background image

VALLOX 130 E

Code

Name

Technical data 

Standard 

(factory settings in parentheses)

/ Option

© VALLOX • We reserve the right to make changes without prior notification.

Parts list VALLOX 130 E VKL

G3

Filter, extract air and supply air

G3

Standard

F7

Fine filter, supply air

F7

Standard

H

HR bypass damper

Manual

Standard

HS 

Speed selection switch

4-step

Standard

LP2

Post-heating radiator

1-row liquid radiator

Standard

HR

Heat recovery cell

1-step, efficiency 60 %

Standard

PDS

Pressure difference switch 

Adjustment range 0...500 Pa 

Option

Pressure guard for the supply air side

Factory setting 250 Pa

PF

Extract air fan

125 l/s (100 Pa)

Standard

SV

Thermostat valve with removable sensor Self-actuated

Option

TF

Supply air fan

105 l/s (100 Pa)

Standard

HK

Maintenance switch

Door switch

Standard

TS3

Water radiator defrost thermostat

Factory s5 ˚C

Standard

TS4

HR defrost thermostat

Factory s4 ˚C

Standard

S

Fireplace switch

Opening points 15…30 minutes

Option

LP1

Preheating radiator

VALLOX 1000, 1 kW

Option

G1

Filter (incl. in) LP1

For preheating radiator LP1

TS6

Limiting thermostat (incl. in LP1)

Factory setting 17 ˚C

TS7

Overheat protector (incl. in LP1)

90 ˚C, manually reset

TS5

Regulating thermostat

Vallox thermostat 0…40  ˚C

Option

SP 

Damper 2 pcs 

Air flow operated 

Standard

13

OPERATION AND FUNCTIONAL DIAGRAM FOR VALLOX 130 E VKL / water radiator

Silencer

Silencer

Control of operation

Power supply to the unit is controlled with the 0/1 switch in the distribution
panel. There is also a maintenance switch 

HK

 inside the unit. It stops

power supply when the maintenance door of the unit is opened.

Fan speed adjustment

The fans of the unit, 

TF

 and 

PF

, are controlled depending on operating

conditions with a separate 4-step (1, 2, 3 and 4) speed selector switch
HS located in the ventilation zone.

Supply air temperature

Self-actuated control valve 

SV

 (optional) controls the operation of post-

heating radiator 

LP2

, maintaining the temperature of supply air going

out from the unit at the setpoint value.

Preheating

Preheater 

LP1

 is an optional device, which can be mounted in the outdoor

duct. The radiator can be used to preheat outdoor air and decrease the
stopping of the fan. Thermostat 

TS5

 switches the radiator on before

thermostat 

TS4

 stops the supply fan.

Preheating radiator overheat protector

Thermostat 

TS6

 controls the operation of electric radiator 

LP1

, preventing

radiator surface temperature from exceeding the threshold. As temperature
exceeds the threshold, radiator overheat protector 

TS7

 is triggered and

power supply to the radiator is stopped. The overheat protector is reset
manually.

Heat recovery bypass

Summer-time bypass of heat recovery cell 

HR 

is done manually by turning

HR

 damper 

H

 in the bypass position for the summer.

Heat recovery defrost

Thermostat 

TS4

 of the 

HR

 cell keeps stopping supply air fan 

TF

, thereby

preventing the risk of the freezing of the 

HR

 cell. The fan starts automatically

as soon as the risk of freezing has passed. The threshold temperature
of the risk of freezing can be set at thermostat 

TS4

.

Water radiator anti-freeze

When the surface temperature of the water radiator goes below the
setpoint, freezing protection thermostat 

TS3

 of post-heating radiator 

LP2

stops the unit and the self-actuated dampers 

SP

 close, decreasing the

freezing risk of the water radiator. The unit starts automatically as soon

as the risk of freezing has passed. The threshold temperature of the risk of
freezing can be set at the thermostat 

TS3

.

Alarms

Pressure difference switch 

PDS

 is an optional device for controlling pressure

difference on the supply air side. If the pressure difference rises above the
setup, because of dirty filters or clogged ducts, an indicator is lit on the front
panel of the unit.

Fireplace switch function

The unit can be equipped with an optional fireplace switch 

S

. It can be a

timer equipped with opening points. Timing period can be 15…30 minutes.

F 7

M

G 3

PF

TF

PDS

TS6

G 3

H

TS5

HS

TS3

S

TS7

G 1

M

TS4

10 A

VALLOX 130 E

10 A / 16 A

HR

LP1

LP2

HK

L

SV

Ljm

Ljp

SP

SP

CONTROL DIAGRAM VALLOX 130 E VKL / post-heating – fluid radiator

VENTILATION ZONE

INTERNAL ELECTRICAL AND

CONTROL CONNECTIONS

FIREPLACE

SWITCH

PREHEATING

RADIATOR

POST-HEATING
RADIATOR

SPEED SELECTOR

DISTRIBUTION

PANEL

Summary of Contents for 130 E

Page 1: ...210 W 125 dm3 s 100 Pa 1 09 84E 28 10 2008 VALLOX Technical specifications Code 3500 E 130 E R electric radiator model 130 E VKL R water radiator model Maximum air flow 130 dm3 s 50 Pa ductwork pressu...

Page 2: ...00 W water Heat recovery cell Outdoor air filter F7 Outdoor and extract air pre filter G3 Summer winter damper Connection outlets 160 mm with seals Wall bracket MAIN PARTS Cover of lower housing Elect...

Page 3: ...t air ducts by octave band Lw dB ADJUSTMENT POSITION VOLUME FLOW RATE A weighted sound pressure level dB A coming from 130 E through the envelope to the rooms where the unit has been installed 10 m2 s...

Page 4: ...OX SILENCER EXTRACT AIR 10 m2 sound absorption ROOM SOUND MEASUREMENT MOUNTING Expected sound levels dB A in a room with VALLOX silencer SUPPLY AIR 10 m2 sound absorption rate air flow volume to the r...

Page 5: ...e supply air duct after the silencer by octave band Lw dB Medium frequency of the octave band Hz 63 125 250 500 1000 2000 4000 8000 Lw dB total 1 60 2 80 33 16 3 100 44 40 4 120 57 45 5 140 69 52 6 16...

Page 6: ...r the unit are 2 4 6 and 8 An expert can select different speeds at the transformer of the unit Remote monitoring control It is sometimes necessary e g in public premises to control the unit by remote...

Page 7: ...the exhaust air duct as close to the unit as possible The supply air heater switches on and the thermostat indicator lights up when exhaust air temperature goes below the setpoint of the thermostat If...

Page 8: ...lating radiator connections In the VKL model it is also possible to bring non freezing heat transfer fluid into the post heating radiator In addition the radiator can be provided with a separate non f...

Page 9: ...ir temperature rise in the heat recoverycell with an electric and water radiator Curve 1 Supply air temperature without post heating only heat recovery Curve 2 Supply air temperature controlled by the...

Page 10: ...ion V Filter guard indicator option OK Separate speed selector HK Maintenance switch KK Operating switch TK Fireplace switch option For instance a 15 minute timer with opening points Mounted to replac...

Page 11: ...XTERNAL ELECTRICAL CONNECTIONS VALLOX 130 E control with cooker hood PTXP I 130 VALLOX 130 E remote monitoring VALLOX 1993 A YK CONNECTION BOX VALLOX 130 E COOKER HOOD PTXP I 130 DISTRIBUTION PANEL RE...

Page 12: ...he unit at the setpoint Overheat protector of the electric radiator Thermostat TS1 controls the operation of electric radiator LP2 preventing radiator surface temperature from exceeding the threshold...

Page 13: ...LP1 is an optional device which can be mounted in the outdoor duct The radiator can be used to preheat outdoor air and decrease the stopping of the fan Thermostat TS5 switches the radiator on before t...

Page 14: ...the adjacent figure When needed you can use a lock mounting at the lower part of the unit DURING MOUNTING THE UNIT RISES 10 MM HIGHER THAN THE FINAL HEIGHT VALLOX 130 E UPPER EDGE LOWER EDGE OF BRACK...

Page 15: ...e outlet collars in the ceiling mounting plate enable the mounting of the ductwork before mounting the unit 160 outlet collar female 160 rubber ring outlet Wall mounting plate Ceiling mounting plate o...

Page 16: ...fter the water seal The unit has to be mounted level with the horizontal in order to ensure that condensing water can get out of the unit NOTE If the unit is mounted e g above a hot water accumula tor...

Reviews: