M.32
Building circuit: Pressure low
–
Pressure loss in the building circuit
due to leaks or air pockets
–
Building circuit pressure sensor is
defective
–
Check the building circuit for leaks,
top up with heating water and purge
–
Check the plug contact on the PCB
and on the cable harness; check
that the pressure sensor is working
correctly and, if required, replace the
pressure sensor
M.34
Environment circuit: Pressure low
–
Pressure loss in the environment
circuit due to leaks or air pockets
–
Environment circuit pressure sensor
defective
–
Check the environment circuit
for leaks, top up with medium
(brine/water), and purge
–
Check the plug contact on the PCB
and on the cable harness; check
that the pressure sensor is working
correctly and, if required, replace the
pressure sensor
D
Status codes
Code Meaning
Heat pump system
S.34
Heating mode: Frost protection
S.91
Service message: Demo mode
S.100
Standby
S.101
Heating: Compressor switched off
S.102
Heating: Compressor blocked
S.103
Heating: Flow
S.104
Heating: Compressor active
S.107
Heating: Overrun
S.118
Cooling: Flow
S.119
Cooling: Mixer active
S.131
Hot water: Compressor shutdown
S.132
Hot water: Compressor blocked
S.133
Hot water: Flow
S.134
Hot water: Compressor active
S.137
Hot water: Overrun
General
S.201
Check program: Purging of env. circuit active
S.202
Check program: Purging of building circuit active
S.203
Actuator test active
Communication
S.211
Connection error: Display not detected
S.212
Connection error: Control not detected