background image

Multi Split Type Installation Manual

15

EN

9.3.5  Laying the Pipes

•  If installing the rear piping:

•  Place the lid supplied for the hole in the piping and 

insert the coolant pipes with the condensed water 
pipe through the hole.

•  Seal the hole properly after installing the pipes.

•   Carefully bend the installation pipe in the right 

direction.

  Warning!

Danger of breakdowns or malfunction. Danger of 
wear in the coolant pipes.
Bend the pipe carefully to prevent choking or 
breaks.

•  Cut the pipes, leaving enough extra piping hanging 

over to enable the unit to be hooked up at the indoor 
unit joins.

•  Insert the nut in the coolant pipe and carry out the 

flaring.

•  Carefully remove the insulation of the flared 

connections in the indoor unit.

•  Hang the indoor unit on the top edge of the mounting 

plate.

•  Tilt the lower part of the indoor unit forwards and 

insert an auxiliary tool (e.g. a piece of wood) between 
the mounting plate and the unit (see Figure 9.9).

Fig. 9.9  Assembling the indoor unit.

•  Connect the coolant pipes and the condensed water 

hose to the corresponding pipes and installation drain.

•  Insulate the coolant piping correctly and separately. To 

do so, cover any possible cuts with masking tape or 
insulate any bare coolant piping with the 
corresponding insulation material used for cooling.

Fig. 9.10 Laying the Pipes.

Legend

1  Heat-resistant material
2  Drain pipe
3  Coolant pipe
4  Piping support plate
5  Indoor/outdoor electric cable

•  Insert the electric piping, connect the line on the 

indoor unit terminal strip and assemble the cabling 
covering (see section 13).

•  Carry out the start up and the equipment functional 

test (see section 15).

•  Fix the entire indoor unit (see section 9.3.6)..

  Note!

The connections in the flaring should be 
accessible in order to carry out the water 
tightness tests.

•  Install the mounting plate, lining up the holes with the 

help of the plate.

9.3.6  Installation of the Indoor Unit Body

•  Check that the installation has been carried out 

correctly and that there are no leaks (see section 15.1).

•  Securely hang the indoor unit body onto the upper 

notches of the mounting plate. Briefly move the body 
from side to side to verify that it is secure.

•  Lift the body up slightly from underneath, press it 

onto the mounting plate and then lower it vertically. 
The body will fit into the lower supports on the 
mounting plate.

•  Check that the indoor unit is properly secured.
•  In the event that the body does not slot into the 

supports properly, repeat this process.

Installation of the Wall Mounted Indoor Unit  9

Summary of Contents for VA 6-050 MXNHDI

Page 1: ...6 085 MXNHO VA 6 105 MXNHO VA 6 020 MXNHI VA 6 025 MXNHI VA 6 035 MXNHI VA 10 020 MXNHI VA 10 025 MXNHI VA 10 035 MXNHI VA 6 035 MXNHKI VA 6 050 MXNHKI VA 6 035 MXNHDI VA 6 050 MXNHDI climaVAIR DE EN...

Page 2: ...nditioner climaVAIR Multi Split Type EN VA 6 060 MXNHO VA 6 085 MXNHO VA 6 105 MXNHO VA 6 020 MXNHI VA 6 025 MXNHI VA 6 035 MXNHI VA 10 020 MXNHI VA 10 025 MXNHI VA 10 035 MXNHI VA 6 035 MXNHKI VA 6 0...

Page 3: ...nded Installation Process 17 10 4 Installation of the Condensed Water Pipe 17 10 4 1 Handling the Condensed Water Pipe 17 10 4 2 Laying of the Condensed Water Pipe 17 10 5 Installation of the Coolant...

Page 4: ...any service of maintenance operations involving the handling of the refrigerant fluid must have the necessary certification to comply with all local and international regulations 2 Extreme Operating...

Page 5: ...onnections and channels 5 Condensed water drainage pipe 5 1 Wall mounted type Indoor Unit The indoor unit provides acclimatised air inside the room to be acclimatised The dimensions and weights of the...

Page 6: ...Indoor Unit plant Fig 5 4 Dimensions of the Indoor Unit lateral MODEL H I D VA 6 035 MXNHKI 260 60 100mm VA 6 050 MXNHKI 260 60 100mm Table 5 3 Dimensions of the Indoor Unit lateral 5 3 Duct type Ind...

Page 7: ...and Table 5 5 depending on the model please consult the model nameplate The dimensions are given in mm Fig 5 6 Dimensions of the outdoor unit Legend H Height L Length D Depth A Length of valves B Dis...

Page 8: ...Bracket 1 3 Batteries 2 4 Mounting plate 1 5 Piping support plate 1 6 Cushion 4 7 Drainage elbow 1 8 Cover 1 9 Drain tube 1 10 Steel nail cement 6 11 Screw caps 2 12 Wireclamp 1 13 Installation Manua...

Page 9: ...20x1090x500 Net Weight kg 7 6 17 19 14 25 Panel Net Weight kg 2 8 2 8 Air Drop static pressure Pa 20 20 Pipe Connections Pipe Connection liq gas inches 1 4 3 8 1 4 3 8 1 4 1 2 includes connector for O...

Page 10: ...not dispose of it without the proper controls 8 Installation 8 1 Qualification of the Installation Personnel Ensure that this unit is installed by authorised personnel The personnel authorised by Vai...

Page 11: ...um 2 m E Side separation opposite side connections minimum 10 cm F Rear separation minimum 10 cm G Side separation connections side minimum 15 cm H Front separation minimum 60 cm 8 4 General Installat...

Page 12: ...ning the condensed water E Side separation opposite side connections minimum 10 cm F Rear separation minimum 10 cm G Side separation connections side minimum 15 cm H Front separation minimum 60 cm Fig...

Page 13: ...downs or malfunction Ensure that the assembly plate has been correctly levelled Otherwise disassemble the plate and assemble it again correctly 9 3 Installation of the Pipes 9 3 1 Methods for the Corr...

Page 14: ...cted downwards in order to prevent shavings from getting into the pipes Mount the joining tubes carefully ensuring they cannot become displaced Ensure that they will not cause traction in the joins Eq...

Page 15: ...the event of laying the rear piping a suitable hole must be made see Figure 9 7 Drill a hole in accordance with the diameter indicated in Figure 9 7 slightly descending to the outside Fig 9 7 Dimensi...

Page 16: ...y possible cuts with masking tape or insulate any bare coolant piping with the corresponding insulation material used for cooling Fig 9 10 Laying the Pipes Legend 1 Heat resistant material 2 Drain pip...

Page 17: ...ng the indoor unit in the ceiling and to make the connections immediately after mounting the indoor unit This will provide you with more space 10 2 Selecting the Assembly Location Danger of personal i...

Page 18: ...erged in water Avoid installing the condensed water pipe with crimping Install the condensed water pipe in such a way that the distance of its free end from the floor is at least 5 cm Install the cond...

Page 19: ...ng into the pipes Mount the joining tubes carefully ensuring they cannot become displaced Ensure that they will not cause traction in the joins Equip the coolant pipes inflow and outflow separately an...

Page 20: ...sembly in the Ceiling Note The indoor unit is fixed to the ceiling using hooks and hanging bars threaded varilla M10 with its corresponding nuts locknuts and washers Draw the position of the fixing el...

Page 21: ...unit see figure 10 3 Carry out the electrical connection see section 13 Note The connections in the flaring should be accessible in order to carry out the water tightness tests 10 9 Installation of t...

Page 22: ...ossible transmission of vibration and noise installing if necessary anti vibration and soundproofing elements 11 3 Installation of the indoor unit Introduce and twist a nut on each of the rods Raise t...

Page 23: ...sunlight Ensure that the ground has sufficient rigidity to avoid vibrations Check that there is sufficient space to observe the minimum distances see Figure 121 Check that neighbours are not disturbed...

Page 24: ...tion Danger of wear in the coolant pipes Bend the pipe carefully to prevent choking or breaks Cut the pipes leaving enough extra piping hanging over to enable the unit to be hooked up at the outdoor u...

Page 25: ...able Warning Danger of breakdowns or malfunction Size the electric wiring with sufficient capacity Warning Danger of breakdowns or malfunction Compliance with the Standard EN 61000 3 11 Check that the...

Page 26: ...ight of the body by unscrewing it see Figure 13 1 Fig 13 1 Wiring Cover Insert the cable from the outside Using the same hole through which the coolant pipes are installed or are going to be installed...

Page 27: ...d Otherwise the machine will not work Warning Installation should be done with a proper earth connection and each unit should be properly earthed Otherwise the machine will not work Secure the cable i...

Page 28: ...8 0 8 Inteconnect Shield or not YES NO YES YES YES Immediatte residual current protector A 0 03 0 03 0 03 0 03 0 03 0 03 Electric Wiring 13 Supply VA 10 020 MXNHI VA 10 025 MXNHI VA 10 035 MXNHI VA 6...

Page 29: ...ch on the indoor unit with the remote control by pressing the ON button When the unit switches on it automatically goes into direction setup mode To set the direction of the indoor unit just press the...

Page 30: ...B Note In the case of Cassette indoors first take out the panel and filters take off the flaps and the front cover disconnect the swing motor connectors from the PCB and take out the lower part of the...

Page 31: ...d you will hear 4 beeps Release the emergency button Switch on the indoor unit with the remote control by pressing the ON button The LCD display board will display number 1 When the unit switches on i...

Page 32: ...must be periodically checked for leakage Take the necessary actions to ensure these tests are performed and the results correctly logged into the maintenance record of the machine The leakage test mus...

Page 33: ...5 4 If there are no leaks continue Remove the combined meter with the joining hoses and faucets Open the two and three way valves by twisting the rod anticlockwise as far as it will go Fig 15 6 Openin...

Page 34: ...dis connected or wrong address setting of indoor units or faulty power supply or faulty PCB Abnormal communication between wired controller and indoor unit PCB 7 Times Wrong connection or use the wir...

Page 35: ...on troller be disconnected faulty PCB Drainage System abnormal 08 Pump motor disconnected or at wrong position or the float switch broken down or the float switch disconnected or at wrong position Ind...

Page 36: ...or bad air circulation of outdoor unit DC fan motor fault 24 Fan is blocked or the terminal is disconnected from the PCB Faulty 4 way valve switching on 25 Coil of 4 way valve is disconnected or fault...

Page 37: ...ted or broken or at wrong position or short circuit Faulty EEPROM on indoor unit PCB 5 Faulty indoor unit PCB Abnormal communication between indo or and outdoor unit 6 Wrong connection or the wires be...

Page 38: ...fan motors when heating or refrigerant over abundance 10 System low pressure pro tection Low pressure switch is disconnected or low pres sure switch worked or Te too low and faulty outdo or fan motor...

Page 39: ...or faulty SPDU or ISPM 26 Compressor be locked Faulty compressor or SPDU or ISPM 27 Compressor vibration too big Faulty compressor 28 Compressor lose position Faulty SPDU or ISPM 29 Faulty compressor...

Page 40: ...Notes Multi Split Type Installation Manual 39...

Page 41: ......

Reviews: