Start-up
ecoTEC plus installation and maintenance instructions 0020134823_01
37
11
11.2.4 Heating partial load
The heating partial load of the Vaillant ecoTEC plus boiler is
factory set to "auto". This means that the boiler independ-
ently determines the optimum heating output depending on
the current heat demand of the system. A setting is nor-
mally no longer required. The setting can also be changed
at a later point using diagnostics code D.000.
11.2.5 Auxiliary relay
and multi-functional module
Additional components that are attached to the boiler can
be adjusted directly here.
This setting can be changed using diagnostics codes D.026,
D.027 and D.028.
11.2.6 Competent person telephone number
You can store your telephone number in the unit menu.
The operator can display this number in the information
menu. The telephone numbers can be up to 16 digits long
and must not contain any spaces. If the telephone number
is shorter, end the entry after the last digit by pressing the
right-hand selection button.
All of the digits to the right will be deleted.
11.2.7 Ending the installation assistant
If you have successfully run through and confirmed the
installation assistant, it will not start up automatically next
time the unit is switched on.
11.2.8 Restarting the installation assistant
You can restart the installation assistant any time by calling
it up manually in the menu.
Menu ¬ Installer level ¬ Installation assistant
11.3
Appliance configuration and diagnostics
menu
If you have already filled and purged the heating installa-
tion and have ended the installation assistant but wish to
set the most important system parameters again, you can
also call up the "Appliance configuration" menu point.
Menu ¬ Installer level ¬ Appliance configuration
All of the setting options for more complex systems can be
found in the diagnostics menu (
¬ section 12
).
Menu ¬ Installer level ¬ Diagnostics menu
11.4
Using test programmes
In addition to the installation assistant, you can also call up
other test programmes for start-up.
Menu ¬ Installer level ¬ Test programmes
There, you can not only find the function menu
(
¬ section 13.3
) and an electronics self-test
(
¬ section 13.3.1
) but also the check programmes.
Menu ¬ Installer level ¬ Test programmes ¬
Check programmes
By activating various check programmes, you can trigger
special functions on the boilers.
The following four check programmes are available:
Display
Meaning
P.0
1)
Purging check programme:
The heating circuit and the hot water circuit are purged
via the automatic purging valve (the cap of the auto-
matic purging valve must be released).
1 x right-hand selection button ("
->
"): Start purg-
ing heating
circuit
2 x right-hand selection button ("
->
"): Start purg-
ing hot
water
circuit
1 x left-hand selection button ("Cancel"): Exit purging
programme
The heating pump is timed
Note:
Purging programme runs for 6.5 minutes.
P.1
Maximum load check programme:
After successful ignition, the boiler is operated at maxi-
mum heat input.
P.2
Minimum load check programme:
After successful ignition, the boiler is operated at mini-
mum heat input.
P.6
Filling mode check programme:
The diverter valve (VUV) is moved to the mid-position.
The burner and pump are switched off (to fill or drain
the boiler).
11.1
Overview of the check programmes
1)
Purging the heating circuit:
Diverter valve in heating position, actuation of the heating
pump for 15 cycles: 15 s on, 10 s off. Display: "Active heating
circuit".
Purge hot water circuit:
After the above-mentioned cycles have passed or after repeated
confirmation using the right-hand selection button: diverter
valve in hot water position, actuation of heating pump as above.
Display: "Active hot water circuit".
Starting check programmes
Menu ¬ Installer level ¬ Test programmes ¬
Check programmes