DHP-UM-013
Val Controls A/S
•
Limfjordsvej 3
•
DK-6715 Esbjerg N
•
Tel. +45 7547 0600
•
Fax +45 7547 0611
•
www.valcontrols.com
Revision: 4
6/58
3.2.1
FF – Fieldbus Connector
F
B
-P
F
B
-N
F
B
-P
F
B
-N
1
3
2
4
3.2.2
Terminals
See the chart below to see how to connect to the terminals on the positioner.
1+3 and 2+4 is internally connected.
FF-Fieldbus
1.
FB-P
Receive/transmit data line, positive polarity
2.
FB-N
Receive/transmit data line, negative polarity
3.
FB-P
Receive/transmit data line, positive polarity
4.
FB-N
Receive/transmit data line, negative polarity
3.3
Additional IHP24 FF-Fieldbus Menu Function
Internally in IHP24 there is a hardware Foundation Fieldbus module. This module communicates
with the rest of the hardware in IHP24 via a local Modbus interface. This interface needs to run at a
fixed setup ID = 1, Baud rate = 38400, Parity = Even, Stop bits = 1. The communication settings
should always be set to these values.
It is important to set the Baud rate after an “Advanced Reset” of the IHP24.
Advanced menu
Default
Value
Reset Description
6 Modbus
Modbus configuration
1 ID
1
1-247
A
Change the Modbus node ID
2 Baudrate
57600
9600/38400/57600
A
Change the baudrate
3 Parity
Even
No ne/Even/Od d
A
Change the parity
4 Stopbits
1
1-2
A
Change the number of stopbits
3.4
Additional IHP24 FF-Fieldbus Error Codes
No. 801
Fieldbus_OutOfService
Description
Fieldbus AO block out of service. Mode Block is “OOS”
Set the Mode Block to “Auto” or “Cascade”
The device goes to its hardware fail position. All solenoids are de-energized.
Trouble shooting
Set the Device in In Service
Or check the Internal Modbus Menu parameter settings.
ID = 1, Baud rate = 38400, Parity = Even, Stop bits = 1.