Troubleshooting
MAINTENANCE INSTRUCTIONS
Symptom
Cause
Do this
1
Outdoor air coming to
the dwelling is cold.
• Air cools down in the attic ducts.
• The heat recovery cell is frozen, which is why extract air
cannot heat outdoor air.
• The post-heating radiator does not work.
• The extract air fi lter or cell is clogged.
• The initial adjustment of ventilation has not been done.
• Check the insulation of the attic ducts.
• Check the cleanliness of the fi lters and heat recovery cell.
2
The maintenance
reminder symbol (
) is displayed and
the unit operates
otherwise normally.
• The maintenance reminder lights up the maintenance
reminder symbol in the main display of the control panel
at an interval of circa 4 months (factory setting).
• You may change the interval (see the operating
instructions for control panel, Section 3.2).
• Check the cleanliness of the fi lters and the unit. If needed, clean
or replace the fi lters. Also check the external grille.
• Reset the maintenance reminder symbol (see the operating
instructions for control panel, Section 3.1.).
3
“Exh air sensor
faulty” message is
displayed and the unit
is stopped.
• There is a fault in the freezing protection sensor.
• Contact a maintenance company. Sensor mounting needs to be
checked and the sensor has to be replaced if necessary.
4
“Sup. air sensor
faulty” message is
displayed and the unit
is stopped.
• There is a fault in the supply air sensor.
• Contact a maintenance company. Sensor mounting needs to be
checked and the sensor has to be replaced if necessary.
5
“Ind. air sensor
faulty” message is
displayed and the unit
is stopped.
• There is a fault in the extract air sensor.
• Contact a maintenance company. Sensor mounting needs to be
checked and the sensor has to be replaced if necessary.
6
“Out. air sensor
faulty” message is
displayed and the unit
is stopped.
• There is a fault in the outdoor air sensor.
• Contact a maintenance company. Sensor mounting needs to be
checked and the sensor has to be replaced if necessary.
7
“Cell sensor faulty”
message is displayed
and the unit is
stopped.
• There is a fault in the sensor of the heat recovery cell.
• Contact a maintenance company. Sensor mounting needs to be
checked and corrected if necessary.
8
"Bus fault" message is
displayed and the unit
operates at speed 1
(check the fan speed).
• Wiring fault in the carbon dioxide sensor, in the control
panel or in the humidity sensor, or the cable is of the
wrong type.
• Contact a maintenance company. The connections have to be
checked and corrected if necessary.
9
“Freezing alert”
message is displayed
and the unit is
stopped.
• Antifreeze of the water-circulating radiator is active.
NOTE! If there is no non-freezing solution in the water of
the radiator, the radiator is at risk of freezing.
(Does not apply to the Vallox 096 SE unit)
• Immediately troubleshoot the situation. Consult a maintenance
company to fi nd out if there is any non-freezing solution in the
radiator. Check if the circulation pump is broken, the boiler out
of operation etc. The situation may pass by itself as soon as
supply air temperature exceeds 10 degrees, but do not wait till it
happens.
10
The desired automatic
adjustment does not
stay on.
• There is a fault in the humidity or carbon dioxide sensor.
One of the sensors is broken or missing.
• Contact a maintenance company. Sensor mounting and
connections have to be checked. (Sensors are options.)
11
The fans are not
running and no
indicator light is lit at
the control panel.
• Door switch may be broken or the door is not quite
closed.
• The unit is out of power, for instance because a fuse has
blown.
• The glass tube fuse (located in the control card behind a
protecting plate) protecting the electronics inside the unit
may have blown.
• Check the door switch and fuses. The unit has a T800 mA glass-
tube fuse.
• If needed, contact a maintenance company (for instance to check
the glass tube fuse).
12
The unit does not
obey the control
panel.
• Disconnect the plug of the unit from the wall socket, wait for 30
seconds and put the plug back. If this does not help, contact a
maintenance company.
13
“Carbon dioxide
alarm” message is
displayed and the unit
is stopped.
• Carbon dioxide alarm. Carbon dioxide content has
exceeded 5000 PPM for two minutes. May be caused
by for instance a fi re.
• If there is a fi re, take the necessary steps.
• You can make the unit operational by disconnecting the plug
from the wall socket, waiting for 30 seconds and putting the plug
back.
14
Filter guard symbol
( ) is displayed and
the unit operates
otherwise normally.
• The pressure in the fi lter guard (pressure difference
switch) has risen above the adjustment value or speed is
7 or 8 (option).
• Check the cleanliness of the fi lters and the unit. If needed, clean
or replace the fi lters. Also check the external grille.