Thermo DC 200
Control elements
21
Recalling/erasing preset times
Repeatedly press the
button until the desired memory location is
displayed.
To erase the preset time, press the
button several times until the
time of the day is displayed instead of the memory location.
Programming duration of operating time
The heater must be switched off. Press the
button for 3 seconds -
operating time is flashing - and set the desired operating time (10 to 120
minutes) using the
and
buttons.
Setting the remaining operating time
Set the desired remaining operating time (1 to 120 minutes) using the
and
buttons. The remaining operating time refers to the time the
heater still continues to remain in operation. It can only be changed
while the heater is in operation and the ignition switched off.
Setting the wake-up time
A wake-up time can only be programmed on the standard digital timer.
The wake-up time is not bound to a specific day of the week. Repeatedly
press the
button until the bell symbol
appears on the display.
Set the desired wake-up time using the
and
buttons. The alarm
clock turns off after 5 minutes or when one of the buttons is pressed.
Recalling/erasing the wake-up time
Repeatedly press the
button until the bell symbol
appears on
the display - read off wake-up time. To erase the wake-up time: press
the
button until the bell symbol
is no longer visible on the
display.
Remote control
Possible by means of an optional external "instant heating" button
Vehicles with ADR equipment
On ADR vehicles it is not possible to program a preset starting time. The
remaining time is shown on the display while the heater is in operation.
The clock can be set. The alarm clock function can be programmed on
the standard digital timer.
8.3. Activation via mains power
If you bridge the contacts of the control line, the heating system is acti-
vated when mains power is applied.
8.4. Operation indicator
For monitoring there should be an operation indicator provided at the
vehicle, which displays the status of the switching signal/heating
system.
If the operation indicator is integrated into the power circuit for external
control, it may require a current of max. 250mA. Only suitable lamps for
the voltage range of 18 - 30V are to be used (ref. also para. 8.1, Fig. 11
and 12).
Summary of Contents for THERMO DC 200
Page 4: ...IV Thermo DC 200...
Page 34: ...Technical data Thermo DC 200 30 For notes...
Page 35: ...memos...