8. Ensure that the filling in the hole around the sensor is slanted towards the sensor so
that moisture is able to accumulate on top of the sensor.
This is needed for determining salt concentration.
9. Allow to cure.
The cure time depends on the air temperature as well as the filling material used. As the
final curing takes place, use a wire brush to remove any excess filling material from
around the sensor head as well as to roughen the surface. This will best reflect the
surface tension of the surrounding road or runway.
10. Clean DRS511.
a. Remove the protective tape from the sensor head.
b. Clean the tape residue from the sensor head with sanding paper (grade 800).
c. Finalize by cleaning the sensor with a wet wipe.
11. Lead the sensor cable to the weather station enclosure.
a. Pull the cable through the plastic protective ducting.
b. Place the duct into the trench that leads to the weather station enclosure.
The cable is cut to length, but if you have a manhole available, you can leave tooling
allowance in the cable and bury the excess in the hole.
c. Backfill the trench.
12. Use a multimeter again to check that neither the sensor nor the cable were damaged
during installation.
More information
‣
DRI701 wiring for DRS511 and DTS12G (page 70)
Chapter 4 – Installation
45