background image

Quick Guide  ______________________________________________________________________________  PDT102 

© Vaisala 2015. All rights reserved. __________________________________________________________________ 2 

ELECTRICAL WIRING 

PDT102 with voltage output operates on any supply voltage between 

12...36 VDC drawing less than 10 mA (24 VDC typical). 
Use of a shielded cable, with the shield grounded, is required. Do not connect 

the shield to the transmitter. Maximum cable length for voltage output wiring 

is 30 m (98.4 ft). 

+

+

POWER

SUPPLY

 

Figure 3

 

Voltage Output Wiring 

The voltage required for a 4...20 mA output is dependent on the loop 

resistance of the circuit. Refer to Figure 5 showing the minimum supply 

voltage (Vmin) required for a given Loop Resistance (RL). 

+

R

S

POWER

SUPPLY

 

Figure 4

 

Current Output Wiring 

0

10 12

20

30

36

40

1250

1091
1000

750

500

250

0

545

24

Loop Resistance (Ω)

Supply

Voltage (V)

Vmin = 34V+ [0244A*(R L)]

*includes a 10% safety factor

RL = RS + RW

RL = Loop Resistance (ohms)

RS = Sense Resistance (ohms)

RW = Wire Resistance (ohms)

 

Figure 5

 

Load Limitations 

FRONT ACCESS TEST JACKS (OPTION) 

The front access test jacks provide on-line process reference signal or 

calibration signal without disconnecting power supply wiring. Measurements 

can be made using a standard multimeter. Reference signals through the test 

jacks are made in series for 4...20 mA output and in parallel for voltage 

output. 
Gold plated contacts accept standard 0.08˝ microtip test leads, snapping in 

place for secure measurements. 

PROCESS VALVE ACTUATOR (OPTION) 

The process valve actuator option includes the process valve actuator,  

actuator tool, and 7˝ of silicon tubing. The actuator tool identifies the 

Calibration (CAL) and Monitoring (MON) modes, and has ports for the (HI) 

and (LO) pressure references. From the (OFF) position the actuator tool can 

be inserted and removed. 
-

 

In the CAL mode the PDT102 is isolated from the process and allows 

externally generated test pressure input for calibration. 

-

 

In the MON mode the system pressures can be monitored using a 

handheld pressure instrument without physically unplugging the process 

tubes. In this mode an on-line measurement can be captured. Using the 

front access test jacks, a reference signal can also be captured without 

process interruption. 

CALIBRATION 

Calibration should be performed after installation and after 100 days from 

installation. Yearly recalibration is recommended. 
1.

 

Pneumatically connect the transmitter’s pressure ports to each other. If the 

transmitter has the process valve actuator option, rotate it clockwise 90 

degrees to isolate the PDT102 from the process, and short the HI and LO 

ports on the actuator tool using the silicon tubing supplied. 

2.

 

Measure the analog output of the transmitter to establish the zero offset. 

3.

 

If the reading is not at the middle of the output range (for example, 12 mA 

for 4 … 20 mA output), the zero point of the transmitter has shifted. To 

remove the zero shift, adjust the transmitter as described below. 

ADJUSTMENT 

Note:

 You need a high accuracy pressure standard and high quality electrical 

meter to adjust the PDT102. 
1.

 

Connect the pressure standard to the ports of the PDT102. 

2.

 

Bring the pressure to 0 % of the transmitter’s span (-50 Pa or -0.25 in H

2

O, 

depending on model). 

3.

 

Adjust the zero potentiometer on the front of the transmitter so that the 

analog output value is at the low end of its range. Use a 3/32” or 2.5 mm 

slotted or Phillips screwdriver to turn the potentiometer. 

4.

 

Now bring the pressure to 100 % of the transmitter’s span (+50 Pa or 

+0.25 in H

2

O, depending on model). 

5.

 

Adjust the span potentiometer on the front of the transmitter so that the 

analog output value is at the high end of its range. 

WARRANTY 

For warranty information, visit our Internet pages at: 

www.vaisala.com/warranty

DISPOSAL 

Dispose of the unit according to local regulations. Do not dispose of 

with regular household waste. Recycle all applicable material. 

Reviews: