Installation instructions 0020140122_04

17

4.3.2  Main board

20 mm max.

2

1

Key

Electrical wires

Casing

When you connect the electrical wires to a connector on the 
main electronic board:

 

>

Keep a distance of a maximum of 20 mm between con-
nector and the start of the insulation (2).

 

>

If single core wires are used (1) ensure that they are 
wrapped together in an insulating sheath.

 

>

Fix the cables in the cable-clamps on the unit.

Commissioning

The commissioning should be carried out by a competent 
person approved at the time by the Health and Safety Exec-
utive and in accordance with the current issue of BS6798.

 

>

Completely open all the radiator thermostatic valves in 
the rooms where the room thermostats were been 
installed.

5.1 

Filling

5.1.1  Boiler

Commission the boiler according to the instructions of its 
installation manual.

 

>

Refer to the installer manual.

5.1.2  Heating circuit

 

>

Manually open the different heating circuit valves.

5.2 

Venting

5.2.1  Boiler

Commission the boiler according to the instructions of its 
installation manual.

 

>

Refer to the installer manual.

5.2.2  Heating circuit adjustement

Venting of the heating circuit enables the purging of any air 
in the heating circuit (valves still manually opened).

 

>

Open the different heating circuit air vent.

b

  Caution!

 

>

When venting is complete, close the dif-
ferent heating circuit air vent and valves.

5.3 

Switching on

 

>

Turn on all the appliances that make up the installation 
(see the installation manual(s)). Use the following order:

 

– Control centre

 

– Boiler

5.4 

Multizone specific adjustment

In case of multizone mode selection (rotary switch in pos 
0), the pairing must be made between the room thermo-
stat(s) and control centre in the system heating (one after 
the other).

 

>

Follow the install assistant of the room thermostat “zone 
1”.

 

>

Consult the installation manual of the room thermostat in 
order to carry out the operation.

 

>

Repeat the operation with the room thermostat “zone 2”

5.5 

Restart and check

 

>

Check if all settings have been saved by switching the 
system off and then on to ensure that any adjustments 
operate correctly and check that the appliances operate 
safely.

 

>

Check if the system answers correctly to a demand:

 

– issue a heating demand for the heating zone 1

 

– issue a heating demand for the heating zone 2 (if 

multizone mode is selected)

 

– issue a domestic hot water demand (if DWH tank is 

connected)

User information

At the end of the installation, the installer must:

 

– explain the operation of the appliance and its safety 

devices to the user, if necessary provide a demonstration 
and answer any questions;

 

– give the user all the required documentation,

 

– fill in the documents where necessary;

 

– advise the user of the precautions necessary to prevent 

damage to the system, appliance and the building;

 

– remind the user to service the appliance annually.

Summary of Contents for VR 66/2

Page 1: ...Control Centre VR 66 2 Installation instructions en 0020140122_04 012023 Subject to technical modi cations...

Page 2: ...and Ireland 5 2 3 2 Benchmark 5 2 4 CE label 5 3 Description of the product 6 3 1 Product Overview 6 3 2 Product structure 6 3 2 1 Monozone operation mode 6 3 2 2 Priorities are defined as follows 6...

Page 3: ...risk of severe personal injury e Danger Risk of death from electric shock a Warning Risk of minor personal injury b Caution Risk of material or environmental damage 1 2 Observe other applicable docum...

Page 4: ...pervised not to play with the appliance 2 1 5 Danger of scalding due to the hot water There is a danger of scalding at the hot water draw off points if the hot water temperatures are higher than 60 C...

Page 5: ...ided with the correct equipment for their needs that it is installed commissioned and serviced in accordance with the manufacturer s instructions by a competent person approved at the time by the Heal...

Page 6: ...nder is communicated to the heating appliance The heating appliance boiler then decides whether a hot water request has to be fulfilled and sends a signal to position the 230 V zone valves The initial...

Page 7: ...p heater for domestic hot water 5 Monovalent domestic hot water cylinder 8c Safety assembly for the potable water connection 8f Expansion vessel for potable water 9a Single room temperature control va...

Page 8: ...connections Connect the live wire white or brown of the valve to the L of the CH1 connector Connect the earth wire yellow green of the valve to the earth of the DWH ON connector Connect the neutral w...

Page 9: ...ic hot water 5 Monovalent domestic hot water cylinder 8c Safety assembly for the potable water connection 8f Expansion vessel for potable water 9a Single room temperature control valve thermostatic mo...

Page 10: ...i and open vent boiler The information about the heating or hot water demand is sent by the room thermostat via the control centre to the boiler The VR 66 2 then decides if the hot water demand needs...

Page 11: ...hot water 5 Monovalent domestic hot water cylinder 8c Safety assembly for the potable water connection 8f Expansion vessel for potable water 9a Single room temperature control valve thermostatic moto...

Page 12: ...2 M 9b1 M M 9e M DHW 230 V 230 V 0 24 V L N X1 230 V X12 L N L N BUS 24V RT Burn off X13 Opt 2 X16 Opt 1 X100 X41 X40 X51 X35 X31 X32 0 0 DCF RF AF FB 1 ecoTEC plus X36 M 9b2 M 38 12q BUS PWR LAN VR...

Page 13: ...10e M 3 M 3 9b2 9b1 12 12a 9a 9a 12f 12f 230 V 3 12q 230 V 3 17 1 230 V 3 2 M BUS BUS WLAN LAN Key 1 Heat generator 9a Single room temperature control valve thermostatic motor ised 9b Zone valve 10e...

Page 14: ...X31 X32 0 0 DCF RF AF FB 1 ecoTEC plus X36 9b2 M 12q BUS PWR LAN VR 921 230 V 12a 3 3 Type designation and serial number Data plate location 1 3 4 Data plate description The data plate certifies the c...

Page 15: ...t sources such as radiators chimney walls televisions direct sunlight above a cooking device capable of generating steam and grease in a room with a lot of dust or with a corrosive atmos phere b Cauti...

Page 16: ...r damages to persons or others caused by the incorrect installation of the appliance earthing This includes failure to comply with current standards b Caution These pipes can become very hot which wil...

Page 17: ...close the dif ferent heating circuit air vent and valves 5 3 Switching on Turn on all the appliances that make up the installation see the installation manual s Use the following order Control centre...

Page 18: ...uit of the connected tempera ture sensor NTC in the cylinder Check the cable of the temperature sensor NTC for damage Replace the temperature sensor NTC in the cylinder Red LED flashes slowly 0 5 Hz 1...

Page 19: ...is case dispose of the batteries at a collection point for batteries Prerequisite The batteries can be removed from the product without causing any destruction Otherwise the batteries are disposed of...

Page 20: ...ant de These instructions or parts thereof are protected by copyright and may be reproduced or distributed only with the manufacturer s written consent Subject to technical modifications Supplier Vail...

Reviews: