 2019 PDF MOUNTING INSTRUCTIONS...

Reviews: