manualshive.com logo in svg
background image

  
 
 
 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 
 

 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 

 
 
 
 
 
 

 
 
 
 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 
 

 

 

 

 

 

 

Modern Gas Fireplaces - Linear Fireplaces

  

 

FLARE REQUIRES INSTALLATION BE 
PERFORMED BY AN NFI CERTIFIED INSTALLER, 
OR A CERTIFIED FLAREAUTHORIZED INSTALLER. 

INSTALLATIONS THAT DO NOT FOLLOW THIS 
INSTRUCTION WILL NOT BE COVERED BY 
WARRANTY OR SERVICED.

 

 

NOTICE

 

INSTALLER: Leave this manual with the appliance.

 

CONSUMER: Retain this manual for future reference.

 

INSTALLATION AND SERVICE OF THIS APPLIANCE MUST BE PERFORMED BY 

QUALIFIED CERTIFIED 

NFI

 PERSONNEL OR CERTIFIED FLARE FIREPLACE 

DEALER.

 

 

Massachusetts: The piping and final gas connection must be performed by a 

licensed plumber or gas fitter in the State of Massachusetts. Also, see 

Carbon Monoxide detector requirements on page 56.

 

 

 

Flare Fireplaces Installation Guide- Honeywell- Control Sys. 7

 

[Flare Double Corner, Left Corner, Right Corner, Front, See-Through and Room Definer] v15.1

 

Содержание Flare Front 30-100"

Страница 1: ...Retain this manual for future reference INSTALLATION AND SERVICE OF THIS APPLIANCE MUST BE PERFORMED BY QUALIFIED CERTIFIED NFI PERSONNEL OR CERTIFIED FLARE FIREPLACE DEALER Massachusetts The piping and final gas connection must be performed by a licensed plumber or gas fitter in the State of Massachusetts Also see Carbon Monoxide detector requirements on page 56 Flare Fireplaces Installation Guid...

Страница 2: ...SS TRIM REMOVAL INSTALLATION FLARE H EH 17 SIDE GLASS TRIM REMOVAL INSTALLATION C RD 18 REFLECTIVE BACK INSTALL 19 INSTALLATION STEPS 20 INSTALLATION PREPARATION 21 ACCESS PANEL 21 FIREPLACE UNPACKING 22 FIREPLACE TELESCOPIC LEGS SETUP 23 LEG SETUP FOR FRONT AND SEE THROUGH UNITS 24 LEG SETUP FOR CORNER UNITS 25 UNPACKING CONTROL UNIT AND ACCESSORIES 26 FIREPLACE POSITIONING 27 LED LIGHTS 28 LED L...

Страница 3: ...G REDUCER 56 ORIFICE SIZE 57 GAS VALVE ACCESS DOOR 57 LIQUID PROPANE USAGE IN A FLARE FIREPLACE 58 COMMONWEALTH OF MASSACHUSETTS 59 FLARE FIREPLACES DOUBLE GLASS 60 OVERVIEW 60 DOUBLE GLASS INSTRUCTIONS 61 POWER REQUIREMENT ELECTRICAL REQUIREMENT 62 TELEVISION MOUNTING ABOVE FIREPLACE 62 TV INSTALL FLAT EXAMPLE 63 TV INSTALL L TYPE E 64 TV INSTALL RECESS 45 DEGREE ELBOW ON TOP OF THE UNIT 65 TV IN...

Страница 4: ...ENSIONS 88 HOME AUTOMATION 89 ELECTRIC AND CONTROL 90 ELECTRIC DIAGRAM SCREEN 90 HONEYWELL DIAGRAM DOUBLE GLASS AND POWER VENT 91 DOUBLE GLASS BOARD LED LIGHT GUIDE 92 ELECTRIC DIAGRAM PV SYSTEM 93 REPLACEMENT PARTS 94 MAINTENANCE 95 TORUBLESHOOTING 97 ADJUSTING YOUR AIR SHUTTER TO PREVENT SOOTING 97 APPENDIX 98 MAINTENANCE LOG 98 WARRANTY POLICY 99 18 Month COMPREHENSIVE WARRANTY 99 LIMITED FIVE ...

Страница 5: ...located out of traffic and away from furniture and draperies Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition Young children should be carefully supervised when they are in the same room as the appliance Toddlers young children and others may be susceptible to accidental contact burns A physical barrier is rec...

Страница 6: ...ge etc and shall specify the following test procedure WARNING Proposition 65 Warning Fuels used in gas wood burning or oil fired appliances and the products of combustion of such fuels contain chemicals known to the State of California to cause cancer birth defects and other reproductive harm California Health Safety Code Sec 25249 6 In the State of Massachusetts only a licensed plumber and gas fi...

Страница 7: ...replaces have been certified and tested to work with Natural Gas or Propane Certification Information ANSI Z21 88 CSA 2 33 2014 Vented Gas Fireplace Heaters CSA CLASSES CLASS 2901 84 CLASS 2901 04 All fireplaces are rated for commercial and residential use The CSA Mark The Canadian Standards Association CSA is a nonprofit association serving business industry government and consumers in Canada and...

Страница 8: ...stallation please use the ICC installation guide http icc chimney com en exceldirect support This product is listed to ANSI standards for Vented Gas Fireplace Heaters and applicable sections of Gas Burning Heating Appliances for Manufactured Homes and Recreational Vehicles and Gas Fired Appliances for Use at High Altitudes Installation MUST comply with local regional state and national codes and r...

Страница 9: ...lectric power is supplied to it The Fireplace power supply needs to be wired by QUALIFIED ELECTRICIAN The electrician can provide the operator a switch to control the outlet the fireplace is connected to The use of the plug should only be done when access to the outlet is available even after installation is completed This appliance must be grounded In the event of a malfunction or breakdown groun...

Страница 10: ... SWITCH The Fireplace ON OFF operation can be done with a standard wall switch provided by the electrician and wired to control the supply of power to the fireplace outlet or hardwire setup Honeywell System Diagram ...

Страница 11: ...t cover view open to be able to view the pilot spark and flame from outside Fireglass a or Fire Glass may be used b When the fireplace viewing window is open and media is placed make sure Fire Glass does not fall on the ceramic glass lower frame as that may cause breakage when putting back the ceramic glass c Make sure pilot is clear of any Fire Glass particles d Flare Fire Glass can be put safely...

Страница 12: ...ONS Please follow the below described quantities of media placement in your firebox Please note over saturation of media throughout the firebox may result in improper combustion or Soot within the fireplace or termination cap ...

Страница 13: ...t viewing glass and is provided with this appliance It must remain installed for the protection of children and other at risk individuals Do NOT operate the fireplace without the safety screen barrier Front See Through and Corner Units Safety screen removal requires no tools Push the top frame of the screen up until it clears the bottom of the opening Tilt the bottom of the screen out and pull dow...

Страница 14: ...uld be done once during install only Attach glass suction cups to the glass Use more than one suction cup if needed any unit above 45 Using suction cups slightly push in the external glass top edge Once glass has been pushed slightly lift the glass to clear bottom part of the glass Remove the glass and place in a secure location Install back external glass Attach glass suction cups to the glass Us...

Страница 15: ...y a licensed or qualified service person Step 1 Attach glass suction cups to the glass Remove the glass lower magnetic trim Place the trim in a secure place Any unit above 45 requires 2 suction cups to hold the glass Step 2 Release the lower glass trim The lower trim bolts can be released by hand and should not require any tools Once bolts are released remove lower glass holder trim Step 3 Hold th...

Страница 16: ...4 1 Step 4 2 When putting back the glass DO NOT overtighten the bolts or glass may break Use step 4 1 for putting the glass back Glass trim screws should be closed hand tight DO NOT overtighten the bolts or glass may break ...

Страница 17: ...TALLATION FLARE H EH Side Glass trim for Front ST unit R H EH is installed by Hanging the side trim over the trim holder as shown in the picture below Then moving the lower side of the trim toward the holder as shown in the picture below ...

Страница 18: ...TALLATION C RD Side Glass trim for C RD unit R H EH is installed by placing the side trim over the trim holder magnetics as shown in the picture below Then moving the lower side of the trim toward the holder as shown in the picture below ...

Страница 19: ...o clean The reflective back is shipped outside the unit inside a sleeve with the other glass panes It should be mounted at the back of the fireplace placed in the gap between the fire bed shown yellow below and held by the top mounting brackets red circle Carefully carry the reflective back using suction cups and place at a 45 degree angle as shown below Screw the mirror clamp as shown below make ...

Страница 20: ...ut the Fireplace in the desired location Verify clearance to non combustible and combustible materials Follow the clearance instruction and example in the manual 5 For LED units connect LED system and test LED 6 Attach the units back bracket to the wall framing 7 For double glass units only remove glass locking screws and discard 8 Adjust Fireplace vent restrictor based on vent configuration and p...

