0020257297_06 Installation and maintenance instructions
79
VWL 35/5
AS 230V
(S2)
VWL 55/5
AS 230V
(S2)
VWL 75/5
AS 230V
(S2)
VWL 105/5
AS 230V
(S2)
VWL 105/5
AS (S2)
VWL 125/5
AS 230V
(S2)
VWL 125/5
AS (S2)
Power consumption,
A35/W18
6.00 A
6.00 A
7.90 A
17.40 A
5.90 A
17.40 A
5.90 A
Cooling output, A35/W7
3.12 kW
3.12 kW
6.17 kW
8.69 kW
8.69 kW
8.69 kW
8.69 kW
Energy efficiency ratio, EER,
EN 14511, A35/W7
2.69
2.69
2.32
2.49
2.49
2.49
2.49
Power consumption, effect-
ive, A35/W7
1.16 kW
1.16 kW
2.66 kW
3.49 kW
3.49 kW
3.49 kW
3.49 kW
Power consumption, A35/W7
5.40 A
5.40 A
7.30 A
15.50 A
5.10 A
15.50 A
5.10 A
Technical data
–
Noise emissions, heating mode
VWL 35/5
AS 230V
(S2)
VWL 55/5
AS 230V
(S2)
VWL 75/5
AS 230V
(S2)
VWL 105/5
AS 230V
(S2)
VWL 105/5
AS (S2)
VWL 125/5
AS 230V
(S2)
VWL 125/5
AS (S2)
Sound power, EN 12102, EN
ISO 9614-1, A7/W35
51 dB(A)
53 dB(A)
54 dB(A)
58 dB(A)
58 dB(A)
59 dB(A)
58 dB(A)
Sound power, EN 12102, EN
ISO 9614-1, A7/W45
51 dB(A)
53 dB(A)
55 dB(A)
59 dB(A)
58 dB(A)
59 dB(A)
59 dB(A)
Sound power, EN 12102, EN
ISO 9614-1, A7/W55
53 dB(A)
54 dB(A)
54 dB(A)
60 dB(A)
60 dB(A)
60 dB(A)
60 dB(A)
Sound power, EN 12102, EN
ISO 9614-1, A-7/W35, noise
reduction mode 40%
52 dB(A)
52 dB(A)
52 dB(A)
57 dB(A)
59 dB(A)
57 dB(A)
59 dB(A)
Sound power, EN 12102, EN
ISO 9614-1, A-7/W35, noise
reduction mode 50%
50 dB(A)
50 dB(A)
50 dB(A)
56 dB(A)
57 dB(A)
56 dB(A)
57 dB(A)
Sound power, EN 12102, EN
ISO 9614-1, A-7/W35, noise
reduction mode 60%
46 dB(A)
46 dB(A)
48 dB(A)
53 dB(A)
55 dB(A)
53 dB(A)
55 dB(A)
Technical data
–
Noise emissions, cooling mode
Validity:
Product with cooling mode
VWL 35/5
AS 230V
(S2)
VWL 55/5
AS 230V
(S2)
VWL 75/5
AS 230V
(S2)
VWL 105/5
AS 230V
(S2)
VWL 105/5
AS (S2)
VWL 125/5
AS 230V
(S2)
VWL 125/5
AS (S2)
Sound power, EN 12102, EN
ISO 9614-1, A35/W18
54 dB(A)
54 dB(A)
56 dB(A)
59 dB(A)
59 dB(A)
59 dB(A)
59 dB(A)
Sound power, EN 12102, EN
ISO 9614-1, A35/W7
54 dB(A)
54 dB(A)
55 dB(A)
58 dB(A)
59 dB(A)
58 dB(A)
59 dB(A)
Summary of Contents for VWL 105/5 AS S2