0020308121_04 Installation and maintenance instructions
67
Diagnostics code
Values
Unit
Increment, select, explanation
Setting
Min.
Max.
Factory
Current
D.023
Status of the heat demand
Current value
Off
,
On
D.025
Status of the eBUS control's domestic
hot water demand
Current value
Off
,
On
(Displayed if a control is connected.)
D.026
Function of internal additional relay
D.027
Function of ext. accessory relay 1
D.028
Function of ext. accessory relay 2
1
9
1: Circulation pump
2: External pump
3: Cylinder charging pump
4: Extraction hood
5: External solenoid valve
6: External fault message
8: eBUS remote control
9: Anti-legionella pump
10: Solar cyl. bypass valve
2
D.029
Heating circuit flow rate
Current value
l/h
Current flow rate quantity via the
water flow sensor
D.031
Automatic filling device
Current value
1. Semi-automatic
2. Automatic
D.033
Target fan speed value
Current value
rpm
D.034
Actual fan speed value
Current value
rpm
D.035
3-port valve position
Current value
%
0: Heating position
1: Mid-position
(centre position)
2: DHW
1
D.036
Domestic hot water circuit flow rate
Current value
l/min
Current flow rate quantity via the
water flow sensor impeller
D.039
Cold water temperature, actual value
Current value
℃
Domestic hot water inlet temperature
D.040
Flow temperature actual value
Current value
℃
D.041
Return temperature actual value
Current value
℃
D.043
Heat curve
0.1
4.0
0.05
1.2
D.045
Heat curve offset
5
30
℃
1
21
D.047
Outdoor temperature
Current value
℃
Only in conjunction with an outdoor
temperature sensor.
D.052
Offset: Gas valve stepper motor
101
183
Valid for the first 3 digits of the 3- or
5-digit offset. The offset is specified
on the rear or underside of the gas
valve assembly.
Product-
dependent
20
70
Valid for the last 2 digits of the 3-digit
offset. The offset is specified on the
rear or underside of the gas valve
assembly.
Product-
dependent