Страница 21: ...e necessary parts that may need servicing over time While Flare also offers access to these components by going inside the fireplace with instructions HERE you will find having a dedicated area where all your components can be easily accessed for servicing without the need to remove the glass media burner is the preferred method HIDDEN ACCESS PANEL EXAMPLE ...

Страница 22: ...and confirm there is no external damage If damage exists please notify Flare Fireplaces immediately Remove the top wood studs and pull the external carton box up Please do not remove the blue wrap completely at this stage Leave the fireplace placed on the pallet for the next step Fireplace legs setup ...

Страница 23: ... telescopic legs extracted to a minimum of 3 Installing fireplace without telescopic legs is a fire hazard Installing the Fireplace without legs sitting on the fireplace frame may bend the frame cause glass breakage Fine Tuning After extending the legs to the desired length use the wrench included to fine tune the feet so that the fireplace is level Note that the feet are intended for minimal adju...

Страница 24: ...hree screws to secure the telescopic leg in position Note that the top pin inserts into the holes only for alignment The two bottom screws tighten down on the legs Step 5 Repeat Steps 1 4 for each on the fireplace so that they are all extended to the same length Step 6 Stand the fireplace up and fine tune the feet with the wrench included so the fireplace is level Open the screws to raise the fire...

Страница 25: ...he 4 screws so that the fireplace will stand at the desired height after the foot for fine tuning is also screwed in Insert the 4 screws into the holes and Rivnuts beneath and tighten Screw in the foot so that it can later be adjusted to slightly raise or lower the fireplace Configure remaining legs to the same height Stand the fireplace up and fine tune the feet with the wrench provided so the fi...

Страница 26: ...test of unit Place accessories white bag in a secure location The control unit gas valve and receiver is attached to the fireplace on an umbilical cord Once fireplace is moved to its final location the control unit can be put close to the service access door Gas valve and receiver GAS VALVE WILL COME WRAPPED ONLY TO BE OPENED FOR UNITS FIRST FIREUP Optional control module for double glass units ...

Страница 27: ...aming Use the manual clearance guide for more details Attach the fireplace top brackets to the metal stud in the back to secure the fireplace in place The bracket length can be adjusted by releasing the screws on the top Fireplace should remain on the wood pallet when carried to final installation location Do not attempt to use a pallet jack or any other moving tools if the unit has been removed f...

Страница 28: ...Double Glass unit LED power is connected to the Flare control system Labeled in picture above as LED Power Outlet and below as Connection C LED will turn On and Off with the fireplace controlled by the fireplace remote or wall switch Color control can be done by the LED remote Once a color is selected the LED remote can be stored away LED to be switched Off when fireplace is turned off LED cannot ...

Страница 29: ...e connected prior to shipping Connect LED connectors points A to the fireplace using the quick connect connectors 3 Connect LED control system to the power supply point B 4 Connect LED Power supply to an external power source point C Do not connect the LED to the Flare control LED plug at this point Use the LED remote to turn the LED on the LED system Once testing is done connect the LED power ada...

Страница 30: ... FABRICATION PROCESSING Multicolor Printing UV Varnish CONTROLLER SIZE 85x45x23mm WORKING VOLTAGE DC12V 24V CONTROL WAY RGB 3 CHANNELS MAX LOAD PER CHANNEL 6A OUTPUT CONNECTION COMMON ANODE TELECONTROL DISTANCE 30 METERS PROGRAMS 20 KINDS LED Strip Y cable LED POWER 24V or ...

Страница 31: ...REEN COLOR GLITTERS ADJUSTABLE ADJUSTABLE 16 BLUE COLOR FREQUENTLY BLINKS ADJUSTABLE ADJUSTABLE 17 BLUE COLOR GLITTERS ADJUSTABLE ADJUSTABLE 18 YELLOW COLOR FREQUENTLY BLINKS ADJUSTABLE ADJUSTABLE 19 YELLOW COLOR GLITTERS ADJUSTABLE ADJUSTABLE 20 CIRCULATION MODE Code Matching Please follow the instructions below Confirm it is correctly connected between power supply LED controller LED load Switch...

Страница 32: ...operation of the blowers is controlled with a power ON Off to the outlet they are connected to The customer has the option to Install a smart outlet to control the blowers Use a wall switch to start shutdown the blowers whenever they want An electrician will need to wire the wall switch to control the power to the fireplace fans Buy a remote system for the outlet Please note that the blowers will ...

