Adjustment of supply air temperature and summer/

winter function

The temperature of air coming to the dwelling can be adjusted between circa +10 °C and 

+30 °C. The midpoint of the adjustment range is circa +20 °C. When supply air temperature 

adjustment has been turned in the OFF position, post-heating is not active. This means that 

summer function is activated for the ventilation unit. The unit has a motorised summer/winter 

function. When the summer function is on, the heat recovery cell is bypassed as soon as 

outdoor air temperature has risen above +14 °C. When outdoor air temperature goes below 

+12 °C, the unit starts to recover heat. When supply air temperature adjustment is in the 

AUTO position, automatic function is activated for the unit.  In this case, the setpoint for post-

heating is +17 °C and the heat recovery cell is bypassed automatically according to outdoor 

temperatures as indicated above. When the unit bypasses the heat recovery cell, in which 

case summer function is activated, post-heating is off.

Fireplace switch function

It is possible to connect a timer-operated switch to the unit. The switch stops the extract air fan 

during the time when the fireplace is heated. NOTE! The starting of the extract air fan may 

weaken draught in the fireplace! In winter, this situation may disturb the winter function of the 

unit. The situation will normalise in a while, after the fireplace function stops.

Winter function of ventilation unit

A threshold value has been set at the factory for the freezing of the heat recovery cell. When 

the threshold is exceeded, the ventilation unit starts to melt the heat recovery cell. Melting is 

done by stopping the supply air fan.
A normal melting period takes from 15 to 45 minutes depending on the extent of ice on 

the heat recovery cell and on the amount of extract air flow. The unit has been optimised to 

operate on the factory settings in normal operation in dwellings and detached houses. The 

winter function parameters can be adjusted in extreme conditions, such as in a swimming 

bath, but even then it is advisable to contact Vallox Maintenance.

Adjustment of the relationship between supply and extract air

This feature may be useful when adjusting air flows at the valves during mounting. After 

the valves have been adjusted, a user does not need, and must not, touch the adjustment. 

When needed, supply or extract air flow can be reduced at the potentiometer. When the 

potentiometer is approximately halfway, supply and extract air flow have not been reduced. 

Turning the potentiometer anticlockwise reduces the air flow on the supply side, and turning it 

clockwise reduces the air flow on the extract side.

Maintenance reminder

The unit reminds of the need for maintenance every six months if an indicator (not standard) 

has been connected to the connectors of the fault signal relay. The indicator then blinks at 

one-second intervals. The maintenance reminder is reset when the door of the ventilation unit 

is opened. See the maintenance instructions for information on the necessary maintenance 

activities.

Fan speed adjustment

The cooker hood is connected to the ventilation unit and is used to control air circulation in 

the whole dwelling. Four operating ranges are available.
Speeds 1, 2, 3 and 4 can be selected at the control switch.
1.    Operation during absence. When the dwelling is empty, ventilation can be reduced 

temporarily.

2–3. Normal operation. In normal operation, air has to be replaced once every two hours.
4.   Boosted operation. Cooking, taking a sauna bath, washing, drying clothes, using 

the toilet, having guests or a corresponding situation may cause a need for higher 

ventilation than in normal operation.

Cooking

Open the boost flap of the cooker hood during cooking.  

At other times, the flap must be kept closed.  

An open flap reduces the power of ventilation in other rooms.

Adjustment of supply 

air temperature

Supply and extract 

air flow adjustment 

potentiometer

Fireplace switch,  

flush mounting (option)

OPERATING INSTRUCTIONS

Fan speed adjustment

This appliance can be used by children 

aged from 8 years and above and 

persons with reduced physical, sensory or 

mental capabilities or lack of experience 

and knowledge if they have been given 

supervision or instruction concerning 

use of the appliance in a safe way and 

understand the hazards involved. 
Children shall not play with the appliance. 
Cleaning and user maintenance shall not 

be made by children without supervision.

Summary of Contents for 90K MC Series

Page 1: ...90K MC R VALLOX 90K MC L Operating maintenance and technical instructions 10 1 2 8 4 5 3 11 12 6 7 9 Electrical connection 230V 50Hz 5 7A Degree of protection provided by enclosures IP34 Fans Extract...

Page 2: ...n it is advisable to contact Vallox Maintenance Adjustment of the relationship between supply and extract air This feature may be useful when adjusting air flows at the valves during mounting After th...

Page 3: ...s of filters A coarse filter A filters off insects heavy pollen and other dust An F7 class fine filter B filters off fine dust invisible to the eye Extract air is filtered with a coarse filter C By us...

Page 4: ...maintenance e g in autumn before the beginning of the heating season make sure that the condensing water outlet L in the bottom tank is not clogged You can check it by pouring a little water in the t...

Page 5: ...nd values Sound power level from the ventilation unit to supply air ducts by octave band LW dB Sound power level from the ventilation unit to extract air ducts by octave band LW dB ADJUSTMENT POSITION...

Page 6: ...fety switch SNO Phase voltage to supply air fan SFN Zero voltage to supply air fan EFL Phase voltage to extract air fan EFN Zero voltage to extract air fan FSO Input to fireplace switch FSI Fireplace...

Page 7: ...g a pipe to the water seal the water condensing from extract air can be led to a floor drain not directly to the drain The pipe must not rise after the water seal The unit has to be mounted horizontal...

Page 8: ...clude can vary depending on the sales area MOUNTING INSTRUCTIONS During mounting the unit rises 10 mm higher than the final height The lead in of electric wires can be done from both sides of the unit...

Page 9: ...e The preset voltages are as follows 2 5 V 5 V 7 5 V and 10 V Note Do not set control voltage so low that the fan does not start circa 1 5 V Sample adjustment of air flows Basic ventilation is adjuste...

Page 10: ...be a separate extract valve in the kitchen Basic extraction is not possible through the cooker hood when a VALLOX 90K MC unit is used The cooker hood is used for boosted smoke abatement An alternativ...

Page 11: ...r edge of the covering door on the door of the ventilation unit VALLOX 90K MC Mounting of covering door brackets Lower edge of covering door 620 Fixing moulding A Glue the magnet tape C Screws 3 5 15...

Page 12: ...12 Vallox 90K MC VALLOX We reserve the right to make changes without prior notice What the units include can vary depending on the sales area 1 09 351E 17 1 2019 PDF MOUNTING INSTRUCTIONS...

Reviews: