background image

VALLOX 130 E

© VALLOX • We reserve the right to make changes without prior notification.

Parts list VALLOX 130 E

G3

Filter, extract air and supply air

G3

Standard

F7

Fine filter, supply air

F7

Standard

H

HR bypass damper

Manual

Standard

HS 

Speed selector switch

4-step

Standard

LP2

Post-heating radiator

Electric radiator 1 kW

Standard

HR

Heat recovery cell

1-step, efficiency 60 %

Standard

PDS

Pressure difference switch 

Adjustment range 0...500 Pa 

Option

Pressure guard for the supply air side

Factory setting 250 Pa

PF

Extract air fan

125 l/s (100 Pa)

Standard

TF

Supply air fan

105 l/s (100 Pa)

Standard

HK

Maintenance switch

Door switch

Standard

TS1

Safety thermostat

Threshold value +40 ˚C

Standard

TS2

Overheat protector 2 pcs

95 ˚C, manually reset

Standard

TS3

Post-heating regulating thermostat

Adjustment range 0...25 ˚C

Standard

TS4

HR defrost thermostat

Factory s4 ˚C

Standard

S

Fireplace switch

Opening points 15…30 minutes

Option

LP1

Preheating radiator

VALLOX 1000,1 kW

Option

G1

Filter (incl. in LP1)

For preheating radiator LP1

TS6

Limiting thermostat (incl. in LP1)

Factory setting 17 ˚C

TS7

Overheat protector (incl. in LP1)

90 ˚C, manually reset

TS5

Regulating thermostat

Vallox thermostat 0…40  ˚C

Option

Code

Name

Technical data 

Standard / Option

(factory settings in parentheses)

OPERATION AND FUNCTIONAL DIAGRAM FOR VALLOX 130 E / electrical radiator

12

Control of operation

Power supply to the unit is controlled with the 0/1 switch in the
distribution panel. There is also a safety switch 

HK

 inside the unit. It

stops power supply when the maintenance door of the unit is opened.

Fan speed adjustment

The fans of the unit, 

TF

 and 

PF

, are controlled depending on operating

conditions with a separate 4-step (1, 2, 3 and 4) speed selector switch

HS

 located in the ventilation zone.

Supply air temperature

Regulating thermostat 

TS3

 controls the operation of electric radiator

LP2

, keeping the supply air going out from the unit at the setpoint.

Overheat protector of the electric radiator

Thermostat 

TS1

 controls the operation of electric radiator 

LP2

, preventing

radiator surface temperature from exceeding the threshold. As
temperature exceeds the threshold, radiator overheat protector 

TS2

 is

triggered and power supply to the radiator is stopped. The overheat
protector is reset manually.

Heat recovery bypass

Summer-time bypass of heat recovery cell 

HR

 is done manually by

turning 

HR

 damper 

H

 in the bypass position for the summer.

Heat recovery defrost

Thermostat 

TS4

 of the 

HR

 cell keeps stopping supply air fan 

TF

, thereby

preventing the risk of the freezing of the 

HR

 cell. The fan starts

automatically as soon as the risk of freezing has passed. The threshold
temperature of the risk of freezing can be set at thermostat 

TS4

.

Preheating

Preheater 

LP1

 is an optional device, which can be mounted in the

outdoor duct. The radiator can be used to preheat outdoor air and
decrease the stopping of the fan. Thermostat 

TS5

 switches the radiator

on before thermostat 

TS4

 stops the supply fan.

Preheating radiator overheat protector

Thermostat 

TS6

 controls the operation of electric preheating radiator

LP1

, preventing radiator surface temperature from exceeding the

threshold. As temperature exceeds the threshold, radiator overheat

VENTILATION ZONE

DISTRIBUTION

PANEL

VALLOX 130 E

INTERNAL ELECTRICAL AND

CONTROL CONNECTIONS

FIREPLACE

SWITCH

PREHEATING

RADIATOR

POST-HEATING
RADIATOR

PF

TF

WT

SPEED SELECTOR

Silencer

Silencer

CONTROL DIAGRAM VALLOX 130 E / post-heating – electrical radiator

protector 

TS7

 is triggered and power supply to the radiator is stopped. The

overheat protector is reset manually.

Alarms

Pressure difference switch 

PDS

 is an optional device for controlling pressure

difference on the supply air side. If the pressure difference rises above the
setup, because of dirty filters or clogged ducts, an indicator is lit on the front
panel of the unit.

Fireplace switch function

The unit can be equipped with an optional fireplace switch 

S

. It can be a timer

equipped with opening points. Timing period can be 15…30 minutes.

Summary of Contents for 130 E

Page 1: ...210 W 125 dm3 s 100 Pa 1 09 84E 28 10 2008 VALLOX Technical specifications Code 3500 E 130 E R electric radiator model 130 E VKL R water radiator model Maximum air flow 130 dm3 s 50 Pa ductwork pressu...

Page 2: ...00 W water Heat recovery cell Outdoor air filter F7 Outdoor and extract air pre filter G3 Summer winter damper Connection outlets 160 mm with seals Wall bracket MAIN PARTS Cover of lower housing Elect...

Page 3: ...t air ducts by octave band Lw dB ADJUSTMENT POSITION VOLUME FLOW RATE A weighted sound pressure level dB A coming from 130 E through the envelope to the rooms where the unit has been installed 10 m2 s...

Page 4: ...OX SILENCER EXTRACT AIR 10 m2 sound absorption ROOM SOUND MEASUREMENT MOUNTING Expected sound levels dB A in a room with VALLOX silencer SUPPLY AIR 10 m2 sound absorption rate air flow volume to the r...

Page 5: ...e supply air duct after the silencer by octave band Lw dB Medium frequency of the octave band Hz 63 125 250 500 1000 2000 4000 8000 Lw dB total 1 60 2 80 33 16 3 100 44 40 4 120 57 45 5 140 69 52 6 16...

Page 6: ...r the unit are 2 4 6 and 8 An expert can select different speeds at the transformer of the unit Remote monitoring control It is sometimes necessary e g in public premises to control the unit by remote...

Page 7: ...the exhaust air duct as close to the unit as possible The supply air heater switches on and the thermostat indicator lights up when exhaust air temperature goes below the setpoint of the thermostat If...

Page 8: ...lating radiator connections In the VKL model it is also possible to bring non freezing heat transfer fluid into the post heating radiator In addition the radiator can be provided with a separate non f...

Page 9: ...ir temperature rise in the heat recoverycell with an electric and water radiator Curve 1 Supply air temperature without post heating only heat recovery Curve 2 Supply air temperature controlled by the...

Page 10: ...ion V Filter guard indicator option OK Separate speed selector HK Maintenance switch KK Operating switch TK Fireplace switch option For instance a 15 minute timer with opening points Mounted to replac...

Page 11: ...XTERNAL ELECTRICAL CONNECTIONS VALLOX 130 E control with cooker hood PTXP I 130 VALLOX 130 E remote monitoring VALLOX 1993 A YK CONNECTION BOX VALLOX 130 E COOKER HOOD PTXP I 130 DISTRIBUTION PANEL RE...

Page 12: ...he unit at the setpoint Overheat protector of the electric radiator Thermostat TS1 controls the operation of electric radiator LP2 preventing radiator surface temperature from exceeding the threshold...

Page 13: ...LP1 is an optional device which can be mounted in the outdoor duct The radiator can be used to preheat outdoor air and decrease the stopping of the fan Thermostat TS5 switches the radiator on before t...

Page 14: ...the adjacent figure When needed you can use a lock mounting at the lower part of the unit DURING MOUNTING THE UNIT RISES 10 MM HIGHER THAN THE FINAL HEIGHT VALLOX 130 E UPPER EDGE LOWER EDGE OF BRACK...

Page 15: ...e outlet collars in the ceiling mounting plate enable the mounting of the ductwork before mounting the unit 160 outlet collar female 160 rubber ring outlet Wall mounting plate Ceiling mounting plate o...

Page 16: ...fter the water seal The unit has to be mounted level with the horizontal in order to ensure that condensing water can get out of the unit NOTE If the unit is mounted e g above a hot water accumula tor...

Reviews: