Troubleshooting
58
ecoTEC plus installation and maintenance instructions 0020134823_01
14
Display
Meaning
Display value/adjustable value
D.033
Fan speed target value
In rpm
D.034
Fan speed actual value
In rpm
D.039
Solar feed temperature
Actual value in °C
D.040
Flow temperature
Actual value in °C
D.041
Return temperature
Actual value in °C
D.044
digitalised ionisation voltage
Display field 0 to 102,
> 80 no flame
< 40 good flame
D.046
Pump type
0 = Relay with disable facility (default setting)
1 = PWM with disable facility
D.047
Outside temperature
(with weather-controlled Vaillant controller)
Actual value in °C
D.050
Offset for minimum speed
Adjustment range in rpm: 0 to 3000 (factory set nominal value)
D.051
Offset for maximum speed
Adjustment range in rpm: - 990 to 0 (factory set nominal value)
D.060
Number of temperature limiter shutdowns
Number
D.061
Number of ignition device cutoffs
Number of unsuccessful ignitions in the last attempt
D.064
Average ignition time
In seconds
D.065
Maximum ignition time
In seconds
D.067
Remaining burner anti-cycling time
In minutes
D.068
Unsuccessful ignitions at 1st attempt
Number
D.069
Unsuccessful ignitions at 2nd attempt
Number
D.071
Target value maximum heating flow temperature
Adjustment range in °C: 40 to 85 (factory setting: 75)
D.072
Internal pump overrun after
Adjustment range in min: 0 to 10 (default setting: 2)
D.076
UNit variant (display)(device specific number)
82 = VU GB 806/5-5
81 = VU GB 1006/5-5
80 = VU GB 1206/5-5
D.077
Partial load for cylinder charging
in kW
D.080
Operating hours, heating
In hours (h)
D.081
Operating hours, hot water generation
In hours (h)
D.082
Number of burner start-ups in heating mode
Number
D.083
Number of burner start-ups in hot water mode
Number
D.084
Maintenance indicator: Number of hours until the next
maintenance
Adjustment range: 0 to 3010 h and "-" for deactivated
(Factory setting: "-")
D.090
Status of digital controller
1 = Recognised, 0 = Not recognised
D.091
Status DCF with external sensor connected
0 = No reception, 1 = Reception, 2 = Synchronised, 3 = Valid
D.093
DSN unit variant setting
Adjustment range: 0 to 99
D.094
Delete fault history
1 = Delete fault list
D.095
Software version eBUS components
1. PCB
2. Display
4. VR34
D.096
Factory setting
1 = Reset all adjustable parameters to factory setting
13.2 Diagnostics codes at Installer level
(continued)