Страница 33: ...ase use the ICC direct vent installation manual http icc chimney com en exceldirect Instructions Where a vent pipe passes through a floor or ceiling a ceiling firestop MUST be used to retain insulation and maintain proper clearances Use roof support brackets where needed Install the first section of vent pipe into the collar on top of the fireplace Connections between each vent system component mu...

Страница 34: ...ibles is required VERTICAL VENT CLEARANCES A minimum of 1 inch 25mm all around the vent pipe on all vertical runs to combustibles is required except for clearances in appliance enclosures Horizontal vents have a minimum 1 4 inch 6mm rise per 1 foot towards the termination When penetrating through combustible walls and ceilings frame a minimum of 10 5 in x 10 5 in opening and ensure that the insula...

Страница 35: ...vent part used Note size of vents depends upon specific fireplace and cutout sizes vary according to the DuraVent or ICC part number used Minimum height from roof to lowest discharge opening Vertical Vent Termination Opening Framing will depend on the part used See table above or vent installation manual Minimum 24 horizontal clearance to any surface such as an exterior wall for vertical terminati...

Страница 36: ...tiple horizontal terminations See the table on page 32 for minimum cutout dimensions or frame openings around wall venting Make sure clearances to combustible material are maintained based on vent part used Note size of vents depends upon specific fireplace and cutout sizes vary per the DuraVent part number used ...

Страница 37: ...aces require 24 inches 61 cm min Clearance to unventilated soffit F 6 15 cm min Clearance to outside corner G 6 15 cm min Clearance to inside corner H 3 90 cm min Not to be installed above a meter regulator assembly within 3 feet 90 cm horizontally from the centerline of the regulator I 3 feet 90 cm min Clearance to service regulator vent outlet J 12 inches 30 cm min Clearance to non mechanical ai...

Страница 38: ... Clearance in accordance with local installation codes and the requirements of the gas supplier As specified in CGA B149 Installation Codes note local Codes or Regulation may require different clearances For U S A Installations follow the current National Fuel Gas Code ANSI Z223 1 Horizontal vent termination minimum clearance to adjacent structure or fence is 48 Minimum 24 horizontal clearance to ...

Страница 39: ...The vent restrictor setting is from 1 minimum restriction to 6 maximum restriction The installer will document the restrictor setting in the end of the installation Use the vent planning guide and table to determine the restrictor setting Signs the vent restrictor needs to be adjusted Vent restrictor should be opened if the flame has the following characteristics Flame is excessively tall and lift...

Страница 40: ...tached example for clarification on how to use the table The numbers in the table represent the restrictor setting based on the vent path Symbol x in the table means the path is not allowed Setting the restrictor to 1 means there is no restriction Numbers in the table represent the restrictor setting to be set Document the restrictor setting configuration prior to leaving the installation site The...

Страница 41: ...41 Page FLARE 30 30H Suitable for all Flare 30 Fireplaces Vent Restrictor Setting Set to 1 6 based on Table below X Run may need to be Power Vented ...

Страница 42: ...42 Page FLARE 45 45H 45EH Suitable for all Flare 45 45H 45EH Fireplaces Vent Restrictor Setting Set to 1 6 based on Table below X Run may need to be Power Vented ...

Страница 43: ...43 Page FLARE 50 50H 50EH Suitable for all Flare 50 50H 50EH Fireplaces Vent Restrictor Setting Set to 1 6 based on Table below X Run may need to be Power Vented ...

Страница 44: ...44 Page FLARE 60 60H 60EH Suitable for all Flare 60 60H 60EH Fireplaces Vent Restrictor Setting Set to 1 6 based on Table below X Run will need to be Power Vented ...

Страница 45: ...45 Page FLARE 70 70H 70EH Suitable for all Flare 70 70H 70EH Fireplaces Vent Restrictor Setting Set to 1 6 based on Table below X Run will need to be Power Vented ...

Страница 46: ...46 Page FLARE 80 80H 80EH Suitable for all Flare 80 80H 80EH Fireplaces Vent Restrictor Setting Set to 1 6 based on Table below X Run will need to be Power Vented 6ft Minimum Rise ...

Страница 47: ...47 Page FLARE 100 100H 100EH Suitable for all Flare 100 100H 100EH Fireplaces Vent Restrictor Setting Set to 1 6 based on Table below X Run will need to be Power Vented 6ft Minimum Rise ...

