nx interface
vacon • 25
24-hour s358 (0)40 837 1150 • Email: [email protected]
7
Command
ControlWord
Description
Prepare READY
0006hex
Set Statemachine to ”Ready To Switch ON” state
Prepare RUN
0007hex
Set Statemachine to “Switched ON” state
RUN
000Fhex
Start motor if ”Fieldbus” is the active control
place
STOP
0007hex
Stop motor
FAULT RESET (step 1)
FAULT RESET (step 2)
bit 7 = 0
bit 7 = 1
Rising edge to bit 7
vl_target_velocity
The vl_target_velocity is the required speed reference to the frequency converter.
The unit is RPM.
vl_control_effort
The vl_control_effort is the actual speed of the motor.
The unit is RPM.