19
INSTALLATION OF THE TELESCOPIC HORIZONTAL AIR/FLUE DUCT
(TOP OUTLET)
• Once the position of the flue exit
hole has been determined, the
hole should be cut through the
wall using a core drill of 125 mm
diameter.
Note: If access can be gained to
the proposed flue exit point from
outside the dwelling, the hole can
be cut with a 107 mm core drill
and the flue external wall seal
fitted from outside the dwelling.
• Measure the distance from the
outside face of the wall to the
centre of the fan outlet on the
boiler (fig. 3.16).
This is dimension A.
• Adjust the air duct and flue duct
to the lengths shown in (fig.
3.17).
• Secure the air duct sections
together by drilling a 3 mm
diameter hole through the location
hole in the end of the outer air
duct (
1
). (Ensure that the drill does
not pierce the inner flue duct).
Secure the air ducts together using
the screw (
1
) provided. Place the
adhesive tape (
2
) across the gap
in the telescopic extensions.
(fig. 3.17)
• All flue sockets should point
towards the terminal.
• Care should be taken not to
scratch the white surface of the air
duct.
• If the installation requires the use
of air/flue duct extensions,
additional bends or elbows refer
to the sections on pages 31 - 35.
*
Fig. 3.15
LAS Euro B/S 077/1
87
A
87
A
*
Fig. 3.16
LAS Euro B/S 078/0
1
2
A + 22 mm
Fig. 3.17
Rear exit
Side exit
*
= 190 mm ecoMAX combination and system boilers
*
= 176 mm ecoMAX pro and ecoTEC plus open vent
*
= 125 mm ecoTEC plus system & combination
*
= 190 mm ecoMAX
combination and system boilers
*
= 176 mm ecoMAX pro and ecoTEC plus
open vent
*
= 125 mm ecoTEC plus
system & combination
PAR
T 1 CONCENTRIC 60/100
834449_09GB_082006.qxd 10.08.2006 12:20 Seite 19
Supplied by HeatingSpares247.com
Summary of Contents for eco TEC plus 415
Page 47: ...Installation and Servicing ecoTEC plus 47 Appendix 14 Supplied by HeatingSpares247 com...
Page 48: ...Installation and Servicing ecoTEC plus 48 Supplied by HeatingSpares247 com...
Page 49: ...Installation and Servicing ecoTEC plus 49 Supplied by HeatingSpares247 com...
Page 50: ...Installation and Servicing ecoTEC plus 50 Notes Supplied by HeatingSpares247 com...
Page 51: ...Installation and Servicing ecoTEC plus 51 Notes Supplied by HeatingSpares247 com...
Page 52: ...0020020828_02 GB 08 2006 Subject to alteration Supplied by HeatingSpares247 com...
Page 54: ...834449_09GB_082006 qxd 10 08 2006 12 20 Seite 2 Supplied by HeatingSpares247 com...
Page 88: ...36 834449_09GB_082006 qxd 10 08 2006 12 20 Seite 36 Supplied by HeatingSpares247 com...
Page 112: ...60 834449_09GB_082006 qxd 10 08 2006 12 20 Seite 60 Supplied by HeatingSpares247 com...
Page 113: ...61 834449_09GB_082006 qxd 10 08 2006 12 20 Seite 61 Supplied by HeatingSpares247 com...
Page 114: ...62 834449_09GB_082006 qxd 10 08 2006 12 20 Seite 62 Supplied by HeatingSpares247 com...
Page 115: ...63 834449_09GB_082006 qxd 10 08 2006 12 20 Seite 63 Supplied by HeatingSpares247 com...
Page 118: ...Supplied by HeatingSpares247 com...
Page 120: ...0020010870 01 GB 03 2006 2 Supplied by HeatingSpares247 com...
Page 138: ...0020010870 01 GB 03 2006 20 Supplied by HeatingSpares247 com...
Page 158: ...Notes 0020010870 01 GB 03 2006 40 Supplied by HeatingSpares247 com...
Page 159: ...Supplied by HeatingSpares247 com...
Page 171: ...Instructions for Use ecoTEC plus 11 Supplied by HeatingSpares247 com...
Page 172: ...0020020829_02 GB 08 2006 Subject to alteration Supplied by HeatingSpares247 com...