Страница 48: ...s allow Flare Fireplaces to operate in vent conditions that would not be possible without the motor unit See the Flare Power Vent Installation Manual for more specific instructions The system is designed and tested with DuraVent 3x5 gasket direct vent pipes It is critical for the safety and operation of the system to use the DuraVent 3x5 gasket system ...

Страница 49: ...s less than 20 feet Refer to the Flare Power Vent Installation Manual for more specific instructions Clearance Clearances between the vent pipe and combustible materials must be maintained at 3 inches top and 1 for side and below Maintain the same clearance from the power vent box to any combustible materials Power vent unit must be installed by a qualified installer in accordance with these instr...

Страница 50: ...e cable labeled below as connection PV Power 115V Cable to be used is 16 AWG 4 copper wire Cable is not included with the PV kit and can be sourced separately Connect 4 wire high voltage cable from the Power Vent to matching colors white to white black to black green to green and red to red on the PV system The Flare Fireplaces Fan board is a must for operating a Flare Fireplace with a PV system ...

Страница 51: ...51 Page ELECTRICAL CONNECTION AND ADJUSTING TO THE PV SYSTEM ...

Страница 52: ...o or less than 1 2 psig 3 5 kPa Move the appliance into position and secure it to the wall using the back or side mount Install a manual gas valve before the connection to the fireplace appliance automatic valve Connect the gas line to the fireplace The appliance is designed to accept a 1 2 13mm gas supply Connect the gas supply in accordance with local codes CAN CSA B149 1 in Canada or to the cur...

Страница 53: ...53 Page SPARK REMOTE SENSE SENSE JUMPER WIRE CUSTOMIZE OPERATING SEQUENCE STATUS LED P1 VENT DAMPER CONNECTOR MV MV PV PV BRN GND 24 GND 24V OPT TH W OPT FLAME CURRENT MEASUREMENT PORTS ...

Страница 54: ...screw and tighten firmly to ensure proper operation Have the gas supply line installed in accordance with local codes if any If not available follow ANSI 223 1 Installation should be done by a qualified installer approved and or licensed as required by the locality in the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter USING A REDUCER TO DE RATE YOU...

Страница 55: ...rating reducer on installations above 4500 Ft If the installer must convert the unit to adjust for varying altitudes the information sticker must be filled out by the installer and adhered to the appliance at the time of conversion DE RATE TABLE MODEL GAS TYPE REDUCER SIZE CALC BTU STANDARD BTU 30 LPG 1 6 mm 18000 23000 45 LPG 1 9 mm 22000 28000 50 LPG 2 0 mm 27000 35000 60 LPG 2 2 mm 36000 43000 ...

Страница 56: ... gas remove power and locate your gas valve Once disconnected verify direction of gas flow by locating the flow arrow on top of the valve Turn off gas and remove hard line to valve SEE EXAMPLE 1 2 Add reducer between gas hard line and flex line connected to Honeywell valve on the burner side Us appropriate reducer as specified in DE RATE TABLE Pilot Gas Pilot GND Module GND Outlet gas Inlet gas In...

Страница 57: ...e and be put next to the access door location Do not place the gas valve or controls above the level of the burner If the fireplace is to sit low on the floor the controls must be placed outside the non combustible zone or insulated from the heat from the fireplace The access door can be placed on any side of the fireplace below the non combustible line The use of a 10 x10 access door is highly re...

Страница 58: ...EPLACE LP CONVERSION KIT ALWAYS MEASURE GAS INLET PRESSURE AND OUTLET PRESSURE POST CONVERSION Your Fireplace may be shipped to support Liquid Propane Gas Check your Flare Fireplaces gas rating plate at the back of your valve to confirm the gas type NOTICE Flare Fireplaces does offer the ability to run your fireplace with a liquid propane tank though there are certain limitations this fuel type pr...

Страница 59: ... line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection the...

Страница 60: ...lass The design allows cool air to flow between the two layers with the help of built in blowers which significantly lowers the temperature of the external glass making it safe for a brief touch Double Glass is suitable for commercial as well as residential use The double glass feature provides a sleek look with no frame while maintaining heating characteristics and efficiency This feature does no...

Страница 61: ...st be at least 100 square inches OPEN AIR FLOW For fireplaces sized 60 70 vent area must be at least 70 square inches OPEN AIR FLOW For fireplaces sized 50 and below vent area must be at least 50 square inches OPEN AIR FLOW FOR SEE THROUGH FIREPLACES THE AIR INTAKE REQUIREMENTS ARE DOUBLE EQUAL ON BOTH SIDES NOTE Openings above for Heat Release and Air Intake are measured for open air space The fa...

