Installation and maintenance instructions ecoTEC 0020029172_03
14
Model
Article
number
Connection
Sizes
1
Header
width
A
Header
depth
B
Total
height
C
Insulation
dimensions
To boiler
D
To heating
circuit
E
Height from
floor
F
Maximum
volume
flow m
3
/hr
WH 40
306720
1
1
/
4
" BSP (f)
115
115
500
115/115
280
340
n/a
3.5
WH 95
306721
2" BSP (f)
155
155
750
155/155
470
540
n/a
8
WH 160
306726
DN65
520*
120
1350
220/220
900
900
300
12
WH 280
306725
DN80
600*
160
1390
260/260
930
930
300
21.5
Table 5.2 Low loss headers dimensions
All dimensions in mm
* = distance between flanges
Fig. 5.1 Low loss header
Safety devices
• The outlet of the expansion relief valve must be
suitably terminated in accordance with BS 6798 or
BS 6644.
• The boiler is suitable for connection to plastic
centralheating pipes. In this connection preferably
1.5 m copper pipes should be used prior to the
transition to the plastic pipes for the connection to
the boiler.
• Should a system be found to include non-oxygen
barrier pipe then it is essential that a plate heat
exchanger be installed in between the boiler and the
non-oxygen barrier pipe, thus preventing corrosion. It
is essential that the boiler and the system have
provision for water make up and expansion.
For more detailed information on examples of systems
and system equipment contact your Vaillant sales
support point.
a
Caution!
The following system diagrams are schematic
representations. They cannot be regarded as a
substitute for professional planning! The
system diagrams do not include the isolator
and safety devices that are required to carry
out a professional installation. Observe the
applicable standards and guidelines.
The boiler can be installed in three different
configurations:
• heat only,
• cylinder only, and
• heating and cylinder.
5.1 Heating
mode
In case of only one heating circuit to be operated
downstream of the low loss header, this one can directly
be controlled by the ecoTEC.
A suitable pump can be selected and installed
downstream of the low loss header. You can select a
pump that fits to your system (4 m or 6 m pump or
electronically controlled pump). In case of systems with
multiple circuits please pay additional attention to the
control system accessories.
5 Installation
Summary of Contents for ecoTEC VU 466/4
Page 53: ......
Page 56: ...0020029172_03 GB 062010 Subject to alterations ...