Appendix

12

Operating instructions ecoTEC exclusive 0020193967_01

Appendix
A

Operator level

overview

Setting level

Values

Unit

Increment, select

Default
setting

Min.

Max.

Water pressure

Water pressure

Current value

bar

Live monitor

Status

Current value

Information

Contact details

Phone number

Serial number

Permanent value

Display contrast

Current value

1

25

15

40

comDIALOG

Current value

No function

Basic settings

Language

Current language

Languages available for selection

Country-
specific

Green iQ

Current value

On, Off

On

Display contrast

Current value

1

25

15

40

Resets

Reset anti-cycl. time

Current value

min

B

Troubleshooting

Fault

Cause

Measure

Product does not start
up:

No hot water

Heating remains cold

The gas isolator cock installed on-site and/or the gas
isolator cock on the product is closed.

Open both gas isolator cocks.

The cold water stop valve is closed.

Open the cold water stop valve.

The power supply in the building is disconnected.

Check the fuse in the building. The product
switches on automatically when the power is
restored.

The product is switched off.

Switch on the product (

"Switching on the

product" section).

The heating flow temperature is set too low or to the

Heating off

position, and/or the hot water temperature

is set too low.

Set the heating flow temperature and hot water
temperature (

"Setting the heating flow temper-

ature" section/

"Setting the hot water temperat-

ure" section).

The system pressure is insufficient.
Low water pressure in the heating installation (fault mes-
sage:

F.22

).

Fill the heating installation (

"Filling the heating

installation" section).

There is air in the heating installation.

Have your competent person purge the heating
installation.

After three unsuccessful attempts to ignite the flame, the
product switches to fault mode (fault message: F.

28

).

Press the reset button for one second. The
product makes another attempt to ignite the
flame.
If you have been unable to eliminate the ignition
fault after three reset attempts, consult a com-
petent person.

Summary of Contents for ecoTEC exclusive 627

Page 1: ...TEC exclusive 627 VU 256 5 7 H GB 835 VUW 356 5 7 H GB 843 VUW 436 5 7 H GB GB IE Publisher manufacturer Vaillant GmbH Berghauser Str 40 D 42859 Remscheid Tel 49 21 91 18 0 Fax 49 21 91 18 2810 info v...

Page 2: ...e product 8 4 9 Setting the language 8 4 10 Setting the domestic hot water temperature 8 4 11 Switching Comfort mode on and off 8 4 12 Setting the heating flow temperature 8 4 13 Switching Green iQ mo...

Page 3: ...children unless they are supervised Any other use that is not specified in these instructions or use beyond that specified in this document shall be considered improper use Any direct commercial or in...

Page 4: ...y of the product 1 3 7 Risk of poisoning caused by insufficient combustion air supply Conditions Open flued operation Ensure that there is a sufficient combus tion air supply 1 3 8 Risk of corrosion d...

Page 5: ...exclusive 0010017065 47 044 67 3 Product description 3 1 Product design 1 2 3 1 Control elements 2 Plate with serial number on the rear 3 Front flap 3 2 Control elements 50 5 4 3 2 1 1 On off button 2...

Page 6: ...eneration equipment ecoTEC exclusive Product description Information on the identification plate Meaning 2H G20 20 mbar 2 0 kPa Gas group and gas connection pressure as set at the factory ww yyyy Date...

Page 7: ...ls Not pressing any button for longer than 15 minutes If there is an error message present the basic displays switches to the error message 4 3 Menu display Xxxx Xxxxxxxxxxx Xxxx Xxxxxxx Xxxxxxxxxx xx...

Page 8: ...Comfort mode on and off Applicability Product with integrated hot water generation Note Comfort mode immediately supplies hot water at the required temperature without you having to wait for the wate...

Page 9: ...e installation with suf ficient heating water the display automatically disappears after 20 seconds 4 14 2 Filling the heating installation Caution Risk of material damage due to heating water that is...

Page 10: ...nsure that the heating installation remains in operation and that all rooms are sufficiently heated even when you are away Note To keep the frost protection devices active you should switch your produ...

Page 11: ...disposal of the packaging If the product is identified with this symbol In this case do not dispose of the product with the household waste Instead hand in the product to a collection centre for waste...

Page 12: ...op valve The power supply in the building is disconnected Check the fuse in the building The product switches on automatically when the power is restored The product is switched off Switch on the prod...