51
Installation and maintenance instructions ecoTEC 0020029172_03
10.5
Replacing PCB and display
d
Danger!
Before replacing the component, observe the
safety information in Chapter 10.1.
e
Danger!
Risk of fatal electric shock through contact
with live connections!
Disconnect the boiler from the power mains by
pulling out the mains plug or deenergising the
boiler using an isolating device with a contact
opening of at least 3 mm (e.g. fuses or power
switches). Only after this you may carry out
the installation.
• Comply with the assembly and installation manuals
provided with the spare parts.
Replacing the display or PCB
If you are replacing only one of the two components,
the parameter matching functions automatically. By
switching on the boiler, the new component takes over
the previously set parameters from the unreplaced
component.
Simultaneously replacing display and PCB
If both components are replaced at the same time (in
event of spare part installation) the boiler enters failure
mode when it is started up and displays the fault
message "F.70".
a
Caution!
Risk of damage!
If you replace both components at the same
time, it is essential to check whether the cor-
rect spare part display for this boiler variant is
available. You must not use any other spare
part displays!
• Enter the number of the boiler variant under diagnosis
point "d.93" at the second diagnosis level in
accordance with Table 10.1 (see Chapter 9.1.2).
The PCB is now set to the boiler type and the
parameters of all adjustable diagnosis points
correspond to the factory settings. You can now make
the specific settings for the system.
Boiler
Number of boiler variant (DSN)
ecoTEC VU GB 466/4-5 H
46
Table 10.1 Boiler variant numbers
11 Vaillant
Service
To ensure efficient and reliable operation of your boiler
it is recommended that regular servicing is carried out
by your service provider.
Vaillant Applied System Sales
Vaillant Ltd., Unit D1 Lowfields Business Park, Elland.
West Yorkshire. HX5 9DG
Training
Telephone
01634 292370
Fax
01634 292354
Commercial Service
Telephone
0870 850 3072
Mon - Fri
8.30 - 17.30
Fax
01773 525 946
12 Recycling and disposal
Both the gas fired boiler and its transport packaging
consist mainly of recyclable raw materials.
12.1 Boiler
The boiler and the accessories do not belong to
domestic waste. Make sure the old boiler and any
existing accessories are disposed of properly.
12.2 Packaging
The transport packaging is disposed by the recognised
skilled trade company that installed the boiler.
h
Note!
Please observe the applicable national legal
regulations.
Replacing components 10
Vaillant Service 11
Recycling and disposal 12
Summary of Contents for ecoTEC VU 466/4