Страница 62: ...ulation above the fireplace may result in a Fire hazard Air flow above the fireplace should remain open to allow heat to be released from the top of the chase Follow the chart below for clearance and sizing It is recommended to double wall the area behind the TV to allow cables and other related material to be installed with less concern of blocking hot air flow Use non combustible material for do...

Страница 63: ...blocking hot air flow THE EXAMPLE SHOWN ABOVE IS NOT AN EXACT RENDERING OF EVERY FIREPLACE STYLE AND VENT PLACEMENT OFFERED BY FLARE BUT MEANT TO CONVEY RELEVANT MEASUREMENTS FOR USE ON ALL UNIT INSTALLATIONS FOR EXACT DRAWINGS OF THE FIREPLACES AND THEIR VENT PLACEMENT PLEASE DOWNLOAD DIMENSION OR FRAMING GUIDES FROM OUR DIRECT VENT DOWNLOAD CENTER ...

Страница 64: ...10 from the face of your finishing material to the back of the recess as it will hinder air flow damage the TV Warning Maintain Open Air flow between the fireplace and drywall Make sure cables or any other materials are not blocking hot air flow THE EXAMPLE SHOWN ABOVE IS NOT AN EXACT RENDERING OF EVERY FIREPLACE STYLE AND VENT PLACEMENT OFFERED BY FLARE BUT MEANT TO CONVEY RELEVANT MEASUREMENTS F...

Страница 65: ...ou must maintain a 1 clearance from your recess to the vent pipe to prevent overheating 2 Install two 45 elbows directly above the fireplace followed by a minimum 4 ft vertical vent rise The two small elbows will move the vertical section back 5 5 8 Note that the 1 inch clearance from the vent applies also to the back non combustible wall 3 Do not use any elbow with an angle larger than 45 degrees...

Страница 66: ...evision manufactures and manuals will instruct the owner not to install television above or near a fireplace Mounting a television above the fireplace is based on the owner s decision and responsibility Flare will not be held liable for any adverse effects on a TV artwork or other equipment located near the Flare appliance It is the customer s or contractor responsibility to verify that their TV o...

Страница 67: ...age CLEARANCES GENERAL INFORMATION AND STEPS All materials inside the chase and above the Fireplace must be non combustible or covered combustible only See more clearance information in the following pages ...

Страница 68: ... pipe on all horizontal runs to combustibles is required VERTICAL VENT PIPE CLEARANCES A minimum of 1 inch 25mm around the vent pipe on all vertical runs to combustibles is required Except for clearances in appliance enclosures Horizontal Vents must have a minimum 1 4 inch 6mm rise per 1 foot run towards the termination WARNING Never allow the vent to run downward A downward slope can trap heat an...

Страница 69: ...inimum clearance to sides and back Covered combustible Combustible material at the back or sides of the fireplace MUST be covered with non combustible material that is at least inch thick Covered wood can be placed a minimum 3 away from the side and back Example A non combustible cement board is placed 2 inches from the back of the fireplace The cement board used is inch thick Combustible material...

Страница 70: ... 18 must be covered Zone B There should be no combustible materials left uncovered above the fireplace inside the chase Fireplace chase should be designed and built to allow hot air to release from the unit and rise up in a non combustible channel to the heat release 13 Chase ceiling Top of the chase must be covered with noncombustible material Firestop No exposed combustible materials are allowed...

Страница 71: ...hen bringing your hearth to glass height it must be non combustible for the first 7 extending from the glass before any combustible material can be used to finish the hearth As seen in EXAMPLE 2 15 Adjacent Wall 1 Distance to any side adjacent wall must be at least 7 inches from the glass As seen in EXAMPLE 1 EXAMPLE 1 EXAMPLE 2 ...

Страница 72: ...e minimum inch Type X fire rated drywall MUST be used to finish around the front of the appliance Covered combustible material can be used to finish around the fireplace if the proper distance from the fireplace is maintained Use example below to find proper distance See Examples 1 2 below for further details EXAMPLE 1 ...

Страница 73: ...73 Page DO NOT connect materials to or drill into the metal fireplace frame This can result in excessive heat transfer and or damage to the fireplace and surrounding materials EXAMPLE 2 ...

Страница 74: ... metal fireplace frame This can result in excessive heat transfer and or damage to the fireplace and surrounding materials All joints between the finished wall sheathing and the appliance must be sealed with non combustible materials WARNING Risk of Fire DO NOT apply combustible materials beyond the minimum clearances Comply with all minimum clearances to combustibles as specified in this manual E...

