3
Specifications
3.1
Electrical specifications for standard configuration
FF-Fieldbus
Interface
FF-Fieldbus - H1 Device Class – Basic Device
Termination
No internal termination
Baud rate
31250 baud
Field bus ID (Node ID)
Node ID 17 – 36 and 223 - 247
Software selectable
Default Node ID 247
Default Tag Name
“Val Controls” can be changed.
Execution Time
-
AI
25 ms
-
AO
31.25 ms
-
DI
25 ms
-
DO
25 ms
-
PID
31.25 ms
-
RATIO
31.25 ms
-
BG
25 ms
-
SC
25 ms
-
ISEL
25 ms
-
LLAG
25 ms
PD_TAG = Modbus_FF
Manufacture Id = 0x000105 hex - Microcyber Inc
Device Type = 0x1001 hex
DEV-Rev = 0x01 hex
DD-Rev=0x01 hex
CF-Rev = 0x01 hex
ITK-Rev = 5.00
DD-File - Tested on the following systems
-
Emerson Delta V version 8.4.2
-
Yokogawa Centum VPR 5.01
-
Honeywell, Experion control system revision 400.2
3.2
Power Ratings
FF-Fieldbus – H1
Power Requirements: 9-32 V
Current Consumption: < 5mA