In areas where equipment sensitive to corrosion is installed or kept, use of Halogen free cables should
be considered to avoid corrosive smoke in case of a fire, as far as is practicable. This is according to IEC
60754-1.
6.5.3 Low smoke emission
Use of cables with low emission of smoke in case of a fire, should be considered for all indoor
installations. This is according to IEC 61034.
6.5.4 Specifications cables inputs and outputs SDB-3
Make sure that the cables you are using for power supply to the SDB-3, Modbus, Analog 4-20mA,
Ethernet, NMEA and Digital Output signal or the optional analog outputs, meet with the following
specification:
Description:
Cable specification:
Power supply 115/230VAC (single phase):
3 x 1.5 mm²
Screened
Modbus, RS485:
1 x 2 x 0.75 mm²
Twisted pair
Individually screened
Braid shielded
4-20mA analog output signal (optional):
3 x 2 x 0.75 mm²
Twisted pair
Individually screened
Braid shielded
Connection cable Ethernet:
CAT5e, RJ45 plug
Braid shielded
NMEA, RS485:
1 x 2 x 0.75 mm²
Twisted pair
Individually screened
Braid shielded
Digital output:
1 x 1 x 0.75 mm²
Twisted pair
Individually screened
Braid shielded
Earth cable SDB-3 enclosure
1 x 1.5 mm²
Single core