Страница 75: ...ove the fireplace as anchor points Non combustible mantels do not have a minimum clearance to the fireplace opening and can be brought as close to the glass as allowed by the frame of the fireplace Please keep in mind any material used could potentially heat up dramatically the closer to the fireplace you bring it and the longer the fireplace is on REF Height Mantel Depth A 2 1 B 4 4 C 6 6 D 10 12...

Страница 76: ...rom the fireplace being operated normally DO NOT INSTALL A SPRINKLER IN THE FIREPLACE CAVITY Please follow local building code to determine what temperature setting is relevant for your installation WARNING VAULTED CEILINGS CAN CREATE A CHANEL THAT FUNNELS HOT AIR DIRECTLY TOWARDS A SPRINKLER HEAD PLACED AT THE PROPER DISTANCE FROM HEAT RELEASE AS STATED ABOVE IF SPRINKLER HEAD SENSOR IS NOT RATED...

Страница 77: ...d All rising heat should be able rise to the fire stop and freely flow though the heat release opening into the room AIR INTAKE Required for installation with double glass or safety screen with optional blower kit This allows air circulation which cools the external glass and increases the efficiency of the fireplace See diagram on page 63 These relatively quiet blowers cannot be turned off and ar...

Страница 78: ...78 Page EXAMPLES OF HEAT RELEASES ...

Страница 79: ...can evacuate the cavity above your fireplace the cooler your wall will be Flare offers many ways to implement a heat release that mask its existence allowing you to increase its size dramatically without ruining the visual aesthetic SEE SECTION REFERENCING EXAMPLES OF HEAT RELEASES AND AIR INTAKES IN FLARE INSTALLATION MANUAL For example if you are installing a Flare Fireplace with a 50 length you...

Страница 80: ...ing you to increase its size dramatically without ruining the visual aesthetic SEE SECTION REFERENCING EXAMPLES OF HEAT RELEASES AND AIR INTAKES IN FLARE INSTALLATION MANUAL For example if you are installing a Flare Fireplace with a 50 length you will need a minimum of 50 SQ of open air flow to cool your double glass successfully But by meeting the minimum specification allowed the glass temperatu...

Страница 81: ...E FRONT SEE THROUGH AND CORNER FIREPLACE CLEARANCE FLAT SIDE AND ISOMETRIC VIEW Warning Maintain open Air flow between the fireplace and drywall Make sure cables or any other materials are not blocking hot air flow ...

Страница 82: ...tatic vent opening The fireplace enclosure must allow air to rise and circulate from the top of the fireplace glass from lower vent opening to be released back to the room from the top To increase heating the enclosure should prevent hot air from being released to the attic by venting it back to the room using the static vent system A Non combustible stud MUST NOT be connected or drilled into the ...

Страница 83: ...83 Page L SHAPE SIDE AND ISOMETRIC VIEW ...

Страница 84: ...e released into the room using the top static vent opening The fireplace enclosure must allow air to rise and circulate from the top of the fireplace glass from lower vent opening to be released back to the room from the top To increase heating the enclosure should prevent hot air from being released to the attic by venting it back to the room using the static vent system A Non combustible stud MU...

Страница 85: ...outdoor kit will tolerate moderate amounts of water on an occasional basis but is not waterproof The fireplace must be enclosed in a weatherproof enclosure covered in typical weatherproof material such as siding stucco stone tile etc and have a weatherproof structure to shed water that extends horizontally beyond the front and side perimeter of the fireplace Water running down vertical surfaces sh...

Страница 86: ...lace is fully turned off when attempting to clean the front of the fireplace including pilot Use the Flare architectural guide for information on the window size and opening http flarefireplaces com portfolio items flare outdoor ...

Страница 87: ...age All studs and surrounding should follow the fireplace clearances and non combustible requirements The outdoor window kit should be sealed with non combustible tape prior to covering with brick or stucco ...

Страница 88: ...cm 55 cm 35 cm 50 1 16 14 22 14 60 3 E 150 cm 35 cm 80 cm 35 cm 59 15 16 14 32 14 70 3 F 175 cm 35 cm 105 cm 35cm 684 16 14 40 14 80 3 G 215 cm 55 cm 105 cm 55 cm 84 22 40 22 100 3 For updated product dimensions and framing information please visit Flare s PRODUCT PAGE navigate to the product of your choice scroll to four tabbed charts click DOWNLOAD CENTER ...

