exists.
FSTATE_VAL_D
[Options]
Description: The preset discrete SP_D value to use
when fault occurs. This value will be used if the I/O
option Fault State to value is selected.
SHED_OPT
[Options]
Description: Defines action to be taken on remote
control device timeout.
ALERT_KEY
[Alarms]
Description: The identification number of the plant
unit. This information may be used in the host for
sorting alarms etc.
BLOCK_ERR
[Diagnostic]
Description: This parameter reflects the error status
associated with the hardware or software components
associated with a block. It is a bit string, so that
multiple errors may be shown.
STRATEGY
[Others]
Description: The strategy field can be used to
identify grouping of blocks. This data is not checked
or processed by the block.
PV_STATE
[Others]
Description: Index to the text describing the states of
a discrete PV.
BKCAL_OUT_D
[Others]
Description: The output value and status provided to
an upstream discrete block. This information is used
to provide bump less transfer to closed loop control.
UPDATE_EVT
[Others]
Description: This alert is generated by any change to
the static data.
BLOCK_ALM
[Others]
Description: The block alarm is used for all
configuration, hardware, and connection failure or
system problems in the block. The cause of the alert
is entered in the sub-code field. The first alert to
become active will set the Active status in the Status
attribute. As soon as the Unreported status is cleared
by the alert reporting task, another block alert may be
reported without clearing the Active status, if the
sub-code has changed.
6.7
Appendix - PID Function Block (PID)
Follows the standard for Fieldbus PID functionality.