9 Inspection and maintenance
26
Installation and maintenance instructions geoTHERM 0020250180_00
8.6
Handing the product over to the end user
▶
Explain to the end user how the safety devices work and
where they are located.
▶
Inform the end user how to handle the product.
▶
In particular, draw attention to the safety information
which the end user must follow.
▶
Inform the end user of the necessity to have the product
maintained according to the specified intervals.
▶
Pass all of the instructions and documentation for the
product to the end user for safe-keeping.
9
Inspection and maintenance
9.1
Inspection and maintenance check-list
The following table shows the inspection and maintenance
work that must be carried out at specific intervals.
No. Work
Inspec-
tion
(every
year,
within 24
months
at the
latest)
Main-
tenance
(every
two
years)
1
Check the general condition and
leak-tightness of the heat pump.
x
x
2
Check the pressure in the heating
circuit and, if required, top up the
heating water.
x
x
3
Check the volume and concen-
tration of the brine fluid and the
pressure in the brine circuit.
x
x
4
Check the condensate discharge
of the heat pump for blockages
and remove any dirt or blockages.
x
x
5
Check that the expansion vessel
in the heating circuit operates
correctly.
x
x
6
Check the heat pump for leaks in
the brine and heating circuit and
eliminate these leaks, if required.
x
x
9.2
Observing inspection and maintenance
intervals
Danger!
Risk of damage and personal injury as a
result of neglected and improper inspec-
tion and maintenance.
Inspection and maintenance work must only
be carried out by a competent person.
▶
Carry out the inspection and maintenance
work described on a regular basis and to a
professional standard.
Danger!
Risk of electric shock!
Touching live connections may cause serious
personal injury.
▶
Always switch off all power supply lines
for the heat pump and all components
involved before carrying out any electrical
installation or maintenance work.
▶
Check that there is no voltage.
▶
Secure the power supply against being
switched back on.
9.3
Preparing for inspection and maintenance
9.3.1
Procuring spare parts
The original components of the product were also certified
by the manufacturer as part of the declaration of conformity.
If you use other, non-certified or unauthorised parts during
maintenance or repair work, this may void the conformity of
the product and it will therefore no longer comply with the
applicable standards.
We strongly recommend that you use original spare parts
from the manufacturer as this guarantees fault-free and safe
operation of the product. To receive information about the
available original spare parts, contact the contact address
provided on the reverse of these instructions.
▶
If you require spare parts for maintenance or repair
work, use only the spare parts that are permitted for the
product.
9.3.2
General inspection and maintenance
information
Inspection
The inspection is intended to determine the actual condition
of the respective product and compare it with the target con-
dition. This is done by measuring, checking and observing.
Maintenance
Maintenance is required in order to eliminate any deviations
between the actual condition and the target condition. This is
normally done by cleaning, setting and, if necessary, repla-
cing individual components that are subject to wear.
9.3.3
Checking maintenance messages
If the
symbol is shown in the display, the product requires
maintenance work or the product is in comfort protection
mode.
▶
To obtain further information, call up the
Live Monitor
.
(
→
Page 27)
▶
Carry out the maintenance work that is listed in the table.
Maintenance messages (
→
Page 34)
Conditions
:
Lhm. 37
is displayed
The product is in Comfort protection mode. The product has
detected a permanent fault and continues to run with restric-
ted comfort.
If the temperature sensor for the building circuit outlet, en-
vironment circuit inlet or environment circuit outlet fails, the
product continues to run with replacement values.
▶
To determine which component is defective, read the
fault memory. (
→
Page 27)