Страница 89: ... system will need to control the Power supply ON OFF to the fireplace outlet or direct wire connection DO NOT CONTROL FIREPLACE FROM OUTSIDE OF HOME USING EXTERNALLY CONNECTED DEVICE ONLY OPERATE 3RD PARTY APPLICATION OR HOME AUTOMATION WHEN YOU CAN PHYSICALLY SEE THE FIREPLACE TURNING ON OFF IT IS NOT MEANT TO OPERATE WITHOUT LINE OF SIGHT TO FIREPLACE CAUTION ...

Страница 90: ...minal remains connected Hard wire 3 way connector wires between valve and control module according to labeling IE PV to PV PVMV to PVMV MV to MV GND Module to GND mark Valve 24vac which is came from the transformer are connected to the 24VGND and TH W transformer is connected to the 110 AC by home socket or by control system Figure SEQ Figure1 overall connection between the pilot valve and module ...

Страница 91: ...91 Page HONEYWELL DIAGRAM DOUBLE GLASS AND POWER VENT AC in 110 AC out 110v Power 110V to RGB LED Power Supply ...

Страница 92: ... with above The third Dipswitch is the Master Bypass PV Relay Fan dipswitch Representing 4 switches 1 3 are used and the 4th switch is not used Switch 1 is used to determine if the system has PV or not Turn the switch ON UP to bypass monitoring of PV system OFF DOWN to begin to monitor PV system Switch 2 is used to Bypass the relay to the Board so that the board will begin work directly when get 1...

Страница 93: ... LED INDICATOR The Blue Power Vent LED lets you know the Power Power Vent is properly sending receiving signal to the board FAN POWER VENT REQUEST LED The White LED indicates the USER has requested to start the fans Power Vent if connected ELECTRIC DIAGRAM PV SYSTEM 4 wire cable 110V from Fireplaces ...

Страница 94: ...neywell Remote Remote for Honeywell System Honeywell Receiver Receiver for Honeywell System Honeywell Ground Cable Ground Cable for Honeywell System Honeywell Module Board Control Board for Honeywell System Honeywell 110 X 1 Cable with Molex Honeywell System Double Glass Adapter Wiring Harness with Molex Honeywell Pilot Assembly NG Natural Gas Pilot assembly for Honeywell System Honeywell Pilot As...

Страница 95: ...to form and results in damage is not the responsibility of the manufacturer Do not modify or substitute any part of this appliance Inspect the external vent cap on a regular basis to make sure that no debris plants trees or shrubs are interfering with the air flow Do not operate the fireplace without the fireplace glass It is imperative that control compartments screens or fans system for double g...

Страница 96: ...peration and burner ignition Burner Maintenance The flames from the burner should be visually checked The flame should have a blue base and yellow tops and be candle like in appearance If excessive soot is found inside the firebox area the fireplace will require adjustment Verify the air shutter and vent restrictor setting and document any changes If the flame becomes sooty dark orange in color or...

Страница 97: ...d screw that can be turned to either increase or decrease the air to gas mixture See Ex 1 above for visual Example 2 The second option allows you to adjust your Flare Fireplaces air shutter by accessing it from directly underneath the fireplace See Ex 2 above for visual FOR CLARITY ON HOW YOUR ADJUSTMENTS IMPACT THE FLAME COLOR AND SOOTING PLEASE CLICK THIS LINK TO WATCH AN ELABORATE AIR SHUTTER V...

Страница 98: ...ny Name_________________________________________________________ Technician NPI ________________________________________________________ Service Information ___________________________________________________________ Yearly Maintenance _________________ Other __________________________ Details __________________________________________________________________________________ ______________________...

Страница 99: ...s include the following components Gas Valve Receiver Remote LED Lighting Strips Remote Controller Authorized Media Wall Switch This warranty does not apply to any component that shows evidence of misuse abuse improper installation exposure to water or moisture excessive heat dust or paint LIMITED FIVE YEAR COVERAGE Effective for five years from the original date of purchase Flare Fireplaces Limit...

Страница 100: ...er is unable to provide necessary parts contact the nearest Flare Fireplaces authorized dealer or supplier EXCLUSIONS This warranty does not apply to any component that shows evidence of misuse abuse improper installation accident or lack of maintenance Flare Fireplaces is not responsible for televisions mantels surrounds or finishing material around the fireplace Flare Fireplaces is not responsib...

Отзывы: