Appendix
62
Installation and maintenance instructions flexoTHERM exclusive 0020213395_00
Building circuit/heating circuit
VWF 57/4 230 V
VWF 87/4 230 V
VWF 117/4 230 V
Nominal flow at
Δ
T 5 K
930 l/h
1,450 l/h
1,930 l/h
Max. remaining feed head with
Δ
T 5 K
0.065 MPa
(0.650 bar)
0.044 MPa
(0.440 bar)
0.03 MPa
(0.30 bar)
Nominal flow with
Δ
T 8 K
600 l/h
930 l/h
1,290 l/h
Max. remaining feed head with
Δ
T 8 K
0.068 MPa
(0.680 bar)
0.065 MPa
(0.650 bar)
0.054 MPa
(0.540 bar)
Max. volume flow during continuous op-
eration at the application limits
930 l/h
1,450 l/h
1,930 l/h
Heating pump electrical power consump-
tion for B0/W35
Δ
T 3 K with an external
pressure loss of 250 mbar in the heating
circuit
24 W
37 W
49 W
Performance data
The following performance data is applicable to new products with clean heat exchangers.
VWF 57/4 230 V
VWF 87/4 230 V
VWF 117/4 230 V
Heating output B0/W35
Δ
T 5 K
5.40 kW
8.40 kW
11.50 kW
Power consumption B0/W35
Δ
T 5 K
1.40 kW
2.10 kW
2.80 kW
Output figure B0/W35
Δ
T 5 K/coefficient
of performance EN 14511
4.50
4.40
4.60
Heating output B0/W45
Δ
T 5 K
5.30 kW
8.50 kW
11.40 kW
Power consumption B0/W45
Δ
T 5 K
1.70 kW
2.60 kW
3.50 kW
Output figure B0/W45
Δ
T 5 K/coefficient
of performance EN 14511
3.50
3.50
3.50
Heating output B0/W55
Δ
T 8 K
5.40 kW
8.70 kW
11.70 kW
Power consumption B0/W55
Δ
T 8 K
2.00 kW
3.10 kW
4.10 kW
Output figure B0/W55
Δ
T 8 K/coefficient
of performance EN 14511
2.90
3.00
3.10
Sound power level B0/W35
EN 12102/EN 14511 L
WI
in heating mode
43.8 dB(A)
45.6 dB(A)
48.5 dB(A)
Sound power level B0/W45
EN 12102/EN 14511 L
WI
in heating mode
43.1 dB(A)
48.6 dB(A)
52.7 dB(A)
Sound power level B0/W55
EN 12102/EN 14511 L
WI
in heating mode
44.9 dB(A)
53.5 dB(A)
51.3 dB(A)
Application limits for the heat pump: Heating (heat source = brine)
–
At the same volume flow rates in the heating circuit (
Δ
T 5 K or
Δ
T 8 K) and the brine circuit (
Δ
T 3 K). Operation of the
pump outside the application limits results in the heat pump being switched off by the internal control and safety devices.
–
Application limits for the heat pump: Heating (Brine heat source):
–
B15/W65
–
B25/W59
–
B25/W25
–
B
−
10/W25
–
B
−
10/W60
–
B
−
5/W65