background image

VALLOX 130 E

R

0

10

20

30

40

°

C

0

10

20

3

0

40

°

C

© VALLOX • We reserve the right to make changes without prior notification.

VALLOX 1000 supply air heater

Instructions for regulating the defrost thermostats for VALLOX 130 E and VALLOX
1000 preheater

• The recommended adjustment for the supply air heater thermostat is circa

+5 

°

C...10 

°

C, however slightly higher than the adjustment for the defrost

thermostat of VALLOX 130 E. This enables the functioning of the preheating
resistor before the stopping of the fan and ensures that preheating is truly
beneficial.

• You can check how defrost functions by comparing the functioning of the supply

air fan and preheating. If the fan stops before the supply air heater switches on
to heat, you have to adjust the defrost thermostat somewhat lower, from  +5 

°

C

to +3 

°

C for example, or increase the setting for the thermostat of the supply air

heater. The indicator of the supply air heater thermostat shows you when the
heater switches on to heat.

• The preheating resistor heats even though the supply air fan has stopped.

Consequently, underpressure causes air coming from the outside to become
warmer before the cell, shortening the time during which the fan is stopped.

The outdoor air duct of VALLOX 130 E can be equipped with an optional VALLOX
1000 supply air heater. The sensor of a separate thermostat on the heater is
mounted in the exhaust air duct as close to the unit as possible. The supply air
heater switches on and the thermostat indicator lights up when exhaust air
temperature goes below the setpoint of the thermostat. If exhaust air temperature
goes even lower, the defrost thermostat of VALLOX 130 E stops the supply air
fan. The preheating resistor switches off when exhaust air temperature is circa

°

C higher than the value set for the thermostat.

SUMMER SETTING

HEAT RECOVERY BYPASS

WINTER

SETTING

7

HEAT RECOVERY BYPASS

PREHEATING OF OUTDOOR AIR (option)

DEFROSTING OF THE HEAT RECOVERY CELL

B

A

J

In winter use

 the heat recovery cell of VALLOX

130 E recovers heat from the air leaving the
dwelling and uses it to heat the air coming
from the outside.

Water condensing from extract air may freeze in the heat recovery cell. Freezing
can be prevented by stopping the supply air fan (standard function) or by switching
the (optional) pre-heating resistor on. Both these functions are automatic.
The defrost thermostat (J) stops the supply air fan whenever the temperature of extract
air goes down to circa +5

°

C. The fan restarts when temperature has risen by three

degrees, i.e. to +8

°

C. The threshold value of the thermostat can be adjusted.

In summer use

 when it is warm outside, it is unnecessary to heat outdoor air. The heat recovery

cell is then bypassed in VALLOX 130 E with the standard damper (A). The position of the
damper can be changed using the handle (B). In the summer position air flow through the
cell is prevented, and heat recovery bypass is activated.

VALLOX thermostat 0–40

Summary of Contents for 130 E

Page 1: ...210 W 125 dm3 s 100 Pa 1 09 84E 28 10 2008 VALLOX Technical specifications Code 3500 E 130 E R electric radiator model 130 E VKL R water radiator model Maximum air flow 130 dm3 s 50 Pa ductwork pressu...

Page 2: ...00 W water Heat recovery cell Outdoor air filter F7 Outdoor and extract air pre filter G3 Summer winter damper Connection outlets 160 mm with seals Wall bracket MAIN PARTS Cover of lower housing Elect...

Page 3: ...t air ducts by octave band Lw dB ADJUSTMENT POSITION VOLUME FLOW RATE A weighted sound pressure level dB A coming from 130 E through the envelope to the rooms where the unit has been installed 10 m2 s...

Page 4: ...OX SILENCER EXTRACT AIR 10 m2 sound absorption ROOM SOUND MEASUREMENT MOUNTING Expected sound levels dB A in a room with VALLOX silencer SUPPLY AIR 10 m2 sound absorption rate air flow volume to the r...

Page 5: ...e supply air duct after the silencer by octave band Lw dB Medium frequency of the octave band Hz 63 125 250 500 1000 2000 4000 8000 Lw dB total 1 60 2 80 33 16 3 100 44 40 4 120 57 45 5 140 69 52 6 16...

Page 6: ...r the unit are 2 4 6 and 8 An expert can select different speeds at the transformer of the unit Remote monitoring control It is sometimes necessary e g in public premises to control the unit by remote...

Page 7: ...the exhaust air duct as close to the unit as possible The supply air heater switches on and the thermostat indicator lights up when exhaust air temperature goes below the setpoint of the thermostat If...

Page 8: ...lating radiator connections In the VKL model it is also possible to bring non freezing heat transfer fluid into the post heating radiator In addition the radiator can be provided with a separate non f...

Page 9: ...ir temperature rise in the heat recoverycell with an electric and water radiator Curve 1 Supply air temperature without post heating only heat recovery Curve 2 Supply air temperature controlled by the...

Page 10: ...ion V Filter guard indicator option OK Separate speed selector HK Maintenance switch KK Operating switch TK Fireplace switch option For instance a 15 minute timer with opening points Mounted to replac...

Page 11: ...XTERNAL ELECTRICAL CONNECTIONS VALLOX 130 E control with cooker hood PTXP I 130 VALLOX 130 E remote monitoring VALLOX 1993 A YK CONNECTION BOX VALLOX 130 E COOKER HOOD PTXP I 130 DISTRIBUTION PANEL RE...

Page 12: ...he unit at the setpoint Overheat protector of the electric radiator Thermostat TS1 controls the operation of electric radiator LP2 preventing radiator surface temperature from exceeding the threshold...

Page 13: ...LP1 is an optional device which can be mounted in the outdoor duct The radiator can be used to preheat outdoor air and decrease the stopping of the fan Thermostat TS5 switches the radiator on before t...

Page 14: ...the adjacent figure When needed you can use a lock mounting at the lower part of the unit DURING MOUNTING THE UNIT RISES 10 MM HIGHER THAN THE FINAL HEIGHT VALLOX 130 E UPPER EDGE LOWER EDGE OF BRACK...

Page 15: ...e outlet collars in the ceiling mounting plate enable the mounting of the ductwork before mounting the unit 160 outlet collar female 160 rubber ring outlet Wall mounting plate Ceiling mounting plate o...

Page 16: ...fter the water seal The unit has to be mounted level with the horizontal in order to ensure that condensing water can get out of the unit NOTE If the unit is mounted e g above a hot water accumula tor...

Reviews: