56
Installation and maintenance instructions 0020257297_06
4.4.2
Side view, right
107
70
41
449
4.4.3
Bottom view
740
180
180
477
106
14
14
270
4.5
Complying with minimum clearances
▶
To guarantee sufficient air flow and to facilitate mainten-
ance work, observe the minimum clearances that are
specified.
▶
Ensure that there is sufficient room to install the hydraulic
lines.
4.5.1
Minimum clearances, ground installation
and flat-roof installation
D
B
A
E
C
Minimum clear-
ance
Heating mode
Heating and cooling
mode
A
100 mm
100 mm
Minimum clear-
ance
Heating mode
Heating and cooling
mode
B
1000 mm
1000 mm
C
200 mm
1)
250 mm
D
500 mm
500 mm
E
600 mm
600 mm
1) 250 mm is recommended for dimension C in order to
guarantee good access during the electrical installation.
4.5.2
Minimum clearances, wall installation
D
B
A
E
C
F
Minimum clear-
ance
Heating mode
Heating and cooling
mode
A
100 mm
100 mm
B
1000 mm
1000 mm
C
200 mm
1)
250 mm
D
500 mm
500 mm
E
600 mm
600 mm
F
300 mm
300 mm
1) 250 mm is recommended for dimension C in order to
guarantee good access during the electrical installation.
4.6
Conditions for the installation type
The product is suitable for these installation types:
–
Ground installation
–
Wall installation
–
Flat-roof installation
The following conditions must be observed for this installa-
tion type:
–
Wall-mounting with the unit mounting bracket from the
accessories is not permitted for products VWL 105/5 and
VWL 125/5.
–
Flat-roof installation is not suitable for extremely cold or
snowy regions.