0000137936
rev. 6.1
7
Modbus communication connection
(only if present)
pH Setpoint reading example:
ADDR
FUNC
DATA
start
Addr HI
DATA
start
Addr LO
DATA
bit # HI
DATA
bit # LO
CRC HI
CRC LO
0X01
0X03
0X04
0X4C
0X00
0X01
0X44
0XED
pH Setpoint writing example:
ADDR
FUNC
DATA
start
Addr HI
DATA
start
Addr LO
DATA
bit # HI
DATA
bit # LO
CRC HI
CRC LO
0X01
0X06
0X04
0X4C
0X02
0X8A
0XC9
0XEA
pH Setpoint applying example:
ADDR
FUNC
DATA
start
Addr HI
DATA
start
Addr LO
DATA
bit # HI
DATA
bit # LO
CRC HI
CRC LO
0X01
0X06
0X0F
0XA0
0X00
0X02
0X0B
0X3D
Remote Start/Stop function:
when the system is stopped by remote the display shows
Std-By (
on all the
screens
),
following the examples to set start and stop by Modbus.
Remote start example:
ADDR
FUNC
DATA
start
Addr HI
DATA
start
Addr LO
DATA
bit # HI
DATA
bit # LO
CRC HI
CRC LO
0X01
0X06
0X04
0X6E
0x00
0X00
0xE9
0x27
Remote stop example:
ADDR
FUNC
DATA
start
Addr HI
DATA
start
Addr LO
DATA
bit # HI
DATA
bit # LO
CRC HI
CRC LO
0X01
0X06
0X04
0X6E
0X00
0X01
0x28
0xE7
Default parameter is OFF (off= Start), the system is set ON by Modbus command.
ON
1
SW
ModBus connection
Pin N°
Description
1
T+R+
2
T-R-
3
GND
4
Not used
SW)
Leave the SWITCH on the “1” position. This switch is
intended to improve the communication and to reduce noise in
installations with very long cables (>50m). If you have long cables
and are facing communication problems, you can try to solve the
problem, sliding the IMPEDANCE MATCHING SWITCH to the
“ON” position only for the first and the last device present on the
bus. (i.e. the two devices farther away from each other). Leave
instead the IMPEDANCE MATCHING SWITCH on the “1”
position for all the other intermediate devices along the bus.