GAS SUPPLY ADJUSTMENTS
(COMMISSIONING PART II)
Gas Rate THERMOcompact 615/2 E
Natural gas 2H
Main burner jet mark
2)
7/120
Gas Rate
1)
[m
3
/h]
Delivered gas
for G20
Output [kW]
6.5
8.0
10.0
12.0
14.0
15.0
0.8
1.0
1.3
1.4
1.7
1.7
Gas Rate THERMOcompact 620/2 E
Natural gas 2H
Main burner jet mark
2)
7/120
Gas Rate
1)
[m
3
/h]
Delivered gas
per G20
Output [kW]
7.7
8.0
10.0
12.0
14.0
16.0
18.0
20.0
0.9
1.0
1.2
1.4
1.7
1.9
2.1
2.3
1)
15 °C, 1013 mbar, dry
2)
The nozzles are stamped with the mark shown in
this table. The marking corresponds to the nozzle
hole diameter multiplied by 100.
Table G.4: Gas flow rate