APPLICATION NOTE AN101
PROTECTING THE 2300 DIGITAL POWER ANALYZER
FROM INDUCTIVE LOADS
101-1. General
The 2300 Series of Digital Power Analyzers is
ideally suited for measuring the power drawn
or supplied by large electric motors,
generators, transformers, or other types of
inductive devices. The testing of highly
inductive loads such as these requires that
precautions be taken to protect the 2300 from
damage due to inductive kickbacks. Very
high voltage spikes may be produced when
the motor or transformer is disconnected from
the source. Spikes may also be produced
when a resistive load is disconnected from an
inductive source, e.g. a transformer or
generator. These spikes can easily exceed the
common mode and series mode specifications
of the 2300.
101-2. Protection Methods
There are two methods of protecting the 2300
from inductive kickbacks. These methods are
described in the following paragraphs.
101-2-1. Switch
Protection
In this method a switch is placed between the
2300 and the inductive load. When
disconnecting, the load switch SW1 should be
opened first. Switch SW2 can now be
opened, disconnecting the 2300 from the
source. Figures 1, 2 and 3 detail this type of
protection for single and three-phase loads.
101-2-2. Spark Gap Protection
In many cases the switch protection method is
not practical. Spark gap protection is the
preferred method of protecting the 2300 from
inductive kickbacks because the protection is
not dependent on the operator. The spark
gap(s) dissipate the energy from the inductive
kickback. Figures 4, 5 and 6 detail this type
of protection for single and three-phase
connected loads. When the source is also
inductive, e.g. a generator, additional spark
gaps should be used. In all cases the spark
gaps should be connected close to the load
(source) and as far from the 2300 as practical.
All connections should be made using heavy
gauge wire. The spark gap voltage rating
should be selected at two to four times the
working voltage, 1500 volts maximum. The
energy rating in joules depends on the load.
For motors, a good rule of thumb is 10 joules
per horsepower. For transformers, the energy
rating can be calculated from the equation:
Where:
Energy =
the stored energy in the inductor in Joules
L =
the inductance in Henries
I =
the current used to charge the inductor
(supply current) in amps
If the inductance of the transformer is
estimated, use a spark gap of higher energy
rating than calculated for a margin of safety.
Spark gaps are available from C.P. Clare,
among others.
)
LI
(
2
1
=
ENERGY
2
Summary of Contents for 2300
Page 3: ...This manual covers the following Valhalla Scientific products Models 2300 2301 2300L and 2301L...
Page 19: ......
Page 20: ......
Page 23: ......
Page 24: ......
Page 26: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 50: ......
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 74: ......
Page 83: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 87: ......
Page 88: ......
Page 91: ......
Page 92: ......
Page 93: ......
Page 95: ......
Page 96: ......
Page 97: ......
Page 98: ......
Page 100: ......
Page 101: ......
Page 103: ......
Page 106: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 113: ......
Page 114: ......
Page 115: ......