Appendix
0020213395_00 flexoTHERM exclusive Installation and maintenance instructions
39
Setting level
Values
Unit
Increment, select, ex-
planation
Default setting
Setting
Min.
Max.
T.127 High pressure
0
47
bar (abs)
0.1
T.128 Condensation temperature
−
40
70
℃
0.1
T.129 Low pressure
0
22
bar (abs)
0.1
T.130 Evaporation temperature
−
40
90
℃
0.1
T.131 Superheating target value
−
40
90
K
0.1
T.132 Superheating actual value
−
40
90
K
0.1
to 20 K are normal op-
erating parameters
T.134 High-pressure switch
Closed
Open
Closed, Open
Closed
T.135 Temperature switch: Com-
pressor outlet
Closed
Open
Closed, Open
Closed
Further sensors
T.146 Outside temperature
−
40
90
℃
0.1
T.147 DCF status
Current value
No DCF signal
Validate DCF signal
Valid DCF signal
T.148 System temperature
−
40
90
℃
0.1
T.149 MPI input
Closed
Open
Closed, Open
Open
Installer level
→
Configuration
→
Language
Current language
Languages available for
selection
02English
Contact details, Telephone num-
ber
Phone number
0 - 9
Compressor starts at
−
999
0
°min
1
−
60
Max. return temp.
30
70
℃
1
70
Comp. hysteresis
3
15
1
7
Max. rem. feed head
200
1000
mbar
10
1000
Conf. heat. build. pump
Auto
100
%
1
Auto
Conf. cool. build. pump
Auto
100
%
1
Auto
Conf. DHW. build. pump
Auto
100
%
1
Auto
Reset anti-cycl. time, Anti-cycl.
time after pow. supp. switch-on
0
120
min
10
0
Heat. rod outp. range
External
9
kW
230 V
–
External
–
2 kW
–
3.5 kW
–
5.5 kW
–
7 kW
–
9 kW
5.5
1)
See overview of fault codes