
10
Vallox
096
SE
© VALLOX • We reserve the right to make changes without prior notice.
What the units include can vary depending on the sales area.
TECHNICAL DATA
600
Model R
Model L
121
143
143
121
Dimensions and duct outlets
Duct outlets, model R
Inner diameter of female outlet collar
ø 125 mm
1. Supply air to dwelling
2. Extract air from dwelling to unit
3. Exhaust air out
4. Outdoor air to unit
Duct outlets, model L
Inner diameter of female outlet collar
ø 125 mm
1. Exhaust air out
2. Outdoor air to unit
3. Supply air to dwelling
4. Extract air from dwelling to unit
Fan
speeds
(V)
Extract air
fl ow
(l/s)
Combined input
power of fans
W
1
14
12
2
24
21
3
34
29
4
44
42
5
54
65
6
64
96
7
73
130
8
89
223
Supply/extract air volumes
Sound values
0
25
50
75
100
125
150
175
200
225
250
275
300
325
350
375
400
425
450
475
500
0
5
10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
E1
SFP 1,5
SFP 2,0
SFP 1,0
S1
S2
E2 S3
E3
S4
S6
E6
S7
E7
S8
E8
S5
E5
E4
Pa
93
102
298
363
600
141
459
407
430
600
545
55
3
1
4
2
Location of condensing water
outlets, R and L models
Measuring points
Measuring points after the connection
outlet. Fan curves indicate the total
pressure available for duct losses.
Input powers of fans
Model R in
the fi gure
Extract air
Supply air
Recommended
operating range
E = Extract air fan
S = Supply air fan
Input power (total) (W)
Air fl ow (max.) (dm
3
/s)
SFP =
SFP (Specifi c Fan Power) recommended value <2.5 (kW m
3
/s)
At a lower total pressure, SFP will be smaller at this speed.
Volume fl ow rate
Pressure loss in ducts. T
otal pressure.
Sound power level in supply air duct
(one duct) by octave band L
W
, dB
Sound power level in extract air duct
(one duct) by octave band L
W
, dB
ADJUSTMENT POSITION/AIR FLOW dm
3
/s
ADJUSTMENT POSITION/AIR FLOW dm
3
/s
Adjustment position
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Air fl ow dm
3
/s
10,6
25,2
38,1
46,6
53,8
65,6
72,9
76,0
12,0
27,6
36,7
44,2
50,5
61,0
70,4
76,4
Medium
frequen-
cy of the
octave
band
Hz
63
39
52
61
62
64
71
69
68
26
30
40
44
47
53
54
57
125
36
45
51
56
58
62
65
66
24
34
40
46
49
53
57
57
250
41
51
57
60
62
65
67
68
22
33
39
42
45
49
53
54
500
38
50
54
57
60
63
65
66
28
39
44
47
49
53
55
56
1000
34
48
54
57
59
62
64
65
23
36
42
45
48
51
54
55
2000
24
43
50
55
57
61
64
65
13
24
31
35
37
41
43
44
4000
16
32
42
47
49
54
56
58
16
17
21
24
26
30
33
33
8000
21
21
27
34
38
44
48
49
21
21
21
21
21
22
23
24
L
W
,dB
L
WA
, dB(A)
45
57
64
66
69
73
74
74
33
43
49
52
55
59
62
63
39
52
58
61
64
67
69
70
28
39
45
48
51
54
57
57
Sound pressure level dB (A) coming from the unit through the envelope
in the rooms where the unit has been installed
(10m
2
sound absorption)
Vallox 096 SE
ADJUSTMENT POSITION/AIR FLOW dm
3
/s
1
2
3
4
5
6
7
8
14/15 31/30 48/44 60/54 68/62 82/74
92/83
98/89
L
pA
, dB (A)
23
29
35
38
41
44
46
47
Summary of Contents for 096 SE L
Page 16: ...1 09 602E 3 12 2